Problem set 6: power in nonsinusoidal systems, line-commutated rectifiers, PWM rectifiers and power-factor correction, and inverters
These problems cover lessons 29 to 33: RMS, THD, distortion and power factor, diode and thyristor bridges with commutation overlap and harmonics, boost PFC with its emulated resistance, duty cycle, bulk capacitor and hold-up, and sinusoidal PWM in single- and three-phase inverters.
Check
A 230 V sinusoidal source supplies 4 A of fundamental at 0° lag plus 1 A and 2.5 A of harmonics.
(a)
RMS current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Real power?
(c)
Power factor?
Check
A current with THD 70% at 5° displacement; and a rectifier drawing unit pulses of 120° per half cycle centered on the voltage peaks.
(a)
Distortion factor?
(b)
Power factor?
(c)
The pulse rectifier's power factor?
Check
A six-pulse thyristor bridge on 480 V at α = 0°, with 0.5 mH of source inductance carrying 400 A.
(a)
Ideal output?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
Overlap drop?
(c)
Actual output?
Check
A six-pulse bridge carrying 150 A; and a single-phase bridge with a large inductor on 230 V.
(a)
Six-pulse RMS line current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
Its 5th harmonic?
(c)
Single-phase bridge output?
Check
A boost PFC: 300 W from 230 V RMS to a 420 V bus.
(a)
Emulated resistance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
Peak line current?
(c)
Duty cycle at 70° of the line cycle?
Check
A 1000 W PFC with 1000 µF on a 400 V bus, 50 Hz line, needing 10 ms of hold-up down to 280 V.
(a)
Twice-line ripple?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
Hold-up time it provides?
(c)
Capacitance needed for 10 ms?
Check
An inverter on a 400 V bus, sinusoidal PWM at m = 0.5.
(a)
Half-bridge fundamental peak?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
Full-bridge fundamental RMS?
(c)
Three-phase line-to-line RMS?
Check
A three-phase inverter on 700 V must produce 230 V line to line; its dead time is 2 µs at 20 kHz.
(a)
Modulation index needed (sinusoidal PWM)?
(b)
Most it can make with third-harmonic injection?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(c)
Dead-time error?
Check
A thyristor bridge on 480 V fired at 110° carries 1000 A.
(a)
Magnitude of its DC voltage (inverting)?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
Power returned to the line (ignoring overlap)?
Check
An inverter with a 4 kHz carrier making 50 Hz; and the lowest bus a boost PFC can use on 230 V RMS.
(a)
?
(b)
Minimum PFC bus?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A rectifier drawing 10 A RMS from 120 V in pulses of 90° per half cycle, centered on the voltage peaks.
(a)
Power factor?
(b)
Real power?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A three-phase inverter at m = 0.6 on 300 V; a load current with THD 30% from a sinusoidal source.
(a)
Phase (line-to-neutral) RMS voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
How far below 1 is the current's distortion factor?
Check
A six-pulse thyristor bridge on 480 V, 50 Hz, fired at 0°, carries 200 A through 0.3 mH of source inductance per phase.
(a)
What is the overlap angle?
(b)
What DC output?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A six-pulse thyristor bridge on 400 V, fired at 20°, carries 400 A through a large DC inductor; ignore overlap.
(a)
What power factor does the line see?
(b)
How much fundamental reactive power does it draw?
Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.
Check
A single-phase full-bridge inverter on 200 V runs sinusoidal PWM at m = 0.6, 60 Hz, with a 20 kHz carrier, into 10 Ω in series with 10 mH.
(a)
What is the output's fundamental, RMS?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
What fundamental current flows?
(c)
Around what harmonic number does the first cluster of switching harmonics sit?
Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.