S12 · Lesson 47 · Fault detection and condition monitoring

Hearing a motor's broken bars, worn bearings and aging insulation in its current and vibration

An industrial plant's motors fail rarely, but when one does the whole line stops. Lesson 46 set ratings so that machines last; this lesson listens for the signs that one won't. Most motor faults leave fingerprints at predictable frequencies: a cracked rotor bar modulates the stator current at twice the slip frequency, a damaged bearing makes the frame ring at a rate set by its geometry, eccentricity and winding faults add their own lines. Motor current signature analysis reads them from the supply current alone, with a current transformer in the cabinet and an FFT, so a failing motor can be replaced on a planned shutdown instead of in an emergency.

  • The spectrum of an induction motor's stator current around the 50 Hz supply, with a broken rotor bar adding sidebands at (1±2s)f, plotted in dB relative to the fundamental for slip s.
  • The sidebands sit closer to the supply line at light load (small slip), which is why they're measured near full load, and they grow with the number of broken bars.

Predict

A 50 Hz induction motor runs at 3% slip. A broken rotor bar shows up in its stator current at which frequencies?

Name it

Rotor faults

A broken or cracked rotor bar breaks the rotor cage's symmetry. Its asymmetric current produces a field rotating backward relative to the rotor at slip frequency sf, which induces stator current at (1−2s)f; speed ripple then adds (1+2s)f. The sidebands' size relative to the fundamental, often −50 dB for a healthy rotor and above −40 dB for a broken bar, indicates the severity.

Bearing faults

A defect on a rolling-element bearing is struck at a rate set by the geometry: with n balls of diameter d on a pitch diameter D, contact angle φ, and shaft frequency fr:

BPFO=n2fr(1−dDcos⁡φ),BPFI=n2fr(1+dDcos⁡φ)

for outer- and inner-race defects. They're strongest in vibration, measured with an accelerometer and often demodulated (envelope analysis), and weakly visible in current.

Eccentricity and stator faults

An off-center rotor (static or dynamic eccentricity) adds current lines at f±kfr. Shorted turns raise a phase's current asymmetry and negative-sequence current (lesson 26) and heat locally.

Insulation and thermal aging

Insulation life roughly halves for every 10 °C above its rated temperature (lesson 46's Arrhenius rule). Monitoring winding temperature, partial discharge in high-voltage machines, and insulation resistance to ground (the polarization index, the ratio of 10-minute to 1-minute readings) tracks aging before it becomes a fault.

Resolution

Sidebands a few tenths of a hertz from 50 Hz must be resolved by the FFT: a frequency resolution of 1/T needs records of several seconds to tens of seconds, at steady load.

Worked example

A 4-pole, 50 Hz motor runs at 1455 rpm. Where are its broken-bar sidebands, and how long a record resolves them clearly?

Show the solution
  1. Slip. Synchronous speed is 1500 rpm, so s=451500=0.03
  2. Sidebands. They're at 50(1±0.06): 47 and 53 Hz.
  3. Record length. They're 3 Hz from the fundamental, so even a 2 s record (0.5 Hz resolution) separates them.
  4. At light load. With s = 0.005 they'd be 0.5 Hz away and need 10 s or more, with a window that keeps the fundamental's leakage low.

Answer the sidebands are at 47 and 53 Hz, and a 2 s record resolves them.

Worked example

A bearing has 9 balls with d/D = 0.2 and zero contact angle, on a shaft turning at 1470 rpm. Find its outer- and inner-race defect frequencies.

Show the solution
  1. Shaft frequency. fr = 24.5 Hz.
  2. Outer-race frequency. BPFO=4.5×24.5×0.8=88.2Hz
  3. Inner-race frequency. BPFI=4.5×24.5×1.2=132.3Hz
  4. Check. BPFO + BPFI = nfr = 220.5 Hz: a quick check on a measured pair.
  5. In practice. In envelope spectra of vibration, a peak at 88.2 Hz with harmonics points to the outer race.

Answer BPFO = 88.2 Hz and BPFI = 132.3 Hz.

Worked example

A winding rated for 155 °C runs at 165 °C because of a blocked cooling fan. If it was designed for 20 years at rated temperature, how long will it last?

Show the solution
  1. Ten degrees over. 10 °C over halves the life: 10 years.
  2. Twenty degrees over. At 175 °C it would be 5 years.
  3. What to monitor. Temperature monitoring that catches a blocked fan is worth more than any spectrum analysis for this failure mode.

Answer about 10 years, half its design life.

Check

A 50 Hz induction motor runs at slip 0.01. At what frequency is the lower broken-bar sideband?

Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.

Check

A 3-pole-pair motor on 50 Hz runs 45 rpm below its synchronous speed. What is its slip?

Check

A bearing has 9 balls with d/D = 0.15 and zero contact angle; the shaft turns at 2950 rpm.

(a)

What is its outer-race defect frequency?

Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.

(b)

And its inner-race defect frequency?

Check

To separate broken-bar sidebands from a 50 Hz fundamental at slip 0.01, an FFT's resolution must be a 5th of the sideband offset. How long must the record be?

Write units the way you normally would: 1.5 s and 1500 ms are the same answer.

Check

A winding designed for 20 years at its rated temperature runs 5 °C hotter. How long does it last, by the 10-degree rule?

Check

Why are broken-bar sidebands measured near full load rather than at no load?

Check

Detect a broken bar. Simulate a stator current cos⁡(2π⋅50t)+A[cos⁡(2πf1t)+cos⁡(2πf2t)] with sideband amplitude A=10a/20 (−40 dB), f1,2=50(1∓2s), slip s = 0.02, sampled at 1 kHz for T = 10 s, plus noise of RMS 0.001 (numpy.random.default_rng(3)). Apply a Hann window, take the FFT, and set f_lo (the frequency of the largest bin between 40 and 49.5 Hz) and level_db, that bin's magnitude relative to the 50 Hz bin, in dB.