S11 · Lesson 5 · Switched-capacitor converters
Fixed-ratio conversion with capacitors and switches, and the two limits on its output resistance
Lessons 1 to 4 built converters around an inductor, which stores energy in a magnetic field. Capacitors store energy far more densely than inductors of the same size, so data centers' 48 V-to-12 V converters and phones' battery chargers increasingly use switched-capacitor converters: networks of capacitors that switches reconnect in series and in parallel, giving a fixed ratio such as 2:1 with very high efficiency. They can't regulate efficiently on their own, but their behavior is captured by one model: an ideal transformer with a fixed ratio, in series with an output resistance whose value depends on whether the switching is slow or fast compared with the capacitors' charging time.
- The output resistance of a 2:1 series-parallel converter with one 10 µF flying capacitor and 10 mΩ switches, against switching frequency. At low frequency the capacitor's charge transfer dominates, ; at high frequency the switches do, .
- The combined estimate falls until the switches take over: switching faster beyond that only adds switching loss.
Predict
A 2:1 switched-capacitor converter makes 24 V from 48 V at 10 A, with an output resistance of 0.054 Ω. What's its efficiency, ignoring gate drive and switching losses?
The output sags to = 23.46 V, and the input supplies half the output current at 48 V, the power of 10 A at 24 V. Efficiency is = 23.46/24 = 97.8%. A switched-capacitor converter behaves like a linear regulator around its ideal ratio: the efficiency is the ratio of the actual to the ideal output voltage.
Name it
The model
An :1 switched-capacitor converter acts as an ideal transformer, with no load, in series with an output resistance . Under load,
So the converter is efficient only near its ideal ratio. Regulation by raising (slowing the clock) works but costs efficiency, like a linear regulator; practical designs either accept a fixed ratio, switch between several ratios, or follow the stage with an inductor-based regulator.
Slow and fast switching limits
- Slow switching limit (SSL): the capacitors fully charge and discharge each phase, current flowing in impulses. Each capacitor carrying a charge multiplier (its charge per cycle, relative to the output charge) contributes : . For a 2:1 series-parallel converter with one flying capacitor, and .
- Fast switching limit (FSL): the capacitors barely change voltage; the current is limited by the switches' resistance: , which is for four switches each with .
A good estimate across the range is . The corner where they're equal is the sensible operating point.
Why capacitors
A ceramic capacitor stores energy at a density hundreds of times that of an inductor's magnetic field at the same volume, and switched-capacitor converters put far less stress on their switches. Hybrid converters add a small inductor to soft-charge the capacitors, removing the SSL's charge-sharing loss and allowing regulation.
Worked example
A 48 V-to-24 V 2:1 converter uses a 10 µF flying capacitor at 500 kHz and switches of 10 mΩ. Find , , the combined output resistance, and the output at 10 A.
Show the solution
- Slow-switching limit.
- Fast-switching limit.
- Combined.
- Output at 10 A. 97.8% efficient.
- Doubling the frequency. That would cut to 25 mΩ and to 32 mΩ, at the cost of doubled switching loss.
Answer = 50 mΩ, = 20 mΩ and = 53.9 mΩ, so the output is 23.46 V at 10 A, 97.8% efficient.
Worked example
What frequency balances the two limits for that converter, and what is the output resistance there?
Show the solution
- Set the two limits equal.
- Solve for f.
- Output resistance there. There = 20 mΩ, so Above this frequency, faster switching hardly helps.
Answer the limits balance at 1.25 MHz, where the output resistance is 28 mΩ.
Worked example
A 3.7 V battery feeds a 2:1 converter whose output must be at least 1.8 V at 1 A. What is the largest output resistance allowed, and the efficiency at that point?
Show the solution
- Largest output resistance. The ideal output is 1.85 V, so
- Efficiency there.
- As the battery falls. At 3.6 V the ideal output is 1.80 V and there's no room left: a fixed-ratio converter can't regulate across a battery's whole range without help.
Answer the output resistance can be at most 50 mΩ, and the efficiency there is 97.3%.
Check
A 2:1 series-parallel converter has a 10 µF flying capacitor switched at 100 kHz. What is its slow-switching-limit output resistance?
Write units the way you normally would: 1.5 mΩ, 1500 µΩ and 0.0015 Ω are the same answer.
Check
A 2:1 switched-capacitor converter runs from 12 V with 0.1 Ω output resistance and supplies 20 A.
(a)
What is the output voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
What is its efficiency, ignoring switching losses?
Check
At what switching frequency do the slow and fast limits of a 2:1 converter (flying capacitor 10 µF, switches 5 mΩ) give equal output resistance?
Write units the way you normally would: 1.5 kHz, 1500 Hz and 0.0015 MHz are the same answer.
Check
A converter's slow-switching limit is 50 mΩ and its fast-switching limit 10 mΩ. What output resistance does the usual estimate give?
Write units the way you normally would: 1.5 mΩ, 1500 µΩ and 0.0015 Ω are the same answer.
Check
A battery at 3.7 V feeds a 2:1 converter that must deliver at least 1.7 V at 2 A. What is the largest output resistance allowed?
Write units the way you normally would: 1.5 mΩ, 1500 µΩ and 0.0015 Ω are the same answer.
Check
Why can't a switched-capacitor converter regulate its output efficiently across a wide input range on its own?
Check
Choose a switching frequency. A 48 V-to-24 V 2:1 converter with flying capacitor C = 4.7 µF and switches of Ron = 5 mΩ delivers P = 500 W. Switching losses are 2 mW per kHz. Write loss(f_khz): conduction loss with and , plus switching loss. Search integer frequencies from 10 to 5000 kHz for the minimum, and set f_best and eff_best (efficiency, as a fraction, ignoring that the output sags).
Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.
Explain why
A server's power design replaces a 48 V-to-12 V buck converter with a 4:1 switched-capacitor stage. Explain why its efficiency and power density can be higher, and what the design gives up.
The switched-capacitor stage moves energy with capacitors, which store far more energy per volume than an inductor's magnetic field, so the converter is smaller; and its switches block only a fraction of the input voltage, so lower-voltage, lower-resistance switches can be used, with smaller switching losses. Operated near its 4:1 ratio, its only significant loss is the voltage dropped across its output resistance, so efficiencies of 98% or more are achievable. What it gives up is regulation: the output is a fixed quarter of the input, minus a load-dependent drop, so the 12 V bus varies with the 48 V input and the load. Data centers accept that because the next stage, the point-of-load regulators, provides the tight regulation; the alternative is a hybrid converter with a small inductor, which recovers some regulation and soft-charges the capacitors.
Practice
Keep practicing
8 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.