title: "Problem set 9: faults, protection and stability by computation"
heading: "Problem set 9: Z-bus fault studies, all four fault types, sequence-to-phase conversion, fault resistance and grounding, breaker asymmetry, relay coordination, swing frequencies, equal areas, critical clearing and mode damping"
eyebrow: S10 · Problem set 9
type: problems
---

::: hook
These problems cover lessons 42 and 49 with the fault and stability lessons behind them: the computations a fault study and a transient stability study run, from Z-bus columns and sequence connections to relay times, swing frequencies and critical clearing.
:::

::: pool
pick: 12

::: check
kind: parts
given: g = 0.15 | 0.3; x = 0.1 | 0.25

## Two buses are joined by j{x} pu and each has a generator of j{g} pu. A bolted three-phase fault occurs at bus 1.

::: part
answer: ((1/g + 1/x)^2 - 1/x^2)/(1/g + 1/x)
tolerance: 0.5%

### What fault current flows, in per unit?

::: misses
- [1/g] Bus 2's generator feeds the fault too.
- [any] $1/|Z_{11}|$.
:::
:::

::: part
answer: 1 - (1/x)/(1/g + 1/x)
tolerance: 0.5%

### What voltage does bus 2 keep?

::: misses
- [any] $1 - Z_{21}/Z_{11}$.
:::
:::
:::

::: check
kind: parts
given: a = 0.1 | 0.2 | 0.3; c = 0.05 | 0.15 | 0.4

## A bus has $Z_1 = Z_2$ = j{a} and $Z_0$ = j{c} pu.

::: part
answer: 3/(2*a + c)
tolerance: 0.5%

### What is its bolted single line-to-ground fault current?

::: misses
- [any] $3/(Z_1 + Z_2 + Z_0)$.
:::
:::

::: part
answer: 3*(1/(a + a*c/(a + c)))*a/(a + c)
tolerance: 0.5%

### What ground current does a bolted double line-to-ground fault draw?

::: misses
- [any] $3I_{a0}$ with $I_{a1} = 1/(Z_1 + Z_2 \parallel Z_0)$ and $I_{a0} = -I_{a1}Z_2/(Z_2 + Z_0)$.
:::
:::

::: part
answer: sqrt(3)/(2*a)
tolerance: 0.5%

### What phase current does a line-to-line fault draw?

::: misses
- [any] $\sqrt3/(Z_1 + Z_2)$.
:::
:::
:::

::: check
kind: parts
given: k = 0.1 | 0.2 | 0.4; f = 0.02 | 0.05 | 0.1

## A three-phase fault through j{f} pu occurs at a bus whose Z-bus diagonal is j{k} pu.

::: part
answer: 1/(k + f)
tolerance: 0.5%

### What current flows?

::: misses
- [any] $1/(Z_{kk} + Z_f)$.
:::
:::

::: part
answer: f/(k + f)
tolerance: 0.5%

### What voltage remains at the faulted bus?

::: misses
- [any] $Z_f/(Z_{kk} + Z_f)$.
:::
:::
:::

::: check
kind: parts
given: r = 10 | 20 | 40; c = 2 | 3 | 5

## A breaker interrupts a fault with X/R = {r} (60 Hz) when its contacts part {c} cycles after the fault starts.

::: part
answer: sqrt(1 + 2*exp(-2*c/60/(r/(2*pi*60))))
tolerance: 0.5%

### By what factor does the worst-case offset raise the RMS current?

::: misses
- [any] $\sqrt{1 + 2e^{-2t/\tau}}$ with $\tau = (X/R)/\omega$.
:::
:::
:::

::: check
kind: parts
given: V = 4.16 | 13.8; a = 0.15 | 0.3; c = 0.1 | 0.2; I = 300 | 800

## A {V} kV system with $Z_1 = Z_2$ = j{a}, $Z_0$ = j{c} pu (100 MVA) must limit ground faults to {I} A with a neutral resistor.

::: part
answer: sqrt((3/(I/(100e6/(sqrt(3)*V*1e3))))^2 - (2*a + c)^2)/3*V^2/100
unit: Ω
tolerance: 0.5%

### What resistance does it need?

::: misses
- [any] Solve $|j(Z_1 + Z_2 + Z_0) + 3R_n| = 3/I_f$, then convert to ohms.
:::
:::
:::

::: check
kind: parts
given: T = 1 | 2; M = 5 | 8; c = 0.3 | 0.4; m = 3 | 4

## A downstream very inverse relay (dial {T}) sees {M} times its pickup during a fault; the upstream very inverse relay sees {m} times its pickup and must trail it by {c} s.

::: part
answer: T*(19.61/(M^2 - 1) + 0.491)
unit: s
tolerance: 0.5%

### When does the downstream relay trip?

::: misses
- [any] $T(19.61/(M^2 - 1) + 0.491)$.
:::
:::

::: part
answer: (T*(19.61/(M^2 - 1) + 0.491) + c)/(19.61/(m^2 - 1) + 0.491)
tolerance: 0.5%

### What time dial does the upstream relay need?

::: misses
- [any] Its time at {m} times pickup must be the downstream time plus {c} s.
:::
:::
:::

::: check
kind: parts
given: a = 8 | 15 | 30; b = 7.4 | 13 | 18; s = 25 | 40

## A differential relay with a {s}% slope sees {a} A in and {b} A out of its zone.

::: part
answer: (a - b)/((a + b)/2)*100
unit: %
tolerance: 0.5%

### What is the ratio of operating to restraint current?

::: misses
- [any] |I₁ − I₂| over their average.
:::
:::
:::

::: check
kind: parts
given: P = 0.6 | 1.2; M = 1.8 | 2.4; H = 3 | 6

## A unit with H = {H} s delivers {P} pu with $P_\max$ = {M} pu on a 60 Hz system.

::: part
answer: asin(P/M)*180/pi
unit: °
tolerance: 0.5%

### What is its rotor angle?

::: misses
- [any] $\sin^{-1}(P/P_\max)$.
:::
:::

::: part
answer: sqrt(377*sqrt(M^2 - P^2)/(2*H))/(2*pi)
unit: Hz
tolerance: 0.5%

### At what frequency does it swing?

::: misses
- [any] $\frac{1}{2\pi}\sqrt{\omega_sP_s/2H}$ with $P_s = \sqrt{P_\max^2 - P^2}$.
:::
:::
:::

::: check
kind: parts
given: P = 0.6 | 1; M = 1.8 | 2.5; H = 3 | 6

## A machine with H = {H} s at {P} pu ($P_\max$ = {M} pu before and after) has a fault that drops its output to zero.

::: part
answer: acos((P/M)*(pi - 2*asin(P/M)) + cos(pi - asin(P/M)))*180/pi
unit: °
tolerance: 0.5%

### What is the critical clearing angle?

::: misses
- [any] Equal areas with $r_1 = 0$, $r_2 = 1$.
:::
:::

::: part
answer: sqrt(4*H*(acos((P/M)*(pi - 2*asin(P/M)) + cos(pi - asin(P/M))) - asin(P/M))/(377*P))
unit: s
tolerance: 0.5%

### What is the critical clearing time?

::: misses
- [any] $\sqrt{4H(\delta_c - \delta_0)/(\omega_sP_m)}$.
:::
:::
:::

::: check
kind: parts
given: P = 0.8 | 1; M = 2 | 2.5; r = 0.2 | 0.4; s = 0.7 | 0.85

## A machine at {P} pu has $P_\max$ = {M} pu before a fault, {r} of that during it and {s} of it after clearing.

::: part
answer: (pi - asin(P/(s*M)))*180/pi
unit: °
tolerance: 0.5%

### Where is the post-fault unstable equilibrium?

::: misses
- [any] $\pi - \sin^{-1}(P_m/(r_2P_\max))$.
:::
:::

::: part
answer: acos(((P/M)*(pi - asin(P/(s*M)) - asin(P/M)) + s*cos(pi - asin(P/(s*M))) - r*cos(asin(P/M)))/(s - r))*180/pi
unit: °
tolerance: 0.5%

### What is the critical clearing angle?

::: misses
- [any] The general equal-area formula.
:::
:::
:::

::: check
kind: parts
given: a = 3 | 6; b = 2 | 4 | 8; E = 1.05 | 1.15; X = 0.5 | 1; d = 15 | 30

## Two machines (H = {a} and {b} s, E = {E} pu each) are joined by {X} pu and run {d}° apart, on 60 Hz.

::: part
answer: sqrt(377*E^2/X*cos(d*pi/180)/(2*a*b/(a + b)))/(2*pi)
unit: Hz
tolerance: 0.5%

### At what frequency do they swing against each other?

::: misses
- [any] $\omega_n = \sqrt{\omega_sP_s/2H_{eq}}$.
:::
:::
:::

::: check
kind: parts
given: s = 0.05 | 0.15 | 0.4; w = 1.5 | 3 | 7

## An oscillation mode sits at $-\given{s} \pm j\given{w}$ s⁻¹.

::: part
answer: s/sqrt(s^2 + w^2)
tolerance: 0.5%

### What is its damping ratio?

::: misses
- [any] σ/|λ|.
:::
:::

::: part
answer: ln(2)/s
unit: s
tolerance: 0.5%

### How long does its amplitude take to halve?

::: misses
- [any] ln 2/σ.
:::
:::
:::

::: check
kind: parts
given: P = 0.8 | 1; M = 2 | 3; c = 50 | 65

## A zero-output fault on a machine at {P} pu ($P_\max$ = {M} pu before and after) is cleared at {c}°.

::: part
answer: M*(cos(c*pi/180) + cos(asin(P/M))) - P*(pi - asin(P/M) - c*pi/180) - P*(c*pi/180 - asin(P/M))
tolerance: 1%

### How much decelerating area is left over after absorbing the accelerating area (negative if it fails)?

::: misses
- [any] Available decelerating area minus $P_m(\delta_c - \delta_0)$.
:::
:::
:::

::: check
kind: choice

## A fault study shows a bus's line-to-ground fault current exceeds its three-phase fault current. What does that say about the bus?

- [ ] The calculation is wrong
- [x] Its zero-sequence impedance is smaller than its positive-sequence impedance, as near solidly grounded wye transformers or generators, so breakers there must be rated for the ground fault
- [ ] It has no ground path
- [ ] Its negative-sequence impedance is zero

::: misses
- [1] It's common and physical.
- [3] Without a ground path there would be almost no ground-fault current.
- [4] Negative-sequence impedances are similar to positive.
:::
:::
:::