title: Voltage stability
heading: How much load a network can carry before its voltage collapses: P–V curves and the nose, loadability with power factor, Q–V curves and reactive margins, and the role of load behavior and tap changers
eyebrow: S10 · Lesson 14 · Voltage stability
xp: 50
---

::: hook
Several of the largest blackouts, Tokyo in 1987, the western United States in 1996, the northeastern United States and Canada in 2003, ended with voltages sliding down over seconds or minutes until protection tripped everything. No generator lost synchronism first; the network simply couldn't deliver the reactive power its loads demanded. Lesson 7 found that a line's power transfer has a maximum. This lesson follows that maximum: where it lies, how load power factor moves it, how to measure the distance to it, and why the loads themselves can drive a system over the edge.
:::

::: play
- The solid curve is the load bus voltage of the two-bus system (E = 1 pu behind X = 0.5 pu) against loading, as a fraction of the maximum, for a load at the power factor angle set by the slider (positive is lagging).
- The dashed curve is the second, low-voltage solution. The two meet at the nose, where the loading is at its maximum and the voltage at its critical value.
- Make the load leading (negative angle) and the nose moves up toward 1 pu: with compensated loads the voltage can look healthy almost all the way to collapse.
:::

```sim plot
view: graph
x: x = 0..0.999
y: V = 0..1.2
slider: t = -30..30 = 25
plot: sqrt((1 - x*sin(t*pi/180)/(1 + sin(t*pi/180)) + sqrt((1 - x*sin(t*pi/180)/(1 + sin(t*pi/180)))^2 - x^2/(1 + sin(t*pi/180))^2))/2) | label: operating voltage
plot: sqrt((1 - x*sin(t*pi/180)/(1 + sin(t*pi/180)) - sqrt((1 - x*sin(t*pi/180)/(1 + sin(t*pi/180)))^2 - x^2/(1 + sin(t*pi/180))^2))/2) | dashed | label: low-voltage solution
```

::: predict
## A load bus holds 0.97 pu, its loads heavily compensated with capacitors. What does that voltage say about its distance from voltage collapse?

- [ ] It's far from collapse: the voltage is nearly normal
- [x] Not much: with leading or compensated loads, the critical voltage at the nose can be close to normal, so the bus may be near its limit
- [ ] It's already collapsing
- [ ] Collapse can only happen below 0.7 pu

::: reveal
The critical voltage at the nose is $E/\sqrt{2(1 + \sin\phi)}$: 0.71 pu for a unity-power-factor load but 1.0 pu for a load whose power factor angle is −30°. Capacitors hold the voltage up as load grows, hiding how close the system is to the edge. That's why operators watch reactive reserves and computed margins, not voltage alone.
:::
:::

::: nameit
## The P–V curve

For a source E behind reactance X feeding a load P + jQ with Q = P tan φ, the load voltage solves
$$V^4 + (2QX - E^2)V^2 + X^2(P^2 + Q^2) = 0$$
which has two positive solutions up to a maximum loading and none beyond. At the **nose**,
$$P_\max = \frac{E^2\cos\phi}{2X(1 + \sin\phi)}, \qquad V_\text{cr} = \frac{E}{\sqrt{2(1 + \sin\phi)}}$$
A lagging load (φ > 0) lowers both; a leading one raises both. The power flow's Jacobian becomes singular at the nose (lesson 19), so Newton's method fails there.

## Margins

The **loadability margin** is the extra load, usually as a percentage, before the nose. The **reactive margin** comes from the **Q–V curve**: the reactive power a fictitious compensator at the bus must supply to hold each voltage. Its minimum, how much more the bus could absorb before no voltage is possible, is the margin. For the two-bus system at unity power factor,
$$Q_\text{margin} = \frac{E^4/4 - P^2X^2}{E^2X}$$
and $dV/dQ$, the slope of the curve, is positive and small on the stable side.

## Load behavior

Loads aren't constant power. A constant-impedance load takes $P \propto V^2$, so falling voltage lowers its demand and helps; motors and electronic loads behave closer to constant power. **Load tap changers** restore distribution voltages over tens of seconds, which turns impedance-like loads back into constant-power ones, and a tap changer that keeps raising the secondary voltage at a weak bus can pull the transmission voltage down past the nose: the slow collapse seen in 1987 and 2003. Remedies are reactive reserves (generators, SVCs, STATCOMs), switched capacitors, blocking tap changers, and as a last resort undervoltage load shedding.
:::

::: example
## A 1 pu source feeds a 0.9-power-factor-lagging load through X = 0.2 pu. Find the maximum loading, the critical voltage, and the voltage and margin at 1 pu of load.

::: solution
1. **Maximum loading.** With sin φ = 0.436:
   $$\begin{aligned} P_\max &= \frac{0.9}{2 \times 0.2 \times 1.436} \\ &= 1.567\ \text{pu} \end{aligned}$$
2. **Critical voltage.**
   $$\begin{aligned} V_\text{cr} &= 1/\sqrt{2 \times 1.436} \\ &= 0.590\ \text{pu} \end{aligned}$$
3. **Voltage at 1 pu of load.** At P = 1 (Q = 0.484) the quartic becomes
   $$V^4 - 0.806V^2 + 0.0494 = 0$$
   so $V^2$ = 0.739 and V = 0.860 pu.
4. **Margin.** The loadability margin is 57%, though the voltage is already 14% low.

**Answer:** $P_\max$ = 1.567 pu at a critical voltage of 0.590 pu; at 1 pu of load the voltage is 0.860 pu, with a 57% margin.
:::
:::

::: example
## A tap changer raises a distribution bus by 5%. How much more power does a constant-impedance load there take, and why can that hurt?

::: solution
1. **Extra power.** $P \propto V^2$, so
   $$1.05^2 = 1.1025$$
   which is 10.25% more power.
2. **What the sag was doing.** Right after a disturbance the sagging voltage had cut the load's demand, relieving the transmission system.
3. **What the tap changer does.** Restoring the voltage brings that demand back, drawing more current through the weakened network, which lowers the transmission voltage further, and the tap changer responds again.
4. **The fix.** Blocking tap changers during emergencies breaks the cycle.

**Answer:** 10.25% more power, and restoring that demand after a disturbance drags the weakened transmission voltage further down.
:::
:::

::: example
## For the two-bus system with E = 1 pu, X = 0.2 pu and a 1 pu unity-power-factor load, find the reactive margin from the Q–V curve.

::: solution
1. **The Q–V curve.** The compensation needed to hold V is
   $$Q_c = \frac{V^2 - \sqrt{E^2V^2 - P^2X^2}}{X}$$
2. **Where it bottoms out.**
   $$\begin{aligned} V &= \sqrt{E^2/4 + P^2X^2/E^2} \\ &= 0.539\ \text{pu} \end{aligned}$$
3. **Compensation at the minimum.**
   $$\begin{aligned} Q_c &= \frac{P^2X^2 - E^4/4}{E^2X} \\ &= -1.05\ \text{pu} \end{aligned}$$
4. **Reactive margin.** So the bus could absorb another 1.05 pu of reactive load before no operating point remained: its reactive margin.
5. **At nominal voltage.** At V = 1 pu the curve says the bus needs 0.10 pu of support to hold nominal voltage.

**Answer:** a reactive margin of 1.05 pu, from the curve's minimum at 0.539 pu.
:::
:::

::: check
kind: parts
given: E = 1 | 1.05; X = 0.1 | 0.3 | 0.5; f = 0.8 | 0.85 | 0.95

## A source of {E} pu feeds a load at power factor {f} lagging through X = {X} pu.

::: part
answer: E^2*f/(2*X*(1 + sqrt(1 - f^2)))
tolerance: 0.5%

### What is the maximum load?

::: misses
- [E^2/(2*X)] That ignores the power factor.
- [any] $E^2\cos\phi/(2X(1 + \sin\phi))$.
:::
:::

::: part
answer: E/sqrt(2*(1 + sqrt(1 - f^2)))
tolerance: 0.5%

### What is the critical voltage at the nose?

::: misses
- [any] $E/\sqrt{2(1 + \sin\phi)}$.
:::
:::
:::

::: check
kind: parts
given: P = 0.5 | 1 | 1.5; X = 0.1 | 0.2; f = 0.9 | 0.95

## A 1 pu source feeds {P} pu at power factor {f} lagging through X = {X} pu.

::: part
answer: sqrt((1 - 2*P*sqrt(1 - f^2)/f*X + sqrt((2*P*sqrt(1 - f^2)/f*X - 1)^2 - 4*X^2*P^2/f^2))/2)
tolerance: 0.5%

### What is the load voltage?

::: misses
- [any] The larger root of $V^4 + (2QX - 1)V^2 + X^2(P^2 + Q^2) = 0$.
:::
:::

::: part
answer: (f/(2*X*(1 + sqrt(1 - f^2)))/P - 1)*100
unit: %
tolerance: 0.5%

### What is the loadability margin?

::: misses
- [any] $(P_\max - P)/P$.
:::
:::
:::

::: check
kind: parts
given: P = 0.5 | 1 | 2; X = 0.05 | 0.1 | 0.2

## A 1 pu source feeds {P} pu at unity power factor through X = {X} pu.

::: part
answer: (0.25 - P^2*X^2)/X
tolerance: 0.5%

### What is the bus's reactive margin?

::: misses
- [any] $(E^4/4 - P^2X^2)/(E^2X)$.
:::
:::

::: part
answer: sqrt(0.25 + P^2*X^2)
tolerance: 0.5%

### At what voltage is the Q–V curve's minimum?

::: misses
- [any] $V = \sqrt{E^2/4 + P^2X^2/E^2}$.
:::
:::
:::

::: check
kind: parts
given: t = 2 | 5 | 10; n = 1 | 2

## A tap changer raises a load bus by {t}%; the load's power varies as $V^n$ with n = {n}.

::: part
answer: ((1 + t/100)^n - 1)*100
unit: %
tolerance: 0.5%

### By how much does the load's power rise?

::: misses
- [any] $(1 + t)^n - 1$.
:::
:::
:::

::: check
kind: parts
given: a = -30 | -15 | 0 | 15 | 30

## A load's power factor angle is {a}° (negative is leading), fed from 1 pu.

::: part
answer: 1/sqrt(2*(1 + sin(a*pi/180)))
tolerance: 0.5%

### What is the critical voltage at the nose?

::: misses
- [any] $1/\sqrt{2(1 + \sin\phi)}$.
:::
:::
:::

::: check
kind: parts
given: S = 500 | 2000 | 8000; Q = 50 | 200

## A {Q} Mvar capacitor bank is switched at a bus whose short-circuit level is {S} MVA.

::: part
answer: Q/S*100
unit: %
tolerance: 0.5%

### Roughly how much does it raise the voltage?

::: misses
- [any] $\Delta V \approx \Delta Q/S_{sc}$.
:::
:::

::: part
answer: (1 - 1/(1 + Q/S)^2)*100
unit: %
tolerance: 1%

### If the voltage then sagged by that same fraction, how much of its output would the capacitor lose?

::: misses
- [any] Its output goes as $V^2$.
:::
:::
:::

::: check
kind: choice

## Why can blocking on-load tap changers during a voltage emergency stop a slow voltage collapse?

- [ ] It raises the generators' output
- [x] Tap changers restore load voltages, and with them load power, after the transmission voltage sags; blocking them lets the lower voltage keep the load's demand down, relieving the stressed transmission network instead of pushing it past the nose
- [ ] It disconnects the loads
- [ ] It changes the network's reactance

::: misses
- [1] It doesn't affect generation.
- [3] Loads stay connected, at lower voltage.
- [4] The network is unchanged; the load's behavior is what changes.
:::
:::

::: check
kind: derivation
vars: E = 0.9..1.1, X = 0.05..0.5, s = -0.5..0.5

## A source E behind X feeds a load whose power factor angle has sine s.

::: step
answer: E^2*sqrt(1 - s^2)/(2*X*(1 + s))

### What is the maximum load?
:::

::: step
answer: E/sqrt(2*(1 + s))

### What is the critical voltage?
:::

::: right
Right. Both depend on the power factor through $1 + \sin\phi$: reactive load costs real loadability.
:::
:::

::: check
kind: python

## Write `load_voltage(P, Q, X, E)`: the operating (higher) load voltage of the two-bus system, or None beyond the nose, and `max_load(pf, X, E)`: the largest P at the given lagging power factor, found by bisection on whether `load_voltage` has a solution.

```python starter
def load_voltage(P, Q, X, E):
    return E

def max_load(pf, X, E):
    return E * E / (2 * X)
```

```python solution
import math

def load_voltage(P, Q, X, E):
    b = 2 * Q * X - E * E
    c = X * X * (P * P + Q * Q)
    d = b * b - 4 * c
    if d < 0:
        return None
    return math.sqrt((-b + math.sqrt(d)) / 2)

def max_load(pf, X, E):
    t = math.sqrt(1 - pf * pf) / pf
    lo, hi = 0.0, 10 * E * E / X
    for _ in range(200):
        mid = (lo + hi) / 2
        if load_voltage(mid, mid * t, X, E) is None:
            hi = mid
        else:
            lo = mid
    return lo
```

```python tests
import math
assert abs(load_voltage(1, 0.4843, 0.2, 1) - 0.860) < 1e-3, "The worked example: 0.860 pu."
assert load_voltage(2, 0.97, 0.2, 1) is None, "Past the nose: no solution."
s = math.sin(math.acos(0.9))
assert abs(max_load(0.9, 0.2, 1) - 0.9 / (2 * 0.2 * (1 + s))) < 1e-9, "Bisection finds the formula's 1.567 pu."
assert abs(max_load(1.0, 0.5, 1) - 1.0) < 1e-9, "Unity power factor: E²/2X."
```

::: right
Right. The discriminant reaching zero is the nose; numerical continuation methods trace the same curve on real networks.
:::
:::

::: explain
## Why does voltage collapse often develop over minutes rather than instantly after a disturbance?

::: model
Right after a disturbance the network can usually still find an operating point, because the sagging voltage reduces the power drawn by impedance-like loads and generators briefly supply extra reactive power. Over the following seconds and minutes, slower controls act: tap changers raise distribution voltages and restore the load's power, thermostatically controlled loads stay on longer, and generators hit their field current limits and stop supplying more vars. Each of these pushes the operating point toward the nose of the P–V curve, and when the restored demand exceeds what the weakened network can deliver, no operating point remains and the voltage slides down. That slow progression is why operators have time to act, by blocking tap changers, adding reactive support or shedding load.
:::
:::

::: practice
::: check
given: X = 0.2 | 0.4; f = 0.9 | 1
answer: f/(2*X*(1 + sqrt(1 - f^2)))
tolerance: 0.5%

## Maximum load through X = {X} pu at pf {f} lagging, from 1 pu?

::: misses
- [any] $\cos\phi/(2X(1 + \sin\phi))$.
:::
:::

::: check
given: f = 0.7 | 0.75 | 0.8 | 0.85 | 0.9 | 0.95
answer: 1/sqrt(2*(1 + sqrt(1 - f^2)))
tolerance: 0.5%

## Critical voltage at pf {f} lagging?

::: misses
- [any] $1/\sqrt{2(1 + \sin\phi)}$.
:::
:::

::: check
given: P = 0.8 | 1.5; X = 0.1 | 0.2
answer: (0.25 - P^2*X^2)/X
tolerance: 0.5%

## Reactive margin: P = {P}, X = {X}, unity pf?

::: misses
- [any] $(1/4 - P^2X^2)/X$.
:::
:::
:::