title: Surges, traveling waves and HVDC transmission
heading: Lightning and switching surges as waves on a lossless line, reflection at open, shorted and matched ends, junctions with cables and other lines, lattice diagrams, closing resistors and surge arresters, and direct-current transmission with line-commutated converters
eyebrow: S10 · Lesson 9 · Surges, traveling waves and HVDC transmission
xp: 50
---

::: hook
A 20 kA lightning stroke hits a phase conductor of a 230 kV line. The current splits, 10 kA running each way, and each half is a wave of current that the line can only carry with a wave of voltage beside it: 10 kA times the line's 400 Ω surge impedance is 4 MV, about five times what the insulators can hold. Lines are shielded against exactly this. But surges also start inside the system, every time a breaker closes onto a long line. What happens when such a wave reaches a transformer at the far end, and why do the arresters sit right at the transformer's terminals?
:::

::: play
- A lossless line is energized at t = 0 by a step of 1 pu through a source resistance $R_s$ and ends in a resistance R. Time is in units of the one-way travel time T, and both resistances are in units of the line's surge impedance $Z_c$.
- The plot is the voltage at the receiving end. It changes only when a wave arrives, at T, 3T, 5T and so on, and climbs or rings toward the dashed steady value $R/(R + R_s)$.
- Set $R_s$ near 0 and R large (an unloaded line closed from a stiff source): the end jumps to nearly 2 pu and rings. Set $R_s = Z_c$ (a closing resistor): one step to the final value.
:::

```sim plot
view: graph
x: t = 0..14
y: v = 0..2.2 pu
slider: r = 0.2..5 = 5
slider: s = 0..3 = 0.1
plot: 1/(1 + s)*(2*r/(r + 1))*(1 - ((r - 1)/(r + 1)*(s - 1)/(s + 1))^floor((t + 1)/2))/(1 - (r - 1)/(r + 1)*(s - 1)/(s + 1)) | samples: 1400 | label: receiving end
plot: r/(r + s) + 0*t | dashed | color: ch3 | label: steady value
readout: ρ at the load = (r - 1)/(r + 1) | digits: 3
readout: ρ at the source = (s - 1)/(s + 1) | digits: 3
```

::: predict
## A 300 kV surge travels along a 400 Ω line and reaches a breaker that is open. What voltage appears across the open contacts' line side?

- [ ] 150 kV
- [ ] 300 kV
- [x] 600 kV
- [ ] It depends on how long the line is

::: reveal
600 kV. An open end can't carry current, so a reflected current wave must cancel the incident one exactly. Its voltage wave has the same sign as the incident voltage, and the two add: the reflection coefficient of an open end is +1. The line's length only sets when the doubling happens.
:::
:::

::: nameit
## Waves on a lossless line

For fast events a line is well described by its series inductance L and shunt capacitance C per meter alone. The telegrapher's equations $\partial v/\partial x = -L\,\partial i/\partial t$ and $\partial i/\partial x = -C\,\partial v/\partial t$ combine into a wave equation whose solutions are any shape moving either way, $v = f(x - ut) + g(x + ut)$, at

$$u = \frac{1}{\sqrt{LC}}, \qquad Z_c = \sqrt{\frac{L}{C}}$$

A forward wave carries current $i^+ = v^+/Z_c$, and a backward wave $i^- = -v^-/Z_c$ (current measured in the forward direction). Overhead lines run near the speed of light, about 300 m/µs, with $Z_c$ of 300 to 500 Ω. Cables have far more capacitance per meter: about half that speed and 30 to 60 Ω.

## Reflections

Where a wave meets a resistance $Z_R$, the voltage and current there must satisfy $v = Z_R\,i$. That needs a reflected wave of

$$\rho = \frac{Z_R - Z_c}{Z_R + Z_c}$$

times the incident voltage. Current reflects with $-\rho$. An open end has ρ = 1, a short −1, and a line ended in $Z_c$ has no reflection at all. The voltage passed on is the sum of incident and reflected, $(1 + \rho)$ times the incident wave. At a junction, $Z_R$ is whatever the wave sees beyond it: a cable's $Z_c$, or several lines in parallel.

At the sending end a source of resistance $R_s$ first launches $V Z_c/(R_s + Z_c)$, and returning waves reflect from it with $\rho_s = (R_s - Z_c)/(R_s + Z_c)$. A **lattice diagram** keeps track of the bouncing: time runs down the page, each wave is a slanted line, and each terminal's voltage is the running sum of the waves arriving and leaving there.

## Surges in practice

Up to about 230 kV, lightning sets the insulation level of lines and equipment. Shield wires above the phases take most strokes, and towers carry the current to ground. Above about 700 kV, switching surges matter more. Closing a breaker onto an unloaded line from a stiff source doubles the voltage at the open far end, and charge trapped on the line from an earlier opening can push it toward 3 pu. Closing resistors briefly put about $Z_c$ in series so the first wave is half size and is absorbed when it returns. **Surge arresters**, today blocks of zinc oxide, conduct almost nothing at normal voltage and heavily above a set level. They sit at transformer terminals because that's where an arriving surge doubles. A device's **basic insulation level** (BIL) is the crest of a standard 1.2/50 µs impulse it must withstand.

## Direct-current transmission

A line-commutated converter is a six-pulse thyristor bridge. With the thyristors fired at a delay angle α after their natural turn-on and a commutating reactance $X_c$ per phase, its DC voltage is

$$V_d = \frac{3\sqrt2}{\pi}V_{LL}\cos\alpha - \frac{3}{\pi}X_c I_d$$

where $V_{LL}$ is the RMS line voltage on the converter's AC side and $3\sqrt2/\pi \approx 1.35$. The rectifier runs at small α. The inverter at the other end runs past 90°, which makes $V_d$ negative there, so power flows from the AC system into the DC line at one end and out at the other. Both ends draw reactive power, roughly half the DC power, which shunt capacitors and filters supply, and they put harmonics of order 6k ± 1 into the AC system.

DC wins for long overhead links (a break-even near 600 to 800 km, set by converter cost against line savings), for undersea and underground cables (an AC cable's charging current uses up its rating within about 100 km), and for ties between grids that aren't synchronized. Its flow is set by the converters' controls rather than by network impedances.
:::

::: example
## An 800 kV surge on an overhead line ($Z_c$ = 400 Ω) reaches the junction with an underground cable ($Z_c$ = 40 Ω). What enters the cable, and what goes back?

::: solution
1. **Reflection coefficient.** The wave sees the cable's 40 Ω:
   $$\begin{aligned} \rho &= \frac{40 - 400}{40 + 400} \\ &= -0.818 \end{aligned}$$
2. **Reflected wave.** This travels back up the line:
   $$\begin{aligned} V_r &= 800 \times (-0.818) \\ &= -655\ \text{kV} \end{aligned}$$
3. **Transmitted wave.** This enters the cable:
   $$\begin{aligned} V_t &= 800(1 + \rho) \\ &= 800 \times 0.182 \\ &= 145\ \text{kV} \end{aligned}$$
4. **Check with currents.** The incident wave carries 800/400 = 2 kA, and the reflected one 1.64 kA forward (current reflects with −ρ), so 3.64 kA enters the cable.
5. **Compare with the cable.** The transmitted voltage drives the same current through 40 Ω:
   $$\begin{aligned} I_t &= V_t/40\ \Omega \\ &= 3.64\ \text{kA} \end{aligned}$$
6. **What it means.** A short cable section at a substation entrance knocks a surge down hard, though the wave then doubles when it reaches an open end of the cable.

**Answer:** 145 kV enters the cable, and −655 kV travels back up the line.
:::
:::

::: example
## A breaker closes a stiff 1 pu source onto a 300 km unloaded line (wave speed 295 km/ms). What happens at the far end, and what does a closing resistor equal to $Z_c$ do?

::: solution
1. **Travel time.**
   $$\begin{aligned} T &= 300/295 \\ &= 1.02\ \text{ms} \end{aligned}$$
2. **Reflection coefficients.** With no source resistance, $\rho_s = -1$, and the open end has ρ = +1.
3. **First arrival.** The first 1 pu wave reaches the far end at T and doubles it to 2 pu.
4. **The trip back.** Its reflection returns at 2T and reflects from the source as −1 pu, which arrives at the far end at 3T and takes the end back to 0.
5. **It repeats.** On a lossless line this repeats: 2, 0, 2, 0 pu every 2T. Losses damp it in practice, but the 2 pu crest is real.
6. **With a closing resistor.** With a resistor of $Z_c$ in series, the source launches only 0.5 pu. It doubles to 1 pu at the far end.
7. **Nothing comes back.** The reflection returns and meets $\rho_s = 0$ at the source, so the end steps once to its final value. The resistor is shorted out a few milliseconds later.

**Answer:** without the resistor the far end jumps to 2 pu and swings between 2 and 0 pu every 2T; with a resistor of $Z_c$ it steps once to 1 pu and stays there.
:::
:::

::: example
## A rectifier's valve-side line voltage is 200 kV RMS. It fires at α = 15° and carries 2 kA through a commutating reactance of 10 Ω. Find its DC voltage and the power one pole sends.

::: solution
1. **Ideal DC voltage.**
   $$\begin{aligned} V_{d0} &= 1.3505 \times 200 \\ &= 270.1\ \text{kV} \end{aligned}$$
2. **Firing delay.** It reduces that to
   $$\begin{aligned} V_{d0}\cos\alpha &= 270.1 \cos 15° \\ &= 260.9\ \text{kV} \end{aligned}$$
3. **Commutation overlap.** It costs
   $$\begin{aligned} \Delta V &= (3/\pi)(10)(2000) \\ &= 19.1\ \text{kV} \end{aligned}$$
   leaving $V_d$ = 241.8 kV.
4. **Power per pole.**
   $$\begin{aligned} P &= 241.8\ \text{kV} \times 2\ \text{kA} \\ &= 484\ \text{MW} \end{aligned}$$
   A bipole, one pole positive and one negative, sends twice that over two conductors.

**Answer:** $V_d$ = 241.8 kV, and one pole sends 484 MW.
:::
:::

::: example
## Surges reach a transformer (BIL 1300 kV) with fronts rising at 1000 kV/µs. Its arrester clamps at 800 kV, and a 20% margin is wanted. How far from the transformer may the arrester sit?

::: solution
1. **How the voltage builds.** The voltage at the transformer exceeds the arrester's by about twice the front's rise during the travel time from arrester to transformer:
   $$V_t = V_a + 2S\,d/v$$
2. **Allowed voltage.** With the 20% margin:
   $$\begin{aligned} V_t &\le 1300/1.2 \\ &= 1083\ \text{kV} \end{aligned}$$
3. **Solve for the distance.** With v = 300 m/µs:
   $$\begin{aligned} 2 \times 1000 \times d/300 &\le 283 \\ d &\le 42.5\ \text{m} \end{aligned}$$
4. **In practice.** That's why arresters are mounted at the transformer's bushings, not at the substation fence.

**Answer:** no more than 42.5 m from the transformer.
:::
:::

::: check
given: L = 0.9 | 1.0 | 1.2; C = 9 | 11 | 13
answer: sqrt(L*1e-3/(C*1e-9))
unit: Ω
tolerance: 0.5%

## An overhead line has L = {L} mH/km and C = {C} nF/km. What's its surge impedance?

::: right
Right. $Z_c = \sqrt{L/C}$ = {answer} Ω. The per-kilometer units cancel.
:::

::: misses
- [sqrt(L/C)] Convert to henries and farads before dividing.
- [any] Not yet. $Z_c = \sqrt{L/C}$.
:::
:::

::: check
given: d = 80 | 200 | 350; L = 0.9 | 1.1; C = 10 | 12
answer: d*sqrt(L*1e-3*C*1e-9)*1e6
unit: µs
tolerance: 0.5%

## How long does a surge take to travel {d} km along a line with L = {L} mH/km and C = {C} nF/km?

::: right
Right. $T = d\sqrt{LC}$ = {answer} µs, close to the speed of light.
:::

::: misses
- [d/sqrt(L*1e-3*C*1e-9)*1e6] That's the speed times the length. Divide the length by the speed.
- [any] Not yet. The speed is $1/\sqrt{LC}$ per kilometer.
:::
:::

::: check
given: R = 50 | 200 | 1000 | 5000; Z = 300 | 400
answer: (R - Z)/(R + Z)
tolerance: 0.5%

## A line with $Z_c$ = {Z} Ω ends in {R} Ω. What's the voltage reflection coefficient there?

::: right
Right. ρ = $(Z_R - Z_c)/(Z_R + Z_c)$ = {answer}.
:::

::: misses
- [(Z - R)/(R + Z)] That's the current's reflection coefficient. For voltage it's $(Z_R - Z_c)/(Z_R + Z_c)$.
- [any] Not yet. ρ = $(Z_R - Z_c)/(Z_R + Z_c)$.
:::
:::

::: check
given: V = 400 | 600 | 900; n = 2 | 3 | 4
answer: 2*V/(n + 1)
unit: kV
tolerance: 0.5%

## A {V} kV surge arrives at a substation bus where the line continues into {n} other lines, all with the same surge impedance. What voltage leaves along each of them?

::: right
Right. The wave sees the n lines in parallel, $Z_c/n$, so $1 + \rho = 2/(n + 1)$ and {answer} kV goes out along each.
:::

::: misses
- [V/n] It doesn't divide equally among the lines. Find ρ for $Z_c/n$.
- [2*V*n/(n + 1)] The bus sees the lines in parallel, $Z_c/n$.
- [any] Not yet. Find ρ for the other lines in parallel.
:::
:::

::: check
given: I = 10 | 20 | 40; Z = 300 | 450
answer: I/2*Z/1000
unit: MV
tolerance: 0.5%

## A {I} kA stroke hits a phase conductor of a line with $Z_c$ = {Z} Ω. What's the voltage of the surge on each side?

::: right
Right. Half the current runs each way, so $v = (I/2)Z_c$ = {answer} MV.
:::

::: misses
- [I*Z/1000] The current splits, half each way.
- [any] Not yet. Each half of the current travels with $v = Z_c i$.
:::
:::

::: check
given: s = 50 | 100 | 200 | 400; Z = 300 | 400
answer: 2*Z/(s + Z)
tolerance: 0.5%

## A 1 pu source with {s} Ω of internal resistance is switched onto an unloaded line with $Z_c$ = {Z} Ω. What's the far end's voltage, in per unit, when the first wave arrives?

::: right
Right. The first wave is $V Z_c/(R_s + Z_c)$, and the open end doubles it: {answer} pu.
:::

::: misses
- [Z/(s + Z)] That's the wave launched. The open end doubles it.
- [2] That's for a stiff source. The source resistance and $Z_c$ divide the step first.
- [any] Not yet. Launch through the divider, then double at the open end.
:::
:::

::: check
given: V = 150 | 200 | 250; a = 10 | 15 | 20; X = 8 | 12; I = 1.5 | 2 | 3
answer: 3*sqrt(2)/pi*V*cos(a*pi/180) - 3/pi*X*I
unit: kV
tolerance: 0.5%

## A rectifier has {V} kV RMS on its valve side, fires at α = {a}° and carries {I} kA through $X_c$ = {X} Ω. What's its DC voltage?

::: right
Right. $1.35 V_{LL}\cos\alpha - (3/\pi)X_c I_d$ = {answer} kV.
:::

::: misses
- [3*sqrt(2)/pi*V*cos(a*pi/180)] Subtract the overlap drop $(3/\pi)X_c I_d$.
- [3*sqrt(2)/pi*V - 3/pi*X*I] Include cos α for the firing delay.
- [any] Not yet. $V_d = 1.35 V_{LL}\cos\alpha - (3/\pi)X_c I_d$.
:::
:::

::: check
kind: parts
given: B = 650 | 1050 | 1550; m = 1.15 | 1.25; a = 400 | 600 | 900; S = 500 | 2000

## Equipment with a BIL of {B} kV is protected by an arrester clamping at {a} kV; surges rise at {S} kV/µs and travel at 300 m/µs. A margin of {m} is wanted.

::: part
answer: (B/m - a)*300/(2*S)
unit: m
tolerance: 0.5%

### How far from the equipment may the arrester be?

::: misses
- [(B/m - a)*300/S] Reflection at the equipment doubles the rise: $2Sd/v$.
- [any] $V_a + 2Sd/v \le \text{BIL}/m$.
:::
:::
:::

::: check
kind: derivation
vars: Z = 20..600, R = 1..10000, V = 1..2000

## A surge of V kV on a line of surge impedance Z reaches a termination of R ohms.

::: step
answer: (R - Z)/(R + Z)

### What is the voltage reflection coefficient?
:::

::: step
answer: V*2*R/(R + Z)

### What voltage appears at the termination?
:::

::: step
answer: V*2/(R + Z)

### What current flows into it, in kA?
:::

::: right
Right. The termination sees twice the incident voltage divided between R and Z: a Thévenin source of 2V behind Z.
:::
:::

::: explain
## Why does a surge double when it reaches an open breaker or a transformer, and how does that decide where arresters go?

::: model
A traveling wave of voltage always comes with a wave of current, related by the line's surge impedance. At an open end no current can flow, so a reflected wave must appear whose current cancels the incident current. A backward wave carries current opposite to its voltage, so cancelling the current takes a reflected voltage equal to the incident one, and the two add to twice the incident voltage. A transformer winding looks nearly like an open circuit to a microsecond surge because its inductance blocks the fast current. So the transformer terminal is where a surge reaches its highest voltage, and an arrester placed there, with short leads, clamps the voltage at the equipment it protects. An arrester some distance away sees less than the doubled crest and lets the terminal overshoot.
:::
:::

::: practice

::: check
given: L = 0.3..1.5; C = 8..300
answer: sqrt(L*1e-3/(C*1e-9))
unit: Ω
tolerance: 0.5%

## $Z_c$ for L = {L} mH/km, C = {C} nF/km?

::: misses
- [any] $\sqrt{L/C}$ in henries and farads.
:::
:::

::: check
given: R = 10..5000; Z = 30..500
answer: (R - Z)/(R + Z)
tolerance: 0.5%

## Reflection coefficient: $Z_c$ = {Z} Ω into {R} Ω?

::: misses
- [any] $(Z_R - Z_c)/(Z_R + Z_c)$.
:::
:::

::: check
given: V = 100..1000; Z = 300..500; K = 30..60
answer: 2*K/(K + Z)*V
unit: kV
tolerance: 0.5%

## A {V} kV surge on a {Z} Ω line meets a {K} Ω cable. What enters the cable?

::: misses
- [any] $(1 + \rho)V$ with $Z_R$ = the cable's $Z_c$.
:::
:::

::: check
given: V = 100..300; a = 5..25; X = 5..15; I = 1..3
answer: 3*sqrt(2)/pi*V*cos(a*pi/180) - 3/pi*X*I
unit: kV
tolerance: 0.5%

## Rectifier: {V} kV, α = {a}°, $X_c$ = {X} Ω, $I_d$ = {I} kA. $V_d$?

::: misses
- [any] $1.35 V_{LL}\cos\alpha - (3/\pi)X_c I_d$.
:::
:::

::: check
given: d = 50..500; u = 150..300
answer: d/u*1000
unit: µs
tolerance: 0.5%

## Travel time over {d} km at {u} km/ms?

::: misses
- [any] Length over speed.
:::
:::
:::