title: "Problem set 8: stability, inverter-based resources and distribution"
heading: "Problem set 8: the swing equation, the equal-area criterion, multimachine oscillations, low-inertia grids, and distribution feeders and power quality"
eyebrow: S10 · Problem set 8
type: problems
---

::: hook
These problems cover lessons 43 to 47: rotor angles, synchronizing power and swing frequencies, critical clearing angles and times, two-machine and interarea modes with their damping, inertia, ROCOF and short-circuit ratio on grids with inverter-based resources, and feeder voltage, harmonics, resonance and reliability on distribution systems.
:::

::: pool
pick: 12

::: check
kind: parts
given: P = 0.5 | 0.9 | 1.2; M = 1.6 | 2.4; H = 3 | 6

## A machine with H = {H} s delivers {P} pu with $P_{max}$ = {M} pu.

::: part
answer: asin(P/M)*180/pi
unit: °
tolerance: 0.5%

### Equilibrium angle?

::: misses
- [any] $\sin^{-1}(P/P_{max})$.
:::
:::

::: part
answer: M*cos(asin(P/M))
tolerance: 0.5%

### Synchronizing coefficient?

::: misses
- [any] $P_{max}\cos\delta_0$.
:::
:::

::: part
answer: sqrt(2*pi*60*M*cos(asin(P/M))/(2*H))/(2*pi)
unit: Hz
tolerance: 0.5%

### Swing frequency?

::: misses
- [any] $\sqrt{\omega_sP_s/2H}/2\pi$.
:::
:::
:::

::: check
kind: parts
given: H = 2.5 | 5; S = 150 | 600; B = 100 | 1000; P = 0.6 | 1; t = 0.06 | 0.12

## A {S} MVA machine with H = {H} s on its rating, delivering {P} pu when a fault drops its output to zero.

::: part
answer: H*S
unit: MJ
tolerance: 0.5%

### Stored energy?

::: misses
- [any] HS.
:::
:::

::: part
answer: H*S/B
unit: s
tolerance: 0.5%

### H on a {B} MVA base?

::: misses
- [any] $HS/S_\text{base}$.
:::
:::

::: part
answer: 2*pi*60*P/(4*H)*t^2*180/pi
unit: °
tolerance: 0.5%

### Angle advance in {t} s?

::: misses
- [any] $\frac{\omega_sP_m}{4H}t^2$.
:::
:::
:::

::: check
kind: parts
given: P = 0.5 | 0.8; M = 1.8 | 2.4; H = 3 | 6

## A zero-transfer fault on a machine at {P} pu, $P_{max}$ = {M}, H = {H} s, cleared with the network unchanged.

::: part
answer: acos((pi - 2*asin(P/M))*(P/M) - cos(asin(P/M)))*180/pi
unit: °
tolerance: 0.5%

### Critical clearing angle?

::: misses
- [any] $\cos\delta_c = (\pi - 2\delta_0)\sin\delta_0 - \cos\delta_0$.
:::
:::

::: part
answer: sqrt(4*H*(acos((pi - 2*asin(P/M))*(P/M) - cos(asin(P/M))) - asin(P/M))/(2*pi*60*P))
unit: s
tolerance: 0.5%

### Critical clearing time?

::: misses
- [any] $\sqrt{4H(\delta_c - \delta_0)/\omega_sP_m}$.
:::
:::
:::

::: check
kind: parts
given: P = 0.6 | 1; M = 1.6 | 2.2; c = 60 | 85

## After clearing at {c}° the curve is {M} sin δ with $P_m$ = {P}; the machine started at its equilibrium on the same curve.

::: part
answer: P*(c*pi/180 - asin(P/M))
tolerance: 0.5%

### Accelerating area for a zero-transfer fault?

::: misses
- [any] $P_m(\delta_c - \delta_0)$.
:::
:::

::: part
answer: M*(cos(c*pi/180) - cos(pi - asin(P/M))) - P*(pi - asin(P/M) - c*pi/180)
tolerance: 0.5%

### Available decelerating area?

::: misses
- [any] Integrate to $\pi - \delta_0$.
:::
:::
:::

::: check
kind: parts
given: r = 0.2 | 0.3; s = 0.7 | 0.8; P = 0.8 | 1

## $P_{max}$ = 2 before the fault, {r} of it during, {s} of it after; $P_m$ = {P}.

::: part
answer: 180 - asin(P/(2*s))*180/pi
unit: °
tolerance: 0.5%

### Post-fault unstable equilibrium?

::: misses
- [any] $\pi - \sin^{-1}(P_m/P_{max,3})$.
:::
:::

::: part
answer: acos((P/2*((pi - asin(P/(2*s))) - asin(P/2)) + s*cos(pi - asin(P/(2*s))) - r*cos(asin(P/2)))/(s - r))*180/pi
unit: °
tolerance: 0.5%

### Critical clearing angle?

::: misses
- [any] General formula.
:::
:::
:::

::: check
kind: parts
given: a = 3 | 40; b = 5 | 60; P = 1 | 2.5; s = 0.1 | 0.4; w = 3 | 6

## Two machines with H = {a} s and {b} s, $P_s$ = {P}; a mode at $-\given{s} \pm j\given{w}$.

::: part
answer: a*b/(a + b)
unit: s
tolerance: 0.5%

### $H_{eq}$?

::: misses
- [any] $H_1H_2/(H_1 + H_2)$.
:::
:::

::: part
answer: sqrt(2*pi*60*P*(a + b)/(2*a*b))/(2*pi)
unit: Hz
tolerance: 0.5%

### Swing frequency?

::: misses
- [any] $\sqrt{\omega_sP_s/2H_{eq}}/2\pi$.
:::
:::

::: part
answer: 100*s/sqrt(s^2 + w^2)
unit: %
tolerance: 0.5%

### Damping ratio of the mode?

::: misses
- [any] $\sigma/\sqrt{\sigma^2 + \omega^2}$.
:::
:::
:::

::: check
kind: parts
given: H = 4 | 6; s = 0.3 | 0.6; P = 1 | 2; S = 40 | 90

## A {S} GW system whose synchronous fleet has H = {H} s; {s} of generation becomes inverter-based. It loses {P} GW.

::: part
answer: H*(1 - s)
unit: s
tolerance: 0.5%

### System H?

::: misses
- [any] $H(1 - s)$.
:::
:::

::: part
answer: P*60/(2*H*(1 - s)*S)
unit: Hz/s
tolerance: 0.5%

### ROCOF?

::: misses
- [any] $\Delta Pf_0/(2HS)$.
:::
:::
:::

::: check
kind: parts
given: S = 600 | 2500; P = 150 | 500; V = 115 | 230; k = 1.1 | 1.4

## A {P} MW inverter plant (fault current {k} × rated) at a {V} kV bus with a {S} MVA short-circuit level.

::: part
answer: S/P
tolerance: 0.5%

### SCR?

::: misses
- [any] $S_{sc}/P$.
:::
:::

::: part
answer: k*P*1e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

### Its fault contribution?

::: misses
- [any] k × rated current.
:::
:::
:::

::: check
kind: parts
given: H = 3 | 8; S = 50 | 250; r = 0.2 | 0.8; P = 5 | 7; T = 30 | 50; G = 1.5 | 2.5; q = 0.5 | 0.7

## An inverter of {S} MW emulating H = {H} s at {r} Hz/s; a {T} GW system with H = {G} s losing {P} GW with ROCOF capped at {q} Hz/s.

::: part
answer: 2*H*S*r/60
unit: MW
tolerance: 0.5%

### Synthetic inertia power?

::: misses
- [any] $2HS\dot{f}/f_0$.
:::
:::

::: part
answer: P*1000 - 2*G*T*1000*q/60
unit: MW
tolerance: 0.5%

### Fast frequency response needed?

::: misses
- [any] Deficit minus what inertia supplies.
:::
:::
:::

::: check
kind: parts
given: L = 3 | 8; r = 0.25 | 0.4; x = 0.35 | 0.5; P = 3 | 6; f = 0.85 | 0.95; V = 12.47 | 24.9

## A {V} kV feeder {L} km long, z = {r} + j{x} Ω/km, carrying {P} MW at {f} pf.

::: part
answer: 100*sqrt(3)*P*1e6/(sqrt(3)*V*1e3*f)*(r*L*f + x*L*sqrt(1 - f^2))/(V*1e3)
unit: %
tolerance: 0.5%

### Drop with the load lumped at the end?

::: misses
- [any] $\sqrt{3}I(R\cos\phi + X\sin\phi)$.
:::
:::

::: part
answer: 50*sqrt(3)*P*1e6/(sqrt(3)*V*1e3*f)*(r*L*f + x*L*sqrt(1 - f^2))/(V*1e3)
unit: %
tolerance: 0.5%

### With the load spread evenly?

::: misses
- [any] Half.
:::
:::
:::

::: check
kind: parts
given: a = 12 | 30; b = 8 | 18; c = 4 | 9; I = 80 | 160; S = 50 | 200; Q = 2 | 6

## A {I} A fundamental with {a}, {b} and {c} A of 3rd, 5th and 7th harmonics; a {Q} Mvar capacitor at a {S} MVA bus.

::: part
answer: 100*sqrt(a^2 + b^2 + c^2)/I
unit: %
tolerance: 0.5%

### THD?

::: misses
- [any] Root-sum-square over the fundamental.
:::
:::

::: part
answer: 3*a
unit: A
tolerance: 0.5%

### Neutral third-harmonic current in a balanced set?

::: misses
- [any] 3 × per phase.
:::
:::

::: part
answer: sqrt(S/Q)
tolerance: 0.5%

### Resonant harmonic order?

::: misses
- [any] $\sqrt{S_{sc}/Q}$.
:::
:::
:::

::: check
kind: parts
given: N = 20000 | 80000; m = 9000 | 50000; k = 45 | 120; R = 1 | 2.5; X = 1.5 | 3; P = 1 | 2.5; Q = 0.3 | 0.9; V = 12.47 | 34.5

## A utility of {N} customers with {m} interruptions averaging {k} minutes; and a DG exporting {P} MW, absorbing {Q} Mvar, at the end of {R} + j{X} Ω at {V} kV.

::: part
answer: m*k/N
unit: min
tolerance: 0.5%

### SAIDI?

::: misses
- [any] Customer-minutes over customers.
:::
:::

::: part
answer: m/N
tolerance: 0.5%

### SAIFI?

::: misses
- [any] Interruptions over customers.
:::
:::

::: part
answer: 100*(R*P - X*Q)/V^2
unit: %
tolerance: 0.5%

### Voltage change at the DG?

::: misses
- [any] $(RP - XQ)/V^2$.
:::
:::
:::

::: check
kind: parts
given: H = 3 | 5 | 8; M = 2 | 2.5; a = 0.8 | 1.2; b = 1.6 | 1.8

## A unit with H = {H} s and $P_\max$ = {M} pu goes from {a} pu to {b} pu of output (60 Hz).

::: part
answer: sqrt(377*sqrt(M^2 - a^2)/(2*H))/(2*pi)
unit: Hz
tolerance: 0.5%

### What was its swing frequency?

::: misses
- [any] $\frac{1}{2\pi}\sqrt{\omega_s\sqrt{P_\max^2 - P^2}/2H}$.
:::
:::

::: part
answer: sqrt(377*sqrt(M^2 - b^2)/(2*H))/(2*pi)
unit: Hz
tolerance: 0.5%

### What is it now?

::: misses
- [any] Same formula at the new output.
:::
:::
:::

::: check
kind: parts
given: s = 0.05 | 0.1; w = 2 | 4 | 7; d = 0.15 | 0.4

## A power system stabilizer moves a mode at $-\given{s} \pm j\given{w}$ s⁻¹ left by {d} s⁻¹.

::: part
answer: (s + d)/sqrt((s + d)^2 + w^2)
tolerance: 0.5%

### What damping ratio results?

::: misses
- [s/sqrt(s^2 + w^2)] That's before the stabilizer.
- [any] σ/|λ| with the new σ.
:::
:::

::: part
answer: s/(s + d)
tolerance: 0.5%

### By what factor does the halving time shrink?

::: misses
- [any] Ratio of the old σ to the new.
:::
:::
:::

::: check
kind: parts
given: S = 500 | 1500; P = 150 | 400; C = 150 | 400; x = 0.15 | 0.2

## A {P} MW inverter plant sits at a {S} MVA bus; a {C} MVA synchronous condenser (X″ = {x} pu) is added there.

::: part
answer: (S + C/x)/P
tolerance: 0.5%

### What short-circuit ratio results?

::: misses
- [(S + C)/P] The condenser adds $S/X''$ of fault level.
- [any] $(S_{sc} + S_c/X'')/P$.
:::
:::
:::
:::