title: Fault detection and condition monitoring
heading: Hearing a motor's broken bars, worn bearings and aging insulation in its current and vibration
eyebrow: S12 · Lesson 47 · Fault detection and condition monitoring
xp: 50
---

::: hook
An industrial plant's motors fail rarely, but when one does the whole line stops. Lesson 46 set ratings so that machines last; this lesson listens for the signs that one won't. Most motor faults leave fingerprints at predictable frequencies: a cracked rotor bar modulates the stator current at twice the slip frequency, a damaged bearing makes the frame ring at a rate set by its geometry, eccentricity and winding faults add their own lines. **Motor current signature analysis** reads them from the supply current alone, with a current transformer in the cabinet and an FFT, so a failing motor can be replaced on a planned shutdown instead of in an emergency.
:::

::: play
- The spectrum of an induction motor's stator current around the 50 Hz supply, with a broken rotor bar adding sidebands at $(1 \pm 2s)f$, plotted in dB relative to the fundamental for slip $s$.
- The sidebands sit closer to the supply line at light load (small slip), which is why they're measured near full load, and they grow with the number of broken bars.
:::

```sim plot
view: graph
x: f = 40..60
y: A = -80..0
slider: s = 0.005..0.06 step 0.001 = 0.03
slider: b = -60..-20 step 1 = -45
plot: 20*log(exp(-((f - 50)/0.15)^2) + 10^(b/20)*exp(-((f - 50*(1 - 2*s))/0.15)^2) + 10^(b/20)*exp(-((f - 50*(1 + 2*s))/0.15)^2) + 1e-4) | samples: 3000 | label: stator current spectrum, dB
readout: lower sideband, Hz = 50*(1 - 2*s)
readout: upper sideband, Hz = 50*(1 + 2*s)
```

::: predict
## A 50 Hz induction motor runs at 3% slip. A broken rotor bar shows up in its stator current at which frequencies?

- [ ] 48.5 and 51.5 Hz
- [x] 47 and 53 Hz
- [ ] 50 and 100 Hz
- [ ] 25 and 75 Hz

::: reveal
$(1 \pm 2s)f = (1 \pm 0.06) \times 50$: 47 and 53 Hz. The broken bar makes the rotor's field lopsided, rotating backward relative to the rotor at slip frequency, which modulates the stator current at twice the slip frequency, 3 Hz either side of the supply.
:::
:::

::: nameit
## Rotor faults

A broken or cracked rotor bar breaks the rotor cage's symmetry. Its asymmetric current produces a field rotating backward relative to the rotor at slip frequency $sf$, which induces stator current at $(1 - 2s)f$; speed ripple then adds $(1 + 2s)f$. The sidebands' size relative to the fundamental, often −50 dB for a healthy rotor and above −40 dB for a broken bar, indicates the severity.

## Bearing faults

A defect on a rolling-element bearing is struck at a rate set by the geometry: with $n$ balls of diameter $d$ on a pitch diameter $D$, contact angle φ, and shaft frequency $f_r$:

$$\text{BPFO} = \frac{n}{2}f_r\left(1 - \frac dD\cos\varphi\right), \qquad \text{BPFI} = \frac{n}{2}f_r\left(1 + \frac dD\cos\varphi\right)$$

for outer- and inner-race defects. They're strongest in vibration, measured with an accelerometer and often demodulated (envelope analysis), and weakly visible in current.

## Eccentricity and stator faults

An off-center rotor (static or dynamic eccentricity) adds current lines at $f \pm kf_r$. Shorted turns raise a phase's current asymmetry and negative-sequence current (lesson 26) and heat locally.

## Insulation and thermal aging

Insulation life roughly halves for every 10 °C above its rated temperature (lesson 46's Arrhenius rule). Monitoring winding temperature, partial discharge in high-voltage machines, and insulation resistance to ground (the polarization index, the ratio of 10-minute to 1-minute readings) tracks aging before it becomes a fault.

## Resolution

Sidebands a few tenths of a hertz from 50 Hz must be resolved by the FFT: a frequency resolution of $1/T$ needs records of several seconds to tens of seconds, at steady load.
:::

::: example
## A 4-pole, 50 Hz motor runs at 1455 rpm. Where are its broken-bar sidebands, and how long a record resolves them clearly?

::: solution
1. **Slip.** Synchronous speed is 1500 rpm, so
   $$\begin{aligned} s &= \frac{45}{1500} \\ &= 0.03 \end{aligned}$$
2. **Sidebands.** They're at $50(1 \pm 0.06)$: 47 and 53 Hz.
3. **Record length.** They're 3 Hz from the fundamental, so even a 2 s record (0.5 Hz resolution) separates them.
4. **At light load.** With $s$ = 0.005 they'd be 0.5 Hz away and need 10 s or more, with a window that keeps the fundamental's leakage low.

**Answer:** the sidebands are at 47 and 53 Hz, and a 2 s record resolves them.
:::
:::

::: example
## A bearing has 9 balls with $d/D$ = 0.2 and zero contact angle, on a shaft turning at 1470 rpm. Find its outer- and inner-race defect frequencies.

::: solution
1. **Shaft frequency.** $f_r$ = 24.5 Hz.
2. **Outer-race frequency.**
   $$\begin{aligned} \text{BPFO} &= 4.5 \times 24.5 \times 0.8 \\ &= 88.2\ \text{Hz} \end{aligned}$$
3. **Inner-race frequency.**
   $$\begin{aligned} \text{BPFI} &= 4.5 \times 24.5 \times 1.2 \\ &= 132.3\ \text{Hz} \end{aligned}$$
4. **Check.** BPFO + BPFI = $nf_r$ = 220.5 Hz: a quick check on a measured pair.
5. **In practice.** In envelope spectra of vibration, a peak at 88.2 Hz with harmonics points to the outer race.

**Answer:** BPFO = 88.2 Hz and BPFI = 132.3 Hz.
:::
:::

::: example
## A winding rated for 155 °C runs at 165 °C because of a blocked cooling fan. If it was designed for 20 years at rated temperature, how long will it last?

::: solution
1. **Ten degrees over.** 10 °C over halves the life: 10 years.
2. **Twenty degrees over.** At 175 °C it would be 5 years.
3. **What to monitor.** Temperature monitoring that catches a blocked fan is worth more than any spectrum analysis for this failure mode.

**Answer:** about 10 years, half its design life.
:::
:::

::: check
given: f = 50 | 60; s = 0.01 | 0.02 | 0.04
answer: f*(1 - 2*s)
unit: Hz
tolerance: 0.5%

## A {f} Hz induction motor runs at slip {s}. At what frequency is the lower broken-bar sideband?

::: right
Right. $(1 - 2s)f$ = {answer}.
:::

::: misses
- [f*(1 - s)] The sidebands are at twice the slip frequency from the supply.
- [f*2*s] That's the offset, not the frequency.
- [any] Not yet. $(1 - 2s)f$.
:::
:::

::: check
given: p = 2 | 3 | 4; f = 50 | 60; d = 15 | 30 | 45
answer: d/(60*f/p)
tolerance: 0.5%

## A {p}-pole-pair motor on {f} Hz runs {d} rpm below its synchronous speed. What is its slip?

::: right
Right. $n_s = 60f/p$, and $s = (n_s - n)/n_s$ = {answer}.
:::

::: misses
- [d/(60*f)] Divide the supply frequency by the pole pairs for synchronous speed.
- [d/(120*f/p)] Synchronous speed is $60f/p$ in rpm, with $p$ pole pairs.
- [any] Not yet. $s = \Delta n/n_s$.
:::
:::

::: check
kind: parts
given: N = 7 | 9 | 12; r = 0.15 | 0.2 | 0.25; rpm = 1470 | 1750 | 2950

## A bearing has {N} balls with $d/D$ = {r} and zero contact angle; the shaft turns at {rpm} rpm.

::: part
answer: N/2*rpm/60*(1 - r)
unit: Hz
tolerance: 0.5%

### What is its outer-race defect frequency?

::: misses
- [N/2*rpm/60*(1 + r)] That's the inner race.
- [N*rpm/60*(1 - r)] Include the factor $n/2$.
- [any] Not yet. $\frac n2f_r(1 - d/D)$.
:::
:::

::: part
answer: N/2*rpm/60*(1 + r)
unit: Hz
tolerance: 0.5%

### And its inner-race defect frequency?

::: misses
- [N/2*rpm/60*(1 - r)] That's the outer race.
- [any] Not yet. $\frac n2f_r(1 + d/D)$.
:::
:::

::: right
Right. Their sum is $nf_r$, a handy check on measurements.
:::
:::

::: check
given: s = 0.005 | 0.01 | 0.03; f = 50 | 60; k = 3 | 5
answer: k/(2*s*f)
unit: s
tolerance: 0.5%

## To separate broken-bar sidebands from a {f} Hz fundamental at slip {s}, an FFT's resolution must be a {k}th of the sideband offset. How long must the record be?

::: right
Right. Offset $2sf$; resolution $1/T = 2sf/k$, so $T$ = {answer}.
:::

::: misses
- [1/(2*s*f)] That resolves the offset only just; divide the offset by {k}.
- [k/(s*f)] The offset from the supply is $2sf$.
- [any] Not yet. $T = k/(2sf)$.
:::
:::

::: check
given: L = 10 | 20 | 30; dT = 5 | 15 | 20
answer: L/2^(dT/10)
unit: yr
tolerance: 0.5%

## A winding designed for {L} years at its rated temperature runs {dT} °C hotter. How long does it last, by the 10-degree rule?

::: right
Right. $L/2^{\Delta T/10}$ = {answer}.
:::

::: misses
- [L*(1 - dT/100)] Life falls exponentially with temperature: half per 10 °C.
- [L/2] Halve once per 10 °C: $2^{\Delta T/10}$.
- [any] Not yet. $L \cdot 2^{-\Delta T/10}$.
:::
:::

::: check
kind: choice

## Why are broken-bar sidebands measured near full load rather than at no load?

- [x] The sidebands are at $\pm 2sf$ from the supply, and at no load the slip is so small that they sit almost on the fundamental and are tiny
- [ ] The rotor bars only carry current at full load
- [ ] The current transformer saturates at no load
- [ ] No-load current has no 50 Hz component

::: right
Right. Larger slip means more rotor current (stronger fault signature) and sidebands farther from the fundamental, where the FFT can see them.
:::

::: misses
- [2] Bars carry current at any load, just less at light load.
- [3] Saturation isn't the issue at light current.
- [4] The supply-frequency magnetizing current flows at any load.
:::
:::

::: check
kind: python
given: s = 0.02 | 0.04; a = -40 | -50; T = 4 | 10

## Detect a broken bar. Simulate a stator current $\cos(2\pi \cdot 50t) + A[\cos(2\pi f_1t) + \cos(2\pi f_2t)]$ with sideband amplitude $A = 10^{a/20}$ ({a} dB), $f_{1,2} = 50(1 \mp 2s)$, slip `s` = {s}, sampled at 1 kHz for `T` = {T} s, plus noise of RMS 0.001 (`numpy.random.default_rng(3)`). Apply a Hann window, take the FFT, and set `f_lo` (the frequency of the largest bin between 40 and 49.5 Hz) and `level_db`, that bin's magnitude relative to the 50 Hz bin, in dB.

```python starter
import numpy as np
f_lo = 50.0
level_db = 0.0
```

```python solution
import numpy as np
fs = 1000
t = np.arange(int(fs * T)) / fs
A = 10 ** (a / 20)
x = np.cos(2 * np.pi * 50 * t) + A * (np.cos(2 * np.pi * 50 * (1 - 2 * s) * t) + np.cos(2 * np.pi * 50 * (1 + 2 * s) * t))
x = x + 0.001 * np.random.default_rng(3).standard_normal(len(t))
X = np.abs(np.fft.rfft(x * np.hanning(len(t))))
f = np.fft.rfftfreq(len(t), 1 / fs)
band = (f >= 40) & (f <= 49.5)
i = np.argmax(np.where(band, X, 0))
f_lo = float(f[i])
level_db = float(20 * np.log10(X[i] / X[np.argmin(np.abs(f - 50))]))
```

```python tests
import numpy as np
assert abs(f_lo - 50 * (1 - 2 * s)) <= 1 / T, f"The lower sideband should be found at {50 * (1 - 2 * s):.2f} Hz."
assert abs(level_db - a) < 1.5, "Its level should be close to the simulated sideband level."
```

::: right
Right. A windowed FFT over a few seconds finds a −50 dB sideband 2 to 4 Hz from a strong fundamental: the whole of motor current signature analysis in a dozen lines.
:::
:::

::: explain
## A plant's maintenance team wants to know whether to trust current signature analysis on a motor driven by a variable-frequency drive instead of directly from the grid. Explain what changes, and what they should do.

::: model
On the grid, the supply frequency is fixed and clean, so broken-bar sidebands appear at predictable $(1 \pm 2s)f$ around a sharp 50 or 60 Hz line, easy to separate in a few seconds of data. With a drive, the fundamental frequency varies with the speed command, the current contains PWM switching harmonics and drive-induced sidebands, and the drive's current controller may actively suppress the very current asymmetries the method looks for. The team should measure at steady speed and load, track the actual fundamental frequency and slip from the drive's data, use longer records and careful windowing, compare against a baseline taken when the motor was healthy, and supplement current analysis with vibration measurement for bearings, whose signatures don't depend on the supply.
:::
:::

::: practice

::: check
given: f = 50 | 60; s = 0.015 | 0.05
answer: f*(1 + 2*s)
unit: Hz
tolerance: 0.5%

## Where is the upper broken-bar sideband for a {f} Hz motor at slip {s}?

::: misses
- [f*(1 + s)] It's $2s$ from the supply.
- [any] $(1 + 2s)f$.
:::
:::

::: check
given: N = 8 | 16; rpm = 900 | 3600; r = 0.18 | 0.3
answer: N/2*rpm/60*(1 - r)
unit: Hz
tolerance: 0.5%

## What is the outer-race defect frequency for {N} balls, $d/D$ = {r}, at {rpm} rpm?

::: misses
- [N/2*rpm/60*(1 + r)] That's the inner race.
- [any] $\frac n2f_r(1 - d/D)$.
:::
:::
:::