title: Line-commutated rectifiers
heading: Single-phase and three-phase diode bridges, phase control with thyristors and inverter operation, commutation overlap from source inductance, the 6k ± 1 harmonics of six-pulse bridges, and twelve-pulse cancellation
eyebrow: S11 · Lesson 30 · Line-commutated rectifiers
xp: 50
---

::: hook
The rectifiers at the front of industrial drives, welders, electrochemical plants and HVDC terminals are still mostly diodes and thyristors switched by the AC line itself, not by a high-frequency clock. They're rugged and efficient, but their current comes in blocks that inject harmonics at fixed orders, and the line's own inductance stretches each commutation, costing output voltage. This lesson analyzes the six-pulse bridge that most of them are built from.
:::

::: play
- The DC output of a three-phase six-pulse thyristor bridge against its firing angle α: $V_{dc} = 1.35V_{LL}\cos\alpha - \frac{3}{\pi}\omega L_sI_d$, with source inductance $L_s$ and DC current $I_d$.
- At α = 0 it acts as a diode bridge. Beyond 90° the average voltage goes negative while the current keeps its direction: the converter feeds power back to the AC line as an inverter.
- The commutation term subtracts a load-dependent drop, like an internal resistance that dissipates nothing.
:::

```sim plot
view: graph
x: a = 0..170 °
y: V = -800..800 V
slider: E = 208..690 = 480 V
slider: L = 0..1 = 0.2 mH
slider: I = 0..300 = 100 A
plot: 1.3505*E*cos(a*pi/180) - 3/pi*377*L*1e-3*I | samples: 400 | label: DC output
plot: 0*a | dashed | color: ch3
readout: diode-bridge output (α of 0), V = 1.3505*E - 3/pi*377*L*1e-3*I | digits: 4
readout: commutation drop, V = 3/pi*377*L*1e-3*I | digits: 3
```

::: predict
## A three-phase diode bridge runs from 480 V line to line with a large DC inductor. What's its DC output?

- [ ] 480 V
- [ ] 679 V, the line-to-line peak
- [x] About 648 V
- [ ] About 432 V

::: reveal
The output follows the highest line-to-line voltage at each instant: six 60° segments of a sine near its peak, averaging $\frac{3\sqrt{2}}{\pi}V_{LL} = 1.35 \times 480$ = 648 V. With a large capacitor instead of an inductor and light load, it would charge toward the 679 V peak.
:::
:::

::: nameit
## Single-phase bridge

With a large DC inductor, the output averages $\frac{2\sqrt{2}}{\pi}V_\text{rms} = 0.90V_\text{rms}$, and the line current is a square wave (distortion factor 0.90). With a capacitor instead, the output charges near the peak and the line current is narrow pulses (lesson 29).

## Three-phase six-pulse bridge

$$V_{dc} = \frac{3\sqrt{2}}{\pi}V_{LL}\cos\alpha = 1.35V_{LL}\cos\alpha$$

with α the thyristors' firing delay (α = 0 for diodes). For α > 90° the average is negative: the bridge inverts, used in HVDC and regenerative drives. Each line current is a 120° block of height $I_d$: $I_\text{rms} = \sqrt{2/3}\,I_d$, fundamental RMS $\frac{\sqrt{6}}{\pi}I_d$, and harmonics of order $h = 6k \pm 1$ (5, 7, 11, 13, ...) with amplitudes $I_1/h$.

## Commutation overlap

Source inductance $L_s$ keeps the outgoing phase's current from dropping instantly; during the overlap two phases conduct and the output loses

$$\Delta V = \frac{3}{\pi}\omega L_sI_d$$

a drop proportional to load that dissipates no power.

## Twelve pulses

Two six-pulse bridges fed from Y–Y and Y–Δ transformers (30° apart) cancel the 5th and 7th harmonics at the line, leaving 11, 13, 23, 25, ...: the standard for large rectifiers and HVDC.
:::

::: example
## A 480 V six-pulse thyristor bridge with 0.2 mH of source inductance carries 100 A. Find its output at α = 30°.

::: solution
1. **Ideal output.**
   $$\begin{aligned} V_0 &= 1.35 \times 480 \times \cos 30° \\ &= 561\ \text{V} \end{aligned}$$
2. **Overlap drop.**
   $$\begin{aligned} \Delta V &= \frac{3}{\pi} \times 377 \times 0.2\text{ mH} \times 100 \\ &= 7.2\ \text{V} \end{aligned}$$
3. **Output.**
   $$\begin{aligned} V &= 561 - 7.2 \\ &= 554\ \text{V} \end{aligned}$$
4. **Inverting.** At α = 150° the same bridge would produce −561 V (less overlap), returning power to the line.

**Answer:** the bridge puts out 554 V.
:::
:::

::: example
## What are the line current's RMS, fundamental and dominant harmonics for $I_d$ = 100 A?

::: solution
1. **RMS line current.**
   $$\begin{aligned} I_\text{rms} &= \sqrt{2/3} \times 100\ \text{A} \\ &= 81.6\ \text{A} \end{aligned}$$
2. **Fundamental.**
   $$\begin{aligned} I_1 &= \frac{\sqrt{6}}{\pi} \times 100\ \text{A} \\ &= 78.0\ \text{A} \end{aligned}$$
   RMS, a distortion factor of 0.955.
3. **Dominant harmonics.** Each is $I_1/h$:
   $$\begin{aligned} I_5 &= 78.0/5 \\ &= 15.6\ \text{A} \\ I_7 &= 11.1\ \text{A} \\ I_{11} &= 7.1\ \text{A} \end{aligned}$$

**Answer:** 81.6 A RMS with a 78.0 A fundamental, and harmonics of 15.6 A (5th), 11.1 A (7th) and 7.1 A (11th).
:::
:::

::: example
## Compare the line-current THD of an ideal six-pulse bridge with a twelve-pulse arrangement of two bridges fed 30° apart.

::: solution
1. **Six pulses.** The line current contains harmonics 6k ± 1 with amplitudes $I_1/h$: 5, 7, 11, 13 and on. Their root-sum-square is
   $$\begin{aligned} \text{THD} &= \sqrt{1/5^2 + 1/7^2 + \cdots} \\ &= 31.1\% \end{aligned}$$
2. **Twelve pulses.** The twelve-pulse connection cancels the 5th, 7th, 17th, 19th and so on, leaving 12k ± 1: 11, 13, 23, 25:
   $$\begin{aligned} \text{THD} &= \sqrt{1/11^2 + 1/13^2 + \cdots} \\ &= 15.2\% \end{aligned}$$
3. **The fundamental.** It's the same in each case:
   $$\begin{aligned} I_1 &= (\sqrt6/\pi)I_d \\ &= 0.780I_d \end{aligned}$$
4. **Where it's used.** Large drives and HVDC terminals use twelve or more pulses to meet harmonic limits with smaller filters.

**Answer:** 31.1% THD for six pulses against 15.2% for twelve.
:::
:::

::: check
given: V = 208 | 480 | 690; a = 0 | 30 | 60
answer: 3*sqrt(2)/pi*V*cos(a*pi/180)
unit: V
tolerance: 0.5%

## A six-pulse bridge runs from {V} V line to line at firing angle {a}°. What's its ideal DC output?

::: right
Right. $1.35V_{LL}\cos\alpha$ = {answer} V.
:::

::: misses
- [sqrt(2)*V*cos(a*pi/180)] That's the peak; the average of the six-pulse waveform is $3\sqrt{2}/\pi$ times $V_{LL}$.
- [any] Not yet. $V_{dc} = \frac{3\sqrt{2}}{\pi}V_{LL}\cos\alpha$.
:::
:::

::: check
given: L = 0.1 | 0.5 | 2; I = 50 | 200 | 1000
answer: 3/pi*2*pi*60*L*1e-3*I
unit: V
tolerance: 0.5%

## A six-pulse bridge with {L} mH of source inductance carries {I} A at 60 Hz. How much output voltage does commutation overlap cost?

::: right
Right. $\frac{3}{\pi}\omega L_sI_d$ = {answer} V.
:::

::: misses
- [2*pi*60*L*1e-3*I] Include the factor 3/π.
- [any] Not yet. $\Delta V = \frac{3}{\pi}\omega L_sI_d$.
:::
:::

::: check
given: V = 120 | 230 | 480
answer: 2*sqrt(2)/pi*V
unit: V
tolerance: 0.5%

## A single-phase diode bridge with a large DC inductor runs from {V} V RMS. What's its DC output?

::: right
Right. $\frac{2\sqrt{2}}{\pi}V_\text{rms}$ = {answer} V.
:::

::: misses
- [sqrt(2)*V] That's the peak, reached only with a capacitor at light load.
- [any] Not yet. The average of a full-wave rectified sine.
:::
:::

::: check
given: I = 50 | 200 | 1000; h = 5 | 7 | 11 | 13
answer: sqrt(6)/pi*I/h
unit: A
tolerance: 0.5%

## A six-pulse bridge carries {I} A DC. What's the RMS of its line current's {h}th harmonic?

::: right
Right. The fundamental is $\frac{\sqrt{6}}{\pi}I_d$ and the hth harmonic is 1/h of it: {answer} A.
:::

::: misses
- [I/h] Start from the fundamental's RMS, $\frac{\sqrt{6}}{\pi}I_d$.
- [any] Not yet. $I_h = I_1/h$.
:::
:::

::: check
given: V = 480 | 4160; a = 120 | 150 | 165
answer: -3*sqrt(2)/pi*V*cos(a*pi/180)
unit: V
tolerance: 0.5%

## A thyristor bridge on {V} V is fired at {a}°. What's the magnitude of the DC voltage it applies while returning power to the line?

::: right
Right. $|1.35V_{LL}\cos\alpha|$ = {answer} V, negative in polarity.
:::

::: misses
- [any] Not yet. Above 90°, cos α is negative.
:::
:::

::: check
given: I = 20 | 100 | 400
answer: sqrt(2/3)*I
unit: A
tolerance: 0.5%

## A six-pulse bridge carries {I} A DC (smooth). What's the RMS line current?

::: right
Right. A 120° block in each half cycle: $\sqrt{2/3}\,I_d$ = {answer} A.
:::

::: misses
- [sqrt(6)/pi*I] That's only the fundamental.
- [any] Not yet. Each line conducts for 2/3 of the time.
:::
:::

::: check
kind: parts
given: I = 50 | 200 | 1000; h = 5 | 7 | 11 | 13

## An ideal six-pulse bridge carries a smooth {I} A.

::: part
answer: sqrt(6)/pi*I
unit: A
tolerance: 0.5%

### What is its line current's fundamental, RMS?

::: misses
- [any] $(\sqrt6/\pi)I_d$.
:::
:::

::: part
answer: sqrt(6)/pi*I/h
unit: A
tolerance: 0.5%

### And its {h}th harmonic?

::: misses
- [any] The fundamental over h.
:::
:::
:::

::: check
kind: derivation
vars: V = 100..1000, a = 0..1.4, L = 0.00001..0.005, I = 1..2000

## A six-pulse thyristor bridge on V (line to line, 60 Hz) fires at angle a (radians) and carries I through source inductance L.

::: step
answer: 3*sqrt(2)/pi*V*cos(a)

### What is its ideal DC output?
:::

::: step
answer: 3*2*pi*60*L*I/pi

### How much does commutation overlap take off?
:::

::: step
answer: 3*sqrt(2)/pi*V*cos(a) - 3*2*pi*60*L*I/pi

### What is the output?
:::

::: right
Right. The overlap drop acts like a resistance $3\omega L_s/\pi$ that dissipates nothing.
:::
:::

::: explain
## Why does source inductance reduce a thyristor bridge's output without dissipating power?

::: model
When the bridge hands the DC current from one phase to the next, the source inductance in each phase prevents the currents from changing instantly, so for a short overlap interval both phases conduct together and the output sits at the average of their two voltages instead of jumping to the new, higher one. That shaves a slice off the output waveform every commutation, six times per cycle, lowering the average by an amount proportional to the current being transferred. The missing volt-seconds go into the inductances' magnetic energy and come back out, not into heat, so the drop behaves like a resistance in the equivalent circuit but consumes no power.
:::
:::

::: practice

::: check
given: V = 400 | 600; a = 15 | 45
answer: 3*sqrt(2)/pi*V*cos(a*pi/180)
unit: V
tolerance: 0.5%

## Six-pulse output: {V} V, α = {a}°?

::: misses
- [any] $1.35V_{LL}\cos\alpha$.
:::
:::

::: check
given: L = 0.2 | 1; I = 100 | 500
answer: 3/pi*2*pi*60*L*1e-3*I
unit: V
tolerance: 0.5%

## Overlap drop: {L} mH, {I} A, 60 Hz?

::: misses
- [any] $\frac{3}{\pi}\omega L_sI_d$.
:::
:::

::: check
given: I = 80 | 300; h = 5 | 11
answer: sqrt(6)/pi*I/h
unit: A
tolerance: 0.5%

## {h}th harmonic RMS at {I} A DC?

::: misses