title: Reactive power compensation
heading: Shunt capacitors and reactors, series capacitors that shorten a line electrically, midpoint voltage support, static var compensators, STATCOMs and synchronous condensers, and how each behaves when the voltage sags
eyebrow: S10 · Lesson 8 · Reactive power compensation
xp: 50
---

::: hook
Lesson 7 showed that vars control voltage and that a line's reactance limits the power it can carry. Utilities attack both with compensation: capacitor banks that supply vars near loads, reactors that soak up the charging of lightly loaded lines, series capacitors that cancel part of a long line's reactance, and power-electronic devices that adjust their vars every cycle. They differ most in what they do during a voltage sag, exactly when they're most needed.
:::

::: play
- The power–angle curve of a line with reactance X = 0.5 pu between two 1 pu buses, with a series capacitor cancelling a fraction k of the reactance (dashed: uncompensated).
- The peak transfer is $V^2/(X(1 - k))$: 40% compensation raises it from 2 to 3.33 pu, and the same power flows at a smaller angle, with more stability margin.
- Series compensation is used on long lines in the western US, Brazil and Scandinavia; too much of it can excite subsynchronous resonance with turbine shafts.
:::

```sim plot
view: graph
x: d = 0..180 °
y: P = 0..6 pu
slider: k = 0..0.75 = 0.4
plot: sin(d*pi/180)/(0.5*(1 - k)) | samples: 400 | label: compensated
plot: sin(d*pi/180)/0.5 | dashed | color: ch3 | label: uncompensated
readout: transfer limit, pu = 1/(0.5*(1 - k)) | digits: 3
readout: angle for 1.5 pu, ° = asin(1.5*0.5*(1 - k))*180/pi | digits: 3
```

::: predict
## A 50 Mvar capacitor bank and a 50 Mvar STATCOM are both on a bus whose voltage sags to 0.9 pu. Which supplies more vars?

- [ ] The capacitor: it's a passive device and can't run out
- [x] The STATCOM: 45 Mvar against the capacitor's 40.5
- [ ] They're equal
- [ ] Neither supplies anything below 1 pu

::: reveal
A capacitor's vars go as $V^2$ (its current is proportional to voltage): $50 \times 0.81$ = 40.5 Mvar. A STATCOM is a converter that can hold its rated current down to low voltage, so its output goes as V: 45 Mvar. At 0.7 pu the gap is 24.5 against 35. Capacitors fade just when voltage support is needed most.
:::
:::

::: nameit
## Shunt devices

- **Capacitor banks** supply vars, in switched steps, with output $Q_\text{rated}V^2$.
- **Shunt reactors** absorb vars, mainly to cancel the charging of long or lightly loaded lines (lesson 6) and keep voltages down at night.
- **Static var compensators (SVC)**: thyristor-switched capacitors and thyristor-controlled reactors, continuously variable. At their limits they behave like a fixed capacitor, with output ∝ $V^2$.
- **STATCOM**: a voltage-source converter that can supply its rated current at any voltage in its range, so output ∝ V, and it responds within a cycle.
- **Synchronous condensers**: synchronous machines without a prime mover, which also add inertia and short-circuit strength (lessons 36 and 46).

A shunt device's effect on voltage is roughly $\Delta V \approx \Delta Q/S_{sc}$ in per unit, where $S_{sc}$ is the bus's short-circuit level: weak buses swing more.

## Series capacitors

A capacitor in series with a line cancels part of its reactance: $X_\text{eff} = X(1 - k)$ for compensation degree k. The transfer limit $V^2/X_\text{eff}$ rises and the angle for a given flow falls. Typical k is 25 to 70%.

## Midpoint support

Holding the voltage at the middle of a line at 1 pu (with an SVC or STATCOM) splits it into two halves of X/2. Each can carry $V^2\sin(\delta/2)/(X/2)$, so the limit doubles to $2V^2/X$, reached at δ = 180° across the whole line.
:::

::: example
## A 30 Mvar capacitor bank is switched in at a bus with a 3000 MVA short-circuit level. Estimate the voltage rise.

::: solution
1. **Voltage rise.**
   $$\begin{aligned} \Delta V &\approx 30/3000 \\ &= 0.01\ \text{pu} \end{aligned}$$
   a 1% rise.
2. **On a weak bus.** On a weak 600 MVA bus the same bank would raise the voltage 5%, which is why capacitor banks on weak systems come in small steps.

**Answer:** about 0.01 pu, a 1% rise.
:::
:::

::: example
## A line has X = 0.5 pu between 1 pu buses. What series compensation gives a 3 pu transfer limit?

::: solution
1. **Set the limit.**
   $$\frac{V^2}{X(1 - k)} = 3$$
2. **Solve for k.**
   $$\begin{aligned} 1 - k &= \frac{1}{0.5 \times 3} \\ &= 0.667 \end{aligned}$$
   so k = 33%.
3. **Compare with midpoint support.** Midpoint voltage support alone would give 2/0.5 = 4 pu; combining them gives more still.

**Answer:** series compensation of 33%.
:::
:::

::: example
## A 400 km, 500 kV line has a shunt susceptance of 5 µS/km. How many vars does it generate when lightly loaded, and what reactor rating compensates 70% of it?

::: solution
1. **Line charging.**
   $$\begin{aligned} Q &= V^2B \\ &= (500 \times 10^3)^2 \\ &\quad \times 5 \times 10^{-6} \times 400 \\ &= 500\ \text{Mvar} \end{aligned}$$
2. **When unloaded.** All of it must go somewhere, and the line's far end rises (the Ferranti effect).
3. **Reactor rating.** Shunt reactors, usually split between the two ends, keep the voltage within limits at light load:
   $$\begin{aligned} Q_L &= 0.7 \times 500 \\ &= 350\ \text{Mvar} \end{aligned}$$
4. **At heavy load.** The line's own $I^2X$ absorbs the rest, and some reactors are switched out.

**Answer:** the line generates 500 Mvar, and 350 Mvar of shunt reactors compensate 70% of it.
:::
:::

::: check
given: X = 0.3 | 0.5 | 0.8; k = 0.25 | 0.4 | 0.6
answer: 1/(X*(1 - k))
tolerance: 0.5%

## A line of X = {X} pu between 1 pu buses gets {k} series compensation. What's its new transfer limit?

::: right
Right. $V^2/(X(1 - k))$ = {answer} pu.
:::

::: misses
- [1/(X*k)] The capacitor cancels a fraction k, leaving $1 - k$.
- [(1 + k)/X] The limit scales as $1/(1 - k)$, not $1 + k$.
- [any] Not yet. $X_\text{eff} = X(1 - k)$.
:::
:::

::: check
given: Q = 20 | 50 | 150; V = 0.7 | 0.85 | 0.92
answer: Q*V^2
unit: Mvar
tolerance: 0.5%

## A {Q} Mvar capacitor bank sees its bus sag to {V} pu. What does it supply?

::: right
Right. $Q_\text{rated}V^2$ = {answer} Mvar.
:::

::: misses
- [Q*V] That's a STATCOM at rated current. A capacitor's current falls with voltage too.
- [any] Not yet. $Q = V^2/X_C$.
:::
:::

::: check
given: Q = 20 | 50 | 150; V = 0.7 | 0.85 | 0.92
answer: Q*V
unit: Mvar
tolerance: 0.5%

## A {Q} Mvar STATCOM at rated current sees its bus sag to {V} pu. What does it supply?

::: right
Right. $Q_\text{rated}V$ = {answer} Mvar.
:::

::: misses
- [Q*V^2] That's a capacitor. A STATCOM holds its current, so its vars fall only linearly.
- [any] Not yet. Q = VI with I held at rated.
:::
:::

::: check
given: Q = 10 | 40 | 100; S = 500 | 2000 | 8000
answer: 100*Q/S
unit: %
tolerance: 0.5%

## A {Q} Mvar shunt bank is switched in at a bus with a {S} MVA short-circuit level. Estimate the voltage change.

::: right
Right. $\Delta Q/S_{sc}$ = {answer}%.
:::

::: misses
- [any] Not yet. The bus behaves like a source behind $1/S_{sc}$ per unit reactance.
:::
:::

::: check
given: V = 0.95 | 1 | 1.05; X = 0.4 | 0.8
answer: 2*V^2/X
tolerance: 0.5%

## A line of X = {X} pu joins buses at {V} pu, and its midpoint voltage is held at {V} pu too. What's its transfer limit?

::: right
Right. Two halves of X/2: $2V^2/X$ = {answer} pu.
:::

::: misses
- [V^2/X] Without midpoint support. Holding the middle doubles it.
- [any] Not yet. Each half carries $V^2\sin(\delta/2)/(X/2)$.
:::
:::

::: check
given: X = 0.4 | 0.6; P = 3 | 4 | 5
answer: 100*(1 - 1/(X*P))
unit: %
tolerance: 0.5%

## What series compensation lets a line of X = {X} pu between 1 pu buses reach a {P} pu transfer limit?

::: right
Right. $k = 1 - V^2/(XP_\text{max})$ = {answer}%.
:::

::: misses
- [any] Not yet. Solve $1/(X(1 - k)) = P_\text{max}$.
:::
:::

::: check
kind: parts
given: V = 230 | 345 | 500 | 765; b = 3 | 4 | 5; l = 100 | 300; f = 0.5 | 0.7

## A {V} kV line {l} km long has a shunt susceptance of {b} µS/km.

::: part
answer: V^2*b*l*1e-6
unit: Mvar
tolerance: 0.5%

### How many vars does it generate at rated voltage?

::: misses
- [any] $V^2B$ with B = bl.
:::
:::

::: part
answer: f*V^2*b*l*1e-6
unit: Mvar
tolerance: 0.5%

### What shunt reactor rating compensates {f} of it?

::: misses
- [any] That fraction of the charging.
:::
:::
:::

::: check
kind: derivation
vars: X = 0.1..2, k = 0..0.7, V = 0.9..1.1

## A line of reactance X joins two buses at V pu.

::: step
answer: V^2/(X*(1 - k))

### What is its transfer limit with a fraction k of series compensation?
:::

::: step
answer: 2*V^2/X

### What is it uncompensated, but with the midpoint held at V by a shunt device?
:::

::: right
Right. Series capacitors shorten the line electrically; a midpoint compensator splits it into two halves, each with half the reactance.
:::
:::

::: explain
## Why does a series capacitor raise a line's power transfer limit while a shunt capacitor at the receiving end mostly raises voltage?

::: model
The transfer limit between two held voltages is $V^2/X$, set by the line's series reactance. A series capacitor sits in the current's path and its negative reactance cancels part of the line's, so the effective X falls and the limit rises in proportion, at every load. A shunt capacitor at the end leaves the series reactance unchanged; it supplies vars locally so the line doesn't have to carry them, which raises the receiving voltage and moves the nose of the P–V curve outward. It helps a load whose voltage was sagging, but it can't lift the angle-based limit between two buses whose voltages are already held.
:::
:::

```sim plot
view: graph
x: V = 0.5..1.1 pu
y: Q = 0..60 Mvar
plot: 50*V^2 | samples: 300 | label: 50 Mvar capacitor or SVC at its limit
plot: 50*V | samples: 300 | color: ch3 | label: 50 Mvar STATCOM at rated current
```

::: practice

::: check
given: X = 0.25 | 0.6; k = 0.3 | 0.5 | 0.7
answer: 1/(X*(1 - k))
tolerance: 0.5%

## Transfer limit of X = {X} with {k} compensation?

::: misses
- [any] $1/(X(1 - k))$.
:::
:::

::: check
given: Q = 30 | 200; V = 0.75 | 0.9
answer: Q*V^2
unit: Mvar
tolerance: 0.5%

## Output of a {Q} Mvar capacitor at {V} pu?

::: misses
- [any] $Q_\text{rated}V^2$.
:::
:::

::: check
given: Q = 15 | 60; S = 400 | 5000
answer: 100*Q/S
unit: %
tolerance: 0.5%

## Voltage change from {Q} Mvar at a {S} MVA bus?

::: misses
- [any] $\Delta Q/S_{sc}$.
:::
:::
:::