title: Power system protection
heading: Zones of protection, current and voltage transformers, inverse-time overcurrent relays and their coordination, distance relays and their zones, differential protection, and what makes protection selective, fast and secure
eyebrow: S10 · Lesson 40 · Power system protection
xp: 50
---

::: hook
A fault must be cleared in a fraction of a second, but only the breakers nearest it should open: trip too much and a single tree branch blacks out a city; trip too little and equipment burns. Protective relays make that decision automatically from currents and voltages scaled down by instrument transformers. This lesson covers the three workhorse schemes, overcurrent, distance and differential, and the arithmetic of setting and coordinating them.
:::

::: play
- Operating time against fault current (as a multiple M of the relay's pickup) for the three standard IEEE inverse-time overcurrent curves, at a chosen time dial.
- Inverse-time relays trip faster for bigger currents, so a relay close to a fault (seeing a large current) beats one farther upstream.
- "Extremely inverse" falls steepest, which coordinates well with fuses; the time dial shifts every curve up or down in proportion.
:::

```sim plot
view: graph
x: M = 1.5..30 log
y: t = 0.05..30 s log
slider: T = 0.5..10 = 2
plot: T*(0.0515/(M^0.02 - 1) + 0.114) | samples: 400 | label: moderately inverse
plot: T*(19.61/(M^2 - 1) + 0.491) | samples: 400 | color: ch3 | label: very inverse
plot: T*(28.2/(M^2 - 1) + 0.1217) | samples: 400 | color: ch4 | label: extremely inverse
readout: very inverse time at M of 10, s = T*(19.61/99 + 0.491) | digits: 3
```

::: predict
## A feeder relay operates in 0.69 s for a 4000 A fault. The relay one breaker upstream sees the same fault current. What's the earliest it should operate?

- [ ] 0.69 s, at the same time
- [x] About 1.0 s, a coordination margin after the feeder relay
- [ ] 0.39 s, so it's faster
- [ ] Never, since it's not the closest breaker

::: reveal
The upstream relay is the backup. It must wait long enough for the feeder breaker to clear (a few cycles) plus margins for relay overtravel and errors: a **coordination time interval** of 0.2 to 0.4 s. With 0.3 s, the upstream relay should take at least 0.99 s at 4000 A, but it must still trip if the feeder breaker fails.
:::
:::

::: nameit
## Principles

Protection divides the system into overlapping **zones** (each generator, transformer, bus and line), each with relays that open only its breakers. The goals are **selectivity** (only the faulted zone), **speed**, **sensitivity** (catch high-resistance faults) and **security** (no false trips), with **backup** if the primary scheme or breaker fails.

## Instrument transformers

**CTs** step currents down, typically to 5 A or 1 A at rated primary current (a 600:5 CT turns 6000 A into 50 A). They must not saturate during faults. **VTs** step voltages to 115 or 120 V line to line.

## Overcurrent relays

A relay picks up above a set current and operates after a time that falls with the multiple M of pickup. IEEE standard curves:

$$t = TDS\left(\frac{A}{M^p - 1} + B\right)$$

| Curve | A | B | p |
|---|---|---|---|
| Moderately inverse | 0.0515 | 0.114 | 0.02 |
| Very inverse | 19.61 | 0.491 | 2 |
| Extremely inverse | 28.2 | 0.1217 | 2 |

**Coordination:** at every fault current a downstream relay could see, the upstream relay must be slower by the coordination time interval.

## Distance relays

On transmission lines, a relay measures the apparent impedance V/I. A fault on the line makes it fall to the impedance from the relay to the fault, proportional to distance. **Zone 1** covers about 80% of the line and trips instantly; **zone 2** covers about 120% with a delay of 0.3 to 0.5 s, backing up the remote end; **zone 3** reaches into the next lines as remote backup. Relay settings are in secondary ohms: $Z_\text{sec} = Z_\text{pri} \times \text{CTR}/\text{VTR}$.

## Differential protection

For transformers, generators and buses: compare the currents entering and leaving the zone. Through-current balances out; an internal fault doesn't. **Percentage restraint** trips only when the difference exceeds a slope (often 20 to 40%) times the through current, so CT mismatch during heavy external faults doesn't cause a false trip.
:::

::: example
## A very inverse relay with time dial 2 sees a fault at 10 times pickup. When does it trip, and how do the other curves compare?

::: solution
1. **Very inverse.**
   $$\begin{aligned} t &= 2(19.61/99 + 0.491) \\ &= 1.38\ \text{s} \end{aligned}$$
2. **The other curves.** The moderately inverse curve gives 2.41 s and the extremely inverse 0.81 s at the same dial and multiple.

**Answer:** it trips in 1.38 s; the moderately inverse curve would take 2.41 s and the extremely inverse 0.81 s.
:::
:::

::: example
## A feeder relay (very inverse, dial 1, pickup 400 A) and the upstream relay (very inverse, pickup 600 A) must coordinate with 0.3 s at 4000 A. What dial does the upstream relay need?

::: solution
1. **Feeder relay.** It sees M = 10 and operates in
   $$\begin{aligned} t &= 19.61/99 + 0.491 \\ &= 0.689\ \text{s} \end{aligned}$$
2. **Upstream relay's target.** It sees M = 6.67 and must take 0.989 s.
3. **Its dial.**
   $$\begin{aligned} \text{TD} &= \frac{0.989}{19.61/(6.67^2 - 1) + 0.491} \\ &= 1.05 \end{aligned}$$
4. **Other fault levels.** Coordination must then be checked at the other fault levels too, especially the largest.

**Answer:** a time dial of 1.05.
:::
:::

::: example
## A transformer differential relay has a 25% slope. During a through-fault, 10 A enters and 9.2 A leaves (CT errors); during an internal fault, 10 A enters and 2 A leaves. What does the relay do?

::: solution
1. **What the relay compares.** It compares the operating current |I₁ − I₂| with the restraint current (|I₁| + |I₂|)/2.
2. **Through-fault.** 0.8 A against 9.6 A:
   $$0.8/9.6 = 8.3\%$$
   below 25%: no trip.
3. **Internal fault.** 8 A against 6 A:
   $$8/6 = 133\%$$
   so it trips.
4. **Why the slope.** The restraint grows with the current, so the CT mismatch that's inevitable during heavy through-faults never causes a false trip.

**Answer:** it doesn't trip for the through-fault (8.3%) and trips for the internal fault (133%).
:::
:::

::: check
given: I = 2000 | 8000 | 15000; R = 400 | 1200; s = 5 | 1
answer: I*s/R
unit: A
tolerance: 0.5%

## A {R}:{s} CT carries {I} A of fault current. What flows in its secondary?

::: right
Right. {I} × {s}/{R} = {answer} A.
:::

::: misses
- [I*R/s] The CT steps current down by its ratio.
- [any] Not yet. Divide by the turns ratio.
:::
:::

::: check
given: M = 2 | 5 | 15; T = 0.5 | 2 | 6
answer: T*(19.61/(M^2 - 1) + 0.491)
unit: s
tolerance: 0.5%

## An IEEE very inverse relay with time dial {T} sees {M} times pickup. When does it operate?

::: right
Right. $TDS(19.61/(M^2 - 1) + 0.491)$ = {answer} s.
:::

::: misses
- [any] Not yet. Apply the IEEE formula.
:::
:::

::: check
given: d = 0.15 | 0.4 | 0.8; c = 0.2 | 0.3 | 0.4
answer: d + c
unit: s
tolerance: 0.5%

## A downstream relay operates in {d} s for a fault. With a coordination interval of {c} s, how fast may the upstream relay operate for the same fault?

::: right
Right. No faster than {answer} s.
:::

::: misses
- [d - c] The upstream relay must be slower, not faster.
- [any] Not yet. Add the interval.
:::
:::

::: check
given: Z = 20 | 60 | 120; C = 120 | 200 | 400; V = 1000 | 2000 | 3000
answer: Z*C/V
unit: Ω
tolerance: 0.5%

## A line's impedance is {Z} Ω primary. With CT ratio {C} and VT ratio {V}, what's it in secondary ohms?

::: right
Right. $Z\,\text{CTR}/\text{VTR}$ = {answer} Ω.
:::

::: misses
- [Z*V/C] Voltage is divided by the VT ratio and current by the CT ratio: $Z_\text{sec} = Z \times \text{CTR}/\text{VTR}$.
- [any] Not yet. $V_\text{sec}/I_\text{sec}$.
:::
:::

::: check
given: Z = 15 | 40 | 90; k = 0.8 | 0.85; L = 80 | 200
answer: k*Z
unit: Ω
tolerance: 0.5%

## A {L} km line has {Z} Ω of positive-sequence impedance. Zone 1 is set to {k} of the line. What's its reach in primary ohms?

::: right
Right. {answer} Ω, about {k} × {L} km of line.
:::

::: misses
- [Z] Zone 1 deliberately stops short of the far end.
- [any] Not yet. A fraction of the line impedance.
:::
:::

::: check
given: a = 10 | 25; b = 9.2 | 22; s = 0.2 | 0.3
answer: 100*abs(a - b)/((a + b)/2)
unit: %
tolerance: 0.5%

## A transformer differential relay sees {a} A in and {b} A out (secondary, after ratio correction) during an external fault. What's the operating current as a percentage of the restraint current?

::: right
Right. $|I_1 - I_2|/((|I_1| + |I_2|)/2)$ = {answer}%; it trips only if that exceeds the {s} slope.
:::

::: misses
- [100*abs(a - b)/a] Restraint is the average of the two currents.
- [any] Not yet. Difference over average.
:::
:::

::: check
kind: parts
given: a = 5 | 10 | 20; b = 1 | 4.5 | 9.4; s = 20 | 30

## A differential relay with a {s}% slope sees {a} A entering and {b} A leaving its zone (secondary, after ratio correction).

::: part
answer: a - b
unit: A
tolerance: 0.5%

### What is the operating current?

::: misses
- [any] |I₁ − I₂|.
:::
:::

::: part
answer: (a - b)/((a + b)/2)*100
unit: %
tolerance: 0.5%

### What is its ratio to the restraint current (the relay trips above {s}%)?

::: misses
- [(a - b)/(a + b)*100] The restraint is the average of the two currents.
- [any] Operating over $(|I_1| + |I_2|)/2$.
:::
:::
:::

::: check
kind: derivation
vars: T = 0.5..10, M = 1.5..20

## An IEEE very inverse relay has time dial T and sees M times its pickup current.

::: step
answer: T*(19.61/(M^2 - 1) + 0.491)

### When does it operate, in seconds?
:::

::: step
answer: T*(28.2/(M^2 - 1) + 0.1217)

### When would an extremely inverse relay with the same dial operate?
:::

::: right
Right. The extremely inverse curve is slower at low multiples and faster at high ones, which suits coordination with fuses.
:::
:::

::: explain
## Why do distance relays protect only about 80% of a line instantaneously instead of all of it?

::: model
A distance relay judges where a fault is from the apparent impedance it measures, and that measurement has errors: CT and VT ratio errors, the line's impedance not being known exactly, fault resistance, and infeed from other sources. A fault just beyond the remote bus, on the next line, produces almost the same impedance as one just before it. If zone 1 reached 100%, small errors would make it trip for faults on the next line, taking out the wrong circuit. Setting it short guarantees it only ever trips for faults on its own line, and the remaining 20% is covered by zone 2 with a short delay, or by the relay at the other end, whose zone 1 covers that portion instantly.
:::
:::

::: practice

::: check
given: M = 3 | 8 | 20; T = 1 | 4
answer: T*(28.2/(M^2 - 1) + 0.1217)
unit: s
tolerance: 0.5%

## Extremely inverse time: dial {T}, M = {M}?

::: misses
- [any] $TDS(28.2/(M^2 - 1) + 0.1217)$.
:::
:::

::: check
given: Z = 30 | 100; C = 160 | 300; V = 1500 | 3500
answer: Z*C/V
unit: Ω
tolerance: 0.5%

## Secondary ohms: {Z} Ω, CTR {C}, VTR {V}?

::: misses
- [any] $Z\,\text{CTR}/\text{VTR}$.
:::
:::

::: check
given: I = 3000 | 20000; R = 600 | 2000; s = 5 | 1
answer: I*s/R
unit: A
tolerance: 0.5%

## CT secondary: {I} A through a {R}:{s} CT?

::: misses
- [any] $I \times s/R$.
:::
:::
:::