title: Regulating transformers in the power flow
heading: Tap changers that push reactive power and phase shifters that push real power, their entries in the bus admittance matrix, circulating current between parallel paths, taps and angles as power-flow unknowns, and the studies planners run with them
eyebrow: S10 · Lesson 21 · Regulating transformers in the power flow
xp: 50
---

::: hook
Two identical 100 MVA transformers, each with 8% reactance, run in parallel at a substation. Someone left one of them on a tap that gives 4% more voltage than the other. With no load on the station at all, each transformer carries 25 Mvar, warming both and serving nobody. Where does that power come from, and how do operators use the same effect on purpose?
:::

::: play
- Two parallel paths join bus 1 to bus 2: path A with reactance $x_A$ and a phase-shifting transformer, path B with $x_B$. A transfer P flows from bus 1 to bus 2 (DC power flow, 100 MVA base).
- The plot shows the flow on each path against the phase shift φ the transformer adds to path A. Without it, the transfer splits inversely with reactance.
- The shifter adds the same circulating flow $\varphi/(x_A + x_B)$ to path A and takes it from path B, whatever the transfer. Move P and the lines shift up and down together; move φ and power moves from one path to the other.
:::

```sim plot
view: graph
x: phi = -10..10 °
y: F = -0.5..2.5 pu
slider: P = 0..2 = 1.5 pu
slider: xA = 0.05..0.3 = 0.1 pu
slider: xB = 0.05..0.3 = 0.2 pu
plot: (P*xB + phi*pi/180)/(xA + xB) | samples: 200 | label: path A
plot: (P*xA - phi*pi/180)/(xA + xB) | samples: 200 | color: ch3 | label: path B
plot: 0.8 + 0*phi | dashed | color: ch4 | label: path A's 0.8 pu rating
readout: circulating flow per degree, MW = 100*(pi/180)/(xA + xB) | digits: 3
```

::: predict
## An operator wants to move real power from an overloaded line onto a parallel one. Which device does the job?

- [ ] A tap changer that raises the voltage magnitude on the overloaded path
- [x] A phase shifter that retards the angle on the overloaded path
- [ ] A shunt capacitor at the receiving end
- [ ] Either transformer works equally well

::: reveal
Real power across a reactance follows the angle difference (lesson 7), so a phase shifter that changes the angle driving one path moves real power between paths. A tap changer inserts a voltage in phase with the bus voltage, and across reactances that drives reactive current: it moves vars, and barely touches megawatts.
:::
:::

::: nameit
## Two kinds of regulators

A **magnitude regulator** (an on-load tap changer, or LTC) changes the turns ratio in small steps, typically ±10% in 32 steps of 0.625%. It holds a bus voltage as load changes, and it pushes reactive power toward the side it raises. A **phase-angle regulator** adds a voltage in quadrature, taken from another phase's winding, which shifts the angle by a few degrees to tens of degrees. It controls real power on its path.

## In the bus admittance matrix

Lesson 10 put a real tap a:1 on bus i's side into $Y_\text{bus}$. A complex ratio $a = |a|e^{j\varphi}$ covers both kinds:

$$\Delta Y_{ii} = \frac{y}{|a|^2}, \qquad Y_{ij} = -\frac{y}{a^*}, \qquad Y_{ji} = -\frac{y}{a}, \qquad \Delta Y_{jj} = y$$

where Δ marks what the transformer adds to a diagonal entry.

With a real a the matrix stays symmetric. A phase shift makes $Y_{ij} \ne Y_{ji}$, so the matrix is no longer symmetric and no passive circuit of branches can represent it.

## Circulating current

In a loop of parallel paths, a regulator in one path acts like a small voltage source ΔV inserted in the loop. By superposition its effect is a current $\Delta V/Z_\text{loop}$ that circulates around the loop, added to the share of the load each path would carry anyway. A tap difference of $\Delta t$ inserts $\Delta V \approx \Delta t\,V$, in phase with V; driven through reactances, that current lags by 90° and is reactive. A phase shift φ inserts $\Delta V \approx j\varphi V$, and its current is in phase with V: real power. In the DC power flow the shifted path's flow becomes $(\theta_i - \theta_j + \varphi)/x_A$, and the circulating flow is $\varphi/(x_A + x_B)$.

## Regulators as power-flow unknowns

A tap can be a fixed input to the power flow. Or the program can hold the regulated bus's voltage at its setpoint and solve for the tap, which takes that voltage's place among the unknowns, with $\partial P/\partial t$ and $\partial Q/\partial t$ columns in the Jacobian. Real taps move in steps, so programs usually adjust them in an outer loop between Newton iterations, round to the nearest step and use a deadband so they don't hunt. A phase shifter can likewise hold its path's flow at a setpoint, with its angle as the unknown.

## Power-flow studies

Planners run power flows for peak and light load, for each outage they plan for, and for future years' generation and load. They look for lines above their ratings, voltages outside about 0.95 to 1.05 pu, and generators near their reactive limits, and they test fixes: new lines, capacitors, regulator settings. One known hazard is in voltage collapse. As voltage sags, LTCs raise distribution voltage to restore load power, which draws more current through the weakened network and lowers transmission voltage further. Protection schemes block tap changes when transmission voltage falls too far.
:::

::: example
## Two parallel transformers, each j0.08 pu, feed a load of 1.0 + j0.5 pu held at 1 pu. Transformer A's tap gives 4% more voltage than B's. How do they share the load?

::: solution
1. **Matched taps.** By superposition, each would carry half the load, 0.5 − j0.25 pu of current, if their taps matched.
2. **Circulating current.** The 4% difference inserts about 0.04 pu of voltage in the loop of the two reactances, driving
   $$\begin{aligned} I_c &= 0.04/(j0.16) \\ &= -j0.25\ \text{pu} \end{aligned}$$
3. **Add it in.** It adds to A's current and subtracts from B's: A carries 0.5 − j0.5 and B carries 0.5 − j0.
4. **Exact solution.** Solving the exact $Y_\text{bus}$ model with the 1.04 ratio gives A 0.510 − j0.500 and B 0.490 + j0.000, with the sending bus at 1.0008 pu.
5. **Read the result.** Transformer A supplies all of the load's reactive power and B none, and A runs at 0.71 pu of current while B runs at 0.49.
6. **At no load.** In the hook's no-load case the circulating 0.25 pu is all there is: 25 Mvar out of one transformer and back through the other.

**Answer:** A carries 0.510 − j0.500 pu (0.71 pu of current, all of the load's vars) and B carries 0.490 pu (0.49 pu, no vars).
:::
:::

::: example
## A 1.5 pu transfer splits between path A (x = 0.1 pu, rated 0.8 pu) and path B (x = 0.2 pu). What phase shift on path A keeps it within its rating?

::: solution
1. **Without a shifter.**
   $$\begin{aligned} P_A &= 1.5 \times 0.2/0.3 \\ &= 1.0\ \text{pu} \end{aligned}$$
   25% over its rating.
2. **Shift needed.** The shifter must take 0.2 pu off it:
   $$\begin{aligned} \phi/(x_A + x_B) &= -0.2 \\ \phi &= -0.06\ \text{rad} \\ &= -3.44° \end{aligned}$$
3. **New flows.** Path A then carries 0.8 pu and path B 0.7 pu. The total is unchanged; the shifter only redirects it.
4. **If B is near its limit too.** Then the transfer itself would have to be reduced.

**Answer:** a shift of −3.44° (−0.06 rad), leaving 0.8 pu on path A and 0.7 pu on path B.
:::
:::

::: example
## A phase-shifting transformer of x = 0.1 pu shifts by 10°. What entries does it add to $Y_\text{bus}$?

::: solution
1. **The branch.** Here y = −j10 and $a = e^{j10°}$.
2. **Diagonal entries.**
   $$\begin{aligned} \Delta Y_{ii} &= y/|a|^2 \\ &= -j10 \end{aligned}$$
   and $\Delta Y_{jj} = -j10$.
3. **Off-diagonal entries.**
   $$\begin{aligned} Y_{ij} &= -y/a^* \\ &= j10e^{j10°} \\ &= 10\angle100° \\ Y_{ji} &= -y/a \\ &= 10\angle80° \end{aligned}$$
4. **No longer symmetric.** The off-diagonal entries differ, so $Y_\text{bus}$ is no longer symmetric: no network of ordinary branches behaves like a phase shifter, which is why it can push power against the natural split.

**Answer:** −j10 on both diagonals, $10\angle100°$ at $Y_{ij}$ and $10\angle80°$ at $Y_{ji}$.
:::
:::

::: check
given: d = 2 | 4 | 5; x = 0.06 | 0.08 | 0.1; y = 0.06 | 0.1 | 0.12
answer: d/100/(x + y)
tolerance: 1%

## Two parallel transformers with reactances j{x} and j{y} pu have taps {d}% apart. About how much current circulates between them, in per unit?

::: right
Right. About $\Delta t/(x_1 + x_2)$ = {answer} pu, almost purely reactive.
:::

::: misses
- [d/(x + y)] Write the tap difference as a fraction, not a percentage.
- [d/100/x] The circulating current goes around the loop through both transformers.
- [any] Not yet. The tap difference is a voltage source in the loop of both reactances.
:::
:::

::: check
given: f = 2 | 5 | 8; x = 0.05 | 0.1 | 0.15; y = 0.1 | 0.2 | 0.3
answer: 100*f*pi/180/(x + y)
unit: MW
tolerance: 0.5%

## A phase shifter adds {f}° to a path of x = {x} pu, in parallel with a path of x = {y} pu. How much real power does it move between them (100 MVA base)?

::: right
Right. $\varphi/(x_A + x_B)$ = {answer} MW, whatever the transfer.
:::

::: misses
- [100*f/(x + y)] Convert the angle to radians.
- [100*f*pi/180/x] The circulating flow goes around both paths.
- [any] Not yet. The shift drives a flow $\varphi/(x_A + x_B)$ around the loop.
:::
:::

::: check
given: P = 1.2 | 1.5 | 2; x = 0.1 | 0.15; y = 0.2 | 0.3; R = 0.6 | 0.75
answer: (R*(x + y) - P*y)*180/pi
unit: °
tolerance: 0.5%

## A transfer of {P} pu splits between path A (x = {x} pu, rated {R} pu) and path B (x = {y} pu). What phase shift on path A brings it to exactly its rating?

::: right
Right. $\varphi = R(x_A + x_B) - P x_B$ in radians: {answer}°. A negative shift pushes flow off path A, a positive one onto it.
:::

::: misses
- [(R*(x + y) - P*y)] Convert to degrees.
- [-(R*(x + y) - P*y)*180/pi] Check the sign: a shift that takes flow off path A is negative.
- [any] Not yet. Path A carries $(P x_B + \varphi)/(x_A + x_B)$; set it equal to the rating.
:::
:::

::: check
given: a = 0.95 | 0.975 | 1.025 | 1.05; x = 0.05 | 0.08 | 0.12
answer: 1/(a^2*x)
tolerance: 0.5%

## A transformer of reactance j{x} pu has a tap a = {a} (a:1) on bus i's side. What's the magnitude of its contribution to $Y_{ii}$?

::: right
Right. $|y|/|a|^2$ = {answer}.
:::

::: misses
- [1/(a*x)] That's the off-diagonal. The tap side's diagonal gets $y/|a|^2$.
- [1/x] That's the other side's diagonal. Include the tap.
- [any] Not yet. $Y_{ii}$ gains $y/|a|^2$.
:::
:::

::: check
given: v = 2 | 3.5 | 5 | 7
answer: ceil(v/0.625)
tolerance: 0

## A tap changer covers ±10% in 32 steps. How many steps up does it take to raise a bus voltage by at least {v}%?

::: right
Right. Each step is 20%/32 = 0.625%, so {answer} steps.
:::

::: misses
- [ceil(v/0.3125)] Each step is 20%/32: the range is 20% wide in total.
- [any] Not yet. Find the size of one step first.
:::
:::

::: check
given: t = 1.02 | 1.04 | 1.06; x = 0.05 | 0.1 | 0.2
answer: 100*(t - 1)/x
unit: Mvar
tolerance: 2%

## A transformer of reactance {x} pu joins two stiff 1 pu buses whose angles are equal. Its tap is raised to give {t} times the voltage toward bus 2. About how much reactive power flows into bus 2 (100 MVA base)?

::: right
Right. About $(t - 1)/x$ per unit, {answer} Mvar: a tap pushes vars.
:::

::: misses
- [100*t/x] Only the voltage difference, $t - 1$, drives the current.
- [any] Not yet. The tap inserts a voltage $(t - 1)V$ across the reactance.
:::
:::

::: check
kind: parts
given: x = 0.05 | 0.1 | 0.2; f = 5 | 10 | 20

## A phase shifter of x = {x} pu shifts by {f}°.

::: part
answer: 1/x
tolerance: 0.5%

### What is the magnitude of its off-diagonal $Y_\text{bus}$ entries?

::: misses
- [any] |y|/|a| with |a| = 1.
:::
:::

::: part
answer: 90 + f
unit: °
tolerance: 0.5%

### What is the angle of $Y_{ij}$, for the shift on bus i's side?

::: misses
- [90 - f] That's $Y_{ji} = -y/a$.
- [any] $-y/a^* = (1/x)\angle(90° + \varphi)$.
:::
:::
:::

::: check
kind: derivation
vars: x = 0.02..0.5, a = 0.9..1.1

## A transformer of reactance x has a real tap a:1 on bus i's side.

::: step
answer: 1/(x*a^2)

### What susceptance magnitude does it add to $Y_{ii}$?
:::

::: step
answer: 1/(x*a)

### What is $|Y_{ij}|$?
:::

::: step
answer: 1/x

### What does it add to $Y_{jj}$?
:::

::: right
Right. With a real tap the matrix stays symmetric, and the π equivalent has unequal shunt branches.
:::
:::

::: explain
## Why does a tap changer move reactive power while a phase shifter moves real power?

::: model
Both act like a small voltage inserted in series with the path, and the extra current that voltage drives around a loop flows through reactance, so it lags the inserted voltage by 90°. A tap changer's inserted voltage is in phase with the bus voltage, so the extra current lags the bus voltage by 90°: it is reactive current, and the path carries more vars. A phase shifter inserts a voltage at 90° to the bus voltage, so the extra current, lagging that by another 90°, is in phase with or opposite to the bus voltage: real current, and real power moves between paths. That's lesson 7's decoupling again: angle differences drive real power and magnitude differences drive reactive power across reactive networks.
:::
:::

::: practice

::: check
given: d = 1..8; x = 0.04..0.15; y = 0.04..0.15
answer: d/100/(x + y)
tolerance: 1%

## Parallel transformers j{x} and j{y}, taps {d}% apart: circulating current, pu?

::: misses
- [any] $\Delta t/(x_1 + x_2)$.
:::
:::

::: check
given: f = 1..15; x = 0.03..0.3; y = 0.03..0.3
answer: 100*f*pi/180/(x + y)
unit: MW
tolerance: 0.5%

## Phase shift {f}° with paths of {x} and {y} pu: MW moved?

::: misses
- [any] $\varphi/(x_A + x_B)$, φ in radians, times 100.
:::
:::

::: check
given: a = 0.9..1.1; x = 0.04..0.2
answer: 1/(a^2*x)
tolerance: 0.5%

## Tap a = {a} on bus i's side, reactance {x} pu: $|Y_{ii}|$ contribution?

::: misses
- [any] $|y|/|a|^2$.
:::
:::
:::