title: Unsymmetrical faults
heading: Single line-to-ground, line-to-line and double line-to-ground faults by connecting sequence networks, fault impedance, neutral grounding to limit ground-fault current, and how the fault types compare
eyebrow: S10 · Lesson 38 · Unsymmetrical faults
xp: 50
---

::: hook
About four out of five faults on overhead lines are single line-to-ground: one conductor flashing over to a tower or a tree. Fewer than one in twenty involves all three phases. Symmetrical components (lesson 37) turn each unbalanced fault into a simple connection of the positive-, negative- and zero-sequence networks at the fault point, so the currents follow from Ohm's law. This lesson builds those connections and shows why the way a transformer's neutral is grounded can matter more than the size of the generator behind it.
:::

::: play
- Fault currents at a bus with $Z_1 = Z_2$ = j0.25 and $Z_0$ = j0.35 pu (before grounding), against a neutral reactance $X_n$ in the grounding path.
- With solid grounding the single line-to-ground fault (3.53 pu) is nearly as large as the three-phase one (4 pu). The neutral reactance adds $3X_n$ to the zero-sequence network, cutting the ground-fault current without touching the others.
- Line-to-line faults don't involve ground at all, so they stay at $\sqrt{3}/(Z_1 + Z_2)$.
:::

```sim plot
view: graph
x: X = 0..0.5 pu
y: I = 0..5 pu
slider: z = 0.05..1 = 0.35
plot: 3/(0.5 + z + 3*X) | samples: 300 | label: line-to-ground
plot: 4 + 0*X | dashed | color: ch3 | label: three-phase
plot: sqrt(3)/0.5 + 0*X | dashed | color: ch4 | label: line-to-line
readout: neutral reactance for 3 pu ground-fault current = (1 - 0.5 - z)/3 | digits: 3
```

::: predict
## At a generator's terminals $Z_1$ = $Z_2$ = j0.25 pu and its solidly grounded neutral gives $Z_0$ = j0.1 pu. Which fault draws the most current?

- [ ] Three-phase, always
- [x] Single line-to-ground: 3/0.6 = 5 pu against the three-phase 4 pu
- [ ] Line-to-line
- [ ] They're all equal

::: reveal
The line-to-ground current is $3/(Z_1 + Z_2 + Z_0)$, which exceeds the three-phase $1/Z_1$ whenever $Z_0 < Z_1$. Generators have small zero-sequence reactance, so their neutrals are usually grounded through a resistor or reactor (or a distribution transformer and resistor) to keep ground-fault currents below the three-phase value.
:::
:::

::: nameit
## Connections at the fault (prefault voltage 1 pu, fault impedance $Z_f$)

- **Single line-to-ground (phase a):** the three sequence networks in series, $I_{a1} = I_{a2} = I_{a0} = \dfrac{1}{Z_1 + Z_2 + Z_0 + 3Z_f}$, and the fault current is $I_a = 3I_{a0}$.
- **Line-to-line (b to c):** positive and negative networks in parallel through $Z_f$, $I_{a1} = -I_{a2} = \dfrac{1}{Z_1 + Z_2 + Z_f}$, no zero sequence, and $|I_b| = |I_c| = \sqrt{3}|I_{a1}|$.
- **Double line-to-ground (b and c to ground):** the negative network in parallel with the zero network (plus $3Z_f$), the whole in series with the positive: $I_{a1} = \dfrac{1}{Z_1 + Z_2 \parallel (Z_0 + 3Z_f)}$, then current division gives $I_{a2}$ and $I_{a0}$; the ground carries $3I_{a0}$.
- **Three-phase:** positive network only, $I = 1/(Z_1 + Z_f)$.

The $Z$'s are the Thevenin impedances of each sequence network at the fault bus, found from the three sequence $Z_\text{bus}$ matrices.

## Grounding

A neutral impedance $Z_n$ appears as $3Z_n$ in the zero-sequence network only. Utilities ground transmission solidly (for fast, sure relaying and lower overvoltages on the healthy phases), and ground generators and some distribution through impedance to limit damage.

## Which is worst

With $Z_1 = Z_2$: line-to-line current is $\sqrt{3}/2$ = 0.87 of three-phase; line-to-ground exceeds three-phase if $Z_0 < Z_1$. Breakers are sized for the largest.
:::

::: example
## With $Z_1 = Z_2$ = j0.25 and $Z_0$ = j0.35 pu, find the current for each fault type.

::: solution
1. **Three-phase.**
   $$\begin{aligned} I_f &= 1/0.25 \\ &= 4.00\ \text{pu} \end{aligned}$$
2. **Line-to-ground.**
   $$\begin{aligned} I_f &= 3/0.85 \\ &= 3.53\ \text{pu} \end{aligned}$$
3. **Line-to-line.**
   $$\begin{aligned} I_f &= \sqrt{3}/0.5 \\ &= 3.46\ \text{pu} \end{aligned}$$
4. **Double line-to-ground.**
   $$\begin{aligned} I_{a1} &= \frac{1}{0.25 + 0.25 \parallel 0.35} \\ &= 1/0.396 \\ &= 2.53\ \text{pu} \end{aligned}$$
5. **Its zero sequence.**
   $$\begin{aligned} I_{a0} &= -2.53 \times 0.25/0.6 \\ &= -1.05\ \text{pu} \end{aligned}$$
   so the ground carries 3.16 pu and each faulted phase 3.81 pu.

**Answer:** 4.00 pu for a three-phase fault, 3.53 pu line-to-ground, 3.46 pu line-to-line, and 3.81 pu in each faulted phase for double line-to-ground (3.16 pu in the ground).
:::
:::

::: example
## What neutral reactance limits the line-to-ground current at that bus to 3 pu?

::: solution
1. **Set the current.**
   $$\begin{aligned} Z_1 + Z_2 + Z_0 + 3X_n &= 3/3 \\ &= 1 \end{aligned}$$
2. **Solve.**
   $$\begin{aligned} 3X_n &= 1 - 0.85 \\ &= 0.15 \end{aligned}$$
   so $X_n$ = 0.05 pu.
3. **Fault resistance instead.** A fault resistance does something similar but adds in quadrature: 0.1 pu of $R_f$ gives
   $$\begin{aligned} I_f &= 3/|j0.85 + 0.3| \\ &= 3.33\ \text{pu} \end{aligned}$$

**Answer:** $X_n$ = 0.05 pu.
:::
:::

::: example
## A 13.8 kV bus has $Z_1 = Z_2$ = j0.2 and $Z_0$ = j0.1 pu on 100 MVA. What neutral resistor limits single line-to-ground faults to 400 A?

::: solution
1. **Current in per unit.** The base current is 4184 A, so
   $$\begin{aligned} I_f &= 400/4184 \\ &= 0.0956\ \text{pu} \end{aligned}$$
2. **Impedance needed.**
   $$\begin{aligned} |j0.5 + 3R_n| &= 3/0.0956 \\ &= 31.4\ \text{pu} \end{aligned}$$
   so $R_n$ = 10.46 pu.
3. **In ohms.** With $Z_\text{base} = 13.8^2/100 = 1.904$ Ω:
   $$\begin{aligned} R_n &= 10.46 \times 1.904\ \Omega \\ &= 19.9\ \Omega \end{aligned}$$
4. **Why low-resistance grounding.** Low-resistance grounding like this keeps ground-fault currents to hundreds of amperes, enough for relays to see but far too little to damage machine windings.

**Answer:** a 19.9 Ω neutral resistor (10.46 pu).
:::
:::

::: check
given: a = 0.15 | 0.25; b = 0.15 | 0.25; c = 0.05 | 0.3 | 0.6
answer: 3/(a + b + c)
tolerance: 0.5%

## A bus has $Z_1$ = j{a}, $Z_2$ = j{b} and $Z_0$ = j{c} pu. What's the bolted single line-to-ground fault current?

::: right
Right. $3/(Z_1 + Z_2 + Z_0)$ = {answer} pu.
:::

::: misses
- [1/(a + b + c)] That's one sequence current; the phase current is three times it.
- [any] Not yet. Sequence networks in series.
:::
:::

::: check
given: a = 0.12 | 0.2 | 0.3; b = 0.12 | 0.2 | 0.3
answer: sqrt(3)/(a + b)
tolerance: 0.5%

## With $Z_1$ = j{a} and $Z_2$ = j{b} pu, what's the current in phase b for a bolted b–c fault?

::: right
Right. $\sqrt{3}/(Z_1 + Z_2)$ = {answer} pu.
:::

::: misses
- [1/(a + b)] That's $I_{a1}$; the phase current is $\sqrt{3}$ times it.
- [any] Not yet. Positive and negative networks in parallel, then $I_b = -j\sqrt{3}I_{a1}$.
:::
:::

::: check
given: a = 0.15 | 0.25; c = 0.2 | 0.5; I = 1.5 | 2.2
answer: (3/I - 2*a - c)/3
tolerance: 0.5%

## A bus has $Z_1 = Z_2$ = j{a} and $Z_0$ = j{c} pu with solid grounding. What neutral reactance limits a line-to-ground fault to {I} pu?

::: right
Right. $3X_n = 3/I - (Z_1 + Z_2 + Z_0)$, so $X_n$ = {answer} pu.
:::

::: misses
- [3/I - 2*a - c] The neutral impedance appears as $3X_n$.
- [any] Not yet. Solve $3/(Z_1 + Z_2 + Z_0 + 3X_n) = I$.
:::
:::

::: check
given: a = 0.15 | 0.3; c = 0.1 | 0.4
answer: 3*(1/(a + a*c/(a + c)))*a/(a + c)
tolerance: 0.5%

## A bus has $Z_1 = Z_2$ = j{a} and $Z_0$ = j{c} pu. How much current flows into the ground for a bolted double line-to-ground fault?

::: right
Right. $I_{a1} = 1/(Z_1 + Z_2\parallel Z_0)$, $|I_{a0}| = |I_{a1}|Z_2/(Z_2 + Z_0)$, and the ground carries $3|I_{a0}|$ = {answer} pu.
:::

::: misses
- [(1/(a + a*c/(a + c)))*a/(a + c)] That's $|I_{a0}|$; the ground carries three times it.
- [any] Not yet. Divide $I_{a1}$ between the negative and zero networks.
:::
:::

::: check
given: a = 0.15 | 0.25; c = 0.2 | 0.4; r = 0.05 | 0.2
answer: 3/sqrt((2*a + c)^2 + (3*r)^2)
tolerance: 0.5%

## A line-to-ground fault through {r} pu of resistance occurs at a bus with $Z_1 = Z_2$ = j{a} and $Z_0$ = j{c}. What's the fault current?

::: right
Right. $3/|j(2Z_1 + Z_0) + 3R_f|$ = {answer} pu.
:::

::: misses
- [3/(2*a + c + 3*r)] The resistance adds in quadrature with the reactances.
- [any] Not yet. $3Z_f$ adds to the series loop.
:::
:::

::: check
given: a = 0.15 | 0.25; c = 0.05 | 0.1 | 0.4
answer: 3/(2*a + c)/(1/a)
tolerance: 0.5%

## A generator has $Z_1 = Z_2$ = j{a} and $Z_0$ = j{c}, solidly grounded. What's the ratio of line-to-ground to three-phase fault current at its terminals?

::: right
Right. $\frac{3/(2Z_1 + Z_0)}{1/Z_1}$ = {answer}: above 1 whenever $Z_0 < Z_1$.
:::

::: misses
- [(1/a)/(3/(2*a + c))] That's three-phase over line-to-ground.
- [any] Not yet. Compute both currents.
:::
:::

::: check
kind: parts
given: V = 4.16 | 13.8 | 34.5; a = 0.1 | 0.3; c = 0.05 | 0.2; I = 200 | 400 | 1000

## A {V} kV bus has $Z_1 = Z_2$ = j{a} and $Z_0$ = j{c} pu on 100 MVA. A neutral resistor must limit ground faults to {I} A.

::: part
answer: sqrt((3/(I/(100e6/(sqrt(3)*V*1e3))))^2 - (2*a + c)^2)/3*V^2/100
unit: Ω
tolerance: 0.5%

### What resistance does it need?

::: misses
- [any] $|j(Z_1 + Z_2 + Z_0) + 3R_n| = 3/I_f$ in per unit, then convert with $Z_\text{base}$.
:::
:::
:::

::: check
kind: derivation
vars: a = 0.05..0.5, c = 0.02..1, r = 0..5

## A bus has $Z_1 = Z_2$ = ja and $Z_0$ = jc pu; a line-to-ground fault occurs through resistance r.

::: step
answer: 3/sqrt((2*a + c)^2 + 9*r^2)

### What is the fault current in per unit?
:::

::: step
answer: 3/(2*a + c)

### What would it be for a bolted fault?
:::

::: right
Right. The fault resistance enters three times, once for each sequence network in series.
:::
:::

::: explain
## Why do the three sequence networks connect in series for a single line-to-ground fault?

::: model
A bolted fault from phase a to ground with the other phases open imposes three conditions: $V_a = 0$, $I_b = 0$ and $I_c = 0$. Transforming the two current conditions into sequence quantities shows that the three sequence currents must be equal, $I_{a0} = I_{a1} = I_{a2}$, and the voltage condition says the three sequence voltages at the fault must add to zero. Equal currents through three elements whose voltages sum to zero is exactly a series loop, so the positive network's source drives one current through all three networks' Thevenin impedances in turn. The phase current is the sum of the three equal sequence currents, three times each.
:::
:::

::: practice

::: check
given: a = 0.1 | 0.3; b = 0.1 | 0.3; c = 0.08 | 0.5
answer: 3/(a + b + c)
tolerance: 0.5%

## Line-to-ground current: $Z_1$ = {a}, $Z_2$ = {b}, $Z_0$ = {c}?

::: misses
- [any] $3/(Z_1 + Z_2 + Z_0)$.
:::
:::

::: check
given: a = 0.1 | 0.35; b = 0.1 | 0.35
answer: sqrt(3)/(a + b)
tolerance: 0.5%

## Line-to-line current: $Z_1$ = {a}, $Z_2$ = {b}?

::: misses
- [any] $\sqrt{3}/(Z_1 + Z_2)$.
:::
:::

::: check
given: a = 0.2 | 0.3; c = 0.15 | 0.45; I = 1.5 | 2.5
answer: (3/I - 2*a - c)/3
tolerance: 0.5%

## Neutral reactance limiting ground faults to {I} pu ($Z_1 = Z_2$ = {a}, $Z_0$ = {c})?

::: misses
- [any] $(3/I - Z_1 - Z_2 - Z_0)/3$.
:::
:::
:::