title: Symmetrical components
heading: Splitting any set of three unbalanced phasors into positive-, negative- and zero-sequence sets, the operator a and the transformation matrix, sequence impedances of lines, machines and transformers, and why a delta winding blocks zero-sequence current
eyebrow: S10 · Lesson 37 · Symmetrical components
xp: 50
---

::: hook
Per-phase analysis works only when the three phases are balanced. A single line touching ground isn't. In 1918 Charles Fortescue showed that any three unbalanced phasors are the sum of three balanced sets: one rotating in the normal order, one in reverse, and one with all three phases in step. Each set sees its own impedance and, in a symmetrical network, doesn't interact with the others. That turns an unbalanced three-phase problem into three balanced single-phase ones, and it's how every relay and fault program handles unbalance.
:::

::: play
- Three phase voltages with phase a fixed at 1∠0°, and phase b's magnitude and phase c's angle adjustable, together with their positive-, negative- and zero-sequence components (computed with $a = 1\angle 120°$).
- With balanced phases, only the positive sequence is present. Sag phase b and both a negative- and a zero-sequence component appear.
- The negative-sequence share, $|V_2|/|V_1|$, is the voltage unbalance that heats induction motors: a few percent is enough to matter.
:::

```sim plot
view: complex
range: 1.3
axes: Re, Im
slider: m = 0.5..1.2 = 0.9
slider: c = 100..140 = 120 °
arrow: 1 | label: Va
arrow: m*exp(-j*2*pi/3) | label: Vb
arrow: exp(j*c*pi/180) | label: Vc
arrow: (1 + m*exp(-j*2*pi/3)*exp(j*2*pi/3) + exp(j*c*pi/180)*exp(-j*2*pi/3))/3 | color: ch3 | label: V₁
arrow: (1 + m*exp(-j*2*pi/3)*exp(-j*2*pi/3) + exp(j*c*pi/180)*exp(j*2*pi/3))/3 | color: ch4 | label: V₂
arrow: (1 + m*exp(-j*2*pi/3) + exp(j*c*pi/180))/3 | color: ch5 | label: V₀
readout: unbalance |V₂|/|V₁|, % = 100*abs(1 + m*exp(-j*4*pi/3) + exp(j*c*pi/180)*exp(j*2*pi/3))/abs(1 + m + exp(j*c*pi/180)*exp(-j*2*pi/3)) | digits: 3
```

::: predict
## A single-phase load is connected between phases a and b, drawing $I_a = 10$ A and $I_b = -10$ A, with $I_c = 0$. How big are its sequence currents?

- [ ] All positive sequence, 10 A
- [x] Equal positive and negative sequence, 5.77 A each, and no zero sequence
- [ ] All zero sequence, 3.3 A
- [ ] 10 A of each

::: reveal
$I_0 = (I_a + I_b + I_c)/3$ = 0, and $I_1 = (I_a + aI_b + a^2I_c)/3$ = $10(1 - a)/3$, magnitude $10\sqrt{3}/3$ = 5.77 A, with $|I_2|$ the same. A line-to-line load is half positive and half negative sequence, which is why large single-phase loads unbalance the voltages seen by three-phase motors nearby.
:::
:::

::: nameit
## The transformation

With $a = 1\angle 120° = -\frac{1}{2} + j\frac{\sqrt{3}}{2}$ ($a^3 = 1$, $1 + a + a^2 = 0$):

$$\begin{pmatrix} V_a \\ V_b \\ V_c \end{pmatrix} = \begin{pmatrix} 1 & 1 & 1 \\ 1 & a^2 & a \\ 1 & a & a^2 \end{pmatrix}\begin{pmatrix} V_0 \\ V_1 \\ V_2 \end{pmatrix}, \qquad \begin{pmatrix} V_0 \\ V_1 \\ V_2 \end{pmatrix} = \frac{1}{3}\begin{pmatrix} 1 & 1 & 1 \\ 1 & a & a^2 \\ 1 & a^2 & a \end{pmatrix}\begin{pmatrix} V_a \\ V_b \\ V_c \end{pmatrix}$$

The **positive sequence** (1) has phases in the order a, b, c; the **negative sequence** (2) in the order a, c, b; the **zero sequence** (0) has all three equal. The neutral current is $I_n = I_a + I_b + I_c = 3I_0$.

## Sequence impedances

Each component sees its own network:

- **Lines:** $Z_1 = Z_2$; $Z_0$ two to four times larger, because zero-sequence current returns through the ground and ground wires.
- **Generators:** $Z_1$ is X″ for faults; $Z_2 \approx X''$; $Z_0$ small; a neutral grounding impedance $Z_n$ appears as $3Z_n$ in the zero-sequence network only.
- **Transformers:** $Z_1 = Z_2$ = leakage impedance; the zero-sequence path depends on the connection. A grounded Y passes zero-sequence current into its winding; a Δ winding circulates it internally but no zero-sequence current leaves on its lines; an ungrounded Y blocks it entirely.

## Phase shifts

A Y–Δ transformer shifts positive-sequence quantities by +30° (high side leading, US standard) and negative-sequence quantities by −30°.
:::

::: example
## Phase currents are 100∠0°, 80∠−120° and 90∠120° A. Find the sequence components and the neutral current.

::: solution
1. **Zero sequence.**
   $$\begin{aligned} I_0 &= \tfrac{1}{3}(100 + 80\angle{-120°} \\ &\quad + 90\angle 120°) \\ &= 5.77\angle 30°\ \text{A} \end{aligned}$$
2. **Positive and negative sequences.**
   $$\begin{aligned} I_1 &= 90\angle 0°\ \text{A} \\ I_2 &= 5.77\angle{-30°}\ \text{A} \end{aligned}$$
3. **Neutral current.**
   $$\begin{aligned} I_n &= 3|I_0| \\ &= 17.3\ \text{A} \end{aligned}$$
   even though no phase is far from its share.

**Answer:** $I_0 = 5.77\angle 30°$ A, $I_1 = 90\angle 0°$ A and $I_2 = 5.77\angle{-30°}$ A, and the neutral carries 17.3 A.
:::
:::

::: example
## Phase b's voltage sags to 0.9 pu with angles still 120° apart. How much negative-sequence unbalance results?

::: solution
1. **The phasors.** Here $V_b = 0.9a^2$ and $V_c = a$.
2. **Positive sequence.**
   $$\begin{aligned} V_1 &= (1 + 0.9a^3 + a^3)/3 \\ &= (1 + 0.9 + 1)/3 \\ &= 0.967\ \text{pu} \end{aligned}$$
3. **Negative sequence.**
   $$\begin{aligned} V_2 &= (1 + 0.9a^4 + a^2)/3 \\ &= (1 + 0.9a + a^2)/3 \\ &= -0.1a/3 \end{aligned}$$
   magnitude 0.033 pu.
4. **Unbalance.**
   $$\begin{aligned} V_2/V_1 &= 0.033/0.967 \\ &= 3.4\% \end{aligned}$$
5. **Why it matters.** Motor standards recommend derating above 1%, because negative-sequence voltage drives currents at nearly twice line frequency in the rotor.

**Answer:** 3.4% negative-sequence unbalance.
:::
:::

::: example
## A single-phase load draws 300 A from phase a of a four-wire system, with phases b and c unloaded. Find the sequence currents and the neutral current.

::: solution
1. **Sequence currents.** With $I_a$ = 300 A and $I_b = I_c = 0$, each sequence component is
   $$I_a/3 = 100\ \text{A}$$
   so $I_0$, $I_1$ and $I_2$ are all 100 A, in phase with $I_a$.
2. **Neutral current.**
   $$\begin{aligned} I_n &= 3I_0 \\ &= 300\ \text{A} \end{aligned}$$
   the whole load current returning.
3. **What it means.** A single-phase load is one-third positive sequence, the part a balanced system can use, and two-thirds unbalance.

**Answer:** $I_0$, $I_1$ and $I_2$ are each 100 A, in phase with $I_a$, and the neutral carries 300 A.
:::
:::

::: check
given: I = 5 | 20 | 300
answer: I/sqrt(3)
unit: A
tolerance: 0.5%

## A line-to-line load draws {I} A from phase a and returns it on phase b. How big is its positive-sequence current?

::: right
Right. $|I_1| = I|1 - a|/3 = I/\sqrt{3}$ = {answer} A, and $|I_2|$ is the same.
:::

::: misses
- [I/3] $|1 - a| = \sqrt{3}$, not 1.
- [I/2] The split is equal, but each part is $I/\sqrt{3}$, not I/2.
- [any] Not yet. $I_1 = (I_a + aI_b + a^2I_c)/3$.
:::
:::

::: check
given: A = 100 | 120; B = 70 | 90; C = 80 | 110
answer: abs(A + B*exp(-j*2*pi/3) + C*exp(j*2*pi/3))
unit: A
tolerance: 0.5%

## Phase currents are {A}∠0°, {B}∠−120° and {C}∠120° A. What's the neutral current?

::: right
Right. $|I_a + I_b + I_c| = 3|I_0|$ = {answer} A.
:::

::: misses
- [abs(A + B*exp(-j*2*pi/3) + C*exp(j*2*pi/3))/3] That's $|I_0|$; the neutral carries three times it.
- [any] Not yet. Add the phasors.
:::
:::

::: check
given: A = 100 | 120; B = 70 | 90; C = 80 | 110
answer: (A + B + C)/3
unit: A
tolerance: 0.5%

## For the same currents, what's the positive-sequence magnitude?

::: right
Right. Rotating phases b and c into phase a's position, $I_1 = (A + B + C)/3$ = {answer} A.
:::

::: misses
- [any] Not yet. $I_1 = (I_a + aI_b + a^2I_c)/3$, and here each rotated term lands on 0°.
:::
:::

::: check
given: m = 0.8 | 0.9 | 0.95
answer: 100*(1 - m)/(2 + m)
unit: %
tolerance: 0.5%

## Phase b's voltage sags to {m} pu while phases a and c stay at 1 pu, all 120° apart. What's the negative-sequence unbalance $|V_2|/|V_1|$?

::: right
Right. $V_1 = (2 + m)/3$ and $|V_2| = (1 - m)/3$, so the unbalance is $(1 - m)/(2 + m)$ = {answer}%.
:::

::: misses
- [100*(1 - m)] The sag is shared between negative and zero sequence and divided by 3, relative to $V_1$.
- [any] Not yet. Compute $V_1$ and $V_2$.
:::
:::

::: check
given: x = 0.1 | 0.3 | 0.5
answer: abs(exp(-j*2*pi/3) + x*exp(j*2*pi/3))
tolerance: 0.5%

## A voltage has $V_1$ = 1 pu, $V_2$ = {x} pu (both at 0° in phase a) and no zero sequence. What's the magnitude of phase b?

::: right
Right. $V_b = a^2V_1 + aV_2$, magnitude {answer} pu.
:::

::: misses
- [1 + x] The negative-sequence part of phase b is rotated the other way.
- [any] Not yet. $V_b = V_0 + a^2V_1 + aV_2$.
:::
:::

::: check
given: t = -20 | 0 | 45
answer: t - 30
unit: °
tolerance: 0.5%

## A negative-sequence voltage sits at {t}° on the low side of a standard Y–Δ transformer. At what angle does it appear on the high side?

::: right
Right. Negative sequence shifts the opposite way to positive: {answer}°.
:::

::: misses
- [t + 30] That's the shift for positive sequence.
- [any] Not yet. Positive sequence: high side leads by 30°; negative: lags by 30°.
:::
:::

::: check
kind: parts
given: I = 50 | 300 | 1200

## A single-phase load draws {I} A from phase a only of a four-wire system.

::: part
answer: I/3
unit: A
tolerance: 0.5%

### What is the positive-sequence current?

::: misses
- [I] Each sequence component is a third of the phase current.
- [any] $I_a/3$.
:::
:::

::: part
answer: I
unit: A
tolerance: 0.5%

### What flows in the neutral?

::: misses
- [any] $3I_0$.
:::
:::
:::

::: check
kind: derivation
vars: A = 50..500, B = 50..500, C = 50..500

## Phase currents of magnitudes A, B and C sit at the nominal angles 0°, −120° and 120°.

::: step
answer: (A + B + C)/3

### What is the positive-sequence magnitude?
:::

::: step
answer: sqrt((A - (B + C)/2)^2 + 0.75*(C - B)^2)/3

### What is the zero-sequence magnitude?
:::

::: step
answer: sqrt((A - (B + C)/2)^2 + 0.75*(B - C)^2)/3

### And the negative-sequence magnitude?
:::

::: right
Right. When only the magnitudes are unequal, the zero and negative sequences come out the same size.
:::
:::

::: explain
## Why does no zero-sequence current flow in the lines on the delta side of a transformer?

::: model
Zero-sequence currents are equal in all three phases at every instant. On a delta side, each line current is the difference between two winding currents, so three equal winding currents produce line currents of exactly zero: they circulate around the delta instead. If the other side is a grounded Y carrying zero-sequence current, the delta winding supplies the matching ampere-turns internally, but nothing leaves on its lines. That's why a grounded-Y–delta transformer isolates the ground faults on one side from the zero-sequence network on the other, and why it's the standard generator step-up connection.
:::
:::

::: practice

::: check
given: I = 12 | 20 | 50 | 100 | 150 | 400
answer: I/sqrt(3)
unit: A
tolerance: 0.5%

## $|I_2|$ for a line-to-line load of {I} A?

::: misses
- [any] $I/\sqrt{3}$.
:::
:::

::: check
given: m = 0.5 | 0.6 | 0.7 | 0.8 | 0.85 | 0.9 | 0.95
answer: 100*(1 - m)/(2 + m)
unit: %
tolerance: 0.5%

## Unbalance when phase b sags to {m}?

::: misses
- [any] $(1 - m)/(2 + m)$.
:::
:::

::: check
given: A = 50 | 80; B = 40 | 60; C = 30 | 70
answer: abs(A + B*exp(-j*2*pi/3) + C*exp(j*2*pi/3))
unit: A
tolerance: 0.5%

## Neutral current for {A}∠0°, {B}∠−120°, {C}∠120°?

::: misses
- [any] $|I_a + I_b + I_c|$.
:::
:::
:::