S12 · Lesson 28 · Doubly fed induction generators

A wound-rotor induction machine whose rotor is fed by a back-to-back converter at slip frequency, how power divides between stator and rotor, why the converter needs only the slip's share of the rating, rotor voltage and turns ratio, and control of reactive power

A wind turbine's rotor should turn faster in strong wind and slower in light wind to catch the most energy, but the grid wants a fixed 50 or 60 Hz. One answer is to pass all the power through a converter; the other, used in most of the large turbines built in the 2000s and 2010s, is the doubly fed induction generator. Its stator connects straight to the grid, and a converter feeds its rotor at whatever slip frequency the speed requires. The converter handles only the slip's share of the power, about a third of the rating, which made multi-megawatt variable-speed turbines affordable.

  • The curves are how a doubly fed generator delivering a fixed 2 MW to the grid splits it between stator and rotor converter, against slip (negative above synchronous speed), with no losses: Ps=P/(1−s) through the stator and Pr=−sPs through the rotor converter.
  • Above synchronous speed (s < 0) both paths send power to the grid; below it, the rotor draws power back from the grid.
  • The converter's share is the slip, so a ±30% speed range needs a converter rated near 30% of the stator power.

Predict

A 4-pole, 50 Hz doubly fed generator turns at 1800 rpm and sends 2 MW to the grid, losses aside. How much of that passes through its rotor converter?

Name it

The machine

A wound-rotor induction machine with its stator on the grid at frequency f and its rotor windings fed through slip rings by a back-to-back converter (a rotor-side and a grid-side inverter sharing a DC link). The rotor-side converter applies voltage at slip frequency sf, so the rotor's field turns at synchronous speed in space whatever the shaft speed n=ns(1−s).

Power flow

Neglecting losses, the stator power Ps, rotor power Pr and mechanical power Pm satisfy

Pr=−sPs,Pm=(1−s)Ps

(generator convention: positive means delivered to the grid). The grid receives Ps+Pr=(1−s)Ps=Pm. Above synchronous speed, s is negative and the rotor converter also delivers power; below, it absorbs sPs from the grid and passes it to the rotor.

Converter rating

The converter carries at most |smax⁡|Ps: for a speed range of ±30% around synchronous speed, about 30% of the stator rating. A full-converter generator must instead pass the whole power through its converter.

Rotor voltage

The rotor's induced voltage scales with slip: with rotor-to-stator turns ratio Nr/Ns, its open-circuit value is |s|(Nr/Ns)Vs at frequency |s|f. The turns ratio is chosen so that this voltage at the largest slip suits the converter. Near standstill the rotor voltage would be far higher, which is why a DFIG can't be started from rest through its converter.

Control and grid faults

Controlling the rotor current's d and q parts sets the stator's real and reactive power independently, much as in field-oriented control (lesson 41). During a grid fault the stator flux's transient induces large rotor voltages, and a crowbar or chopper protects the converter; modern grid codes require the turbine to ride through and supply reactive current.

Worked example

A 4-pole, 50 Hz doubly fed generator delivers 2 MW to the grid at 1800 rpm. Find the stator and rotor powers, and the rotor frequency.

Show the solution
  1. Slip. At 1800 rpm, s = −0.2.
  2. Stator and rotor powers. Ps=21.2=1.667MWPr=0.2×1.667=0.333MW both delivered.
  3. Rotor frequency. The rotor currents alternate at |s|f = 10 Hz.
  4. Phase sequence. Since s is negative, the rotor-side converter makes their phase sequence opposite to the stator's, so that their field, turning backward relative to the rotor at 300 rpm, still turns forward at 1500 rpm in space.

Answer the stator delivers 1.667 MW and the rotor 0.333 MW, and the rotor currents alternate at 10 Hz.

Worked example

The same machine runs at 1050 rpm (s = 0.3) delivering 1.2 MW. Where does the rotor power go, and what voltage does the rotor need if its turns ratio is 2.5 with a 690 V stator?

Show the solution
  1. Stator power. Ps=1.20.7=1.714MW
  2. Rotor power. Pr=−0.3×1.714=−0.514MW The grid-side converter draws 0.514 MW from the grid and passes it to the rotor, and the stator sends the sum of that and the shaft's 1.2 MW back out.
  3. Rotor voltage. The rotor's open-circuit voltage is Vr=0.3×2.5×690=518V line to line at 15 Hz, which a converter on a 1 kV-class DC link can supply.
  4. At standstill. It would be 1725 V.

Answer the grid-side converter draws 0.514 MW from the grid and feeds it to the rotor, and the stator sends 1.714 MW back out. The rotor needs 518 V line to line at 15 Hz.

Worked example

A turbine maker compares a 3 MW doubly fed generator with a ±30% speed range against a full-converter generator. How do the converter ratings compare?

Show the solution
  1. Top of the speed range. Here s = −0.3 and the grid receives 3 MW: Ps=31.3=2.31MW and the converter carries 0.69 MW, 23% of the output.
  2. Bottom of the range. Here s = +0.3 and the converter carries 30% of the stator power, but at that low speed the wind's power and the stator's are smaller.
  3. Converter rating. So the converter is rated around a quarter to a third of the turbine, against 100% for a full converter.
  4. The price. The price is slip rings and their maintenance, and the harder fault ride-through.

Answer the doubly fed generator's converter is rated around a quarter to a third of the turbine's 3 MW, against 100% for the full converter.

Check

A 50 Hz doubly fed generator turns at 0.8 times synchronous speed and sends 2 MW to the grid; neglect losses.

(a)

What does the stator deliver?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

What does the rotor converter deliver to the grid (negative if it draws power)?

(c)

At what frequency do the rotor currents alternate?

Check

A doubly fed generator's stator is on 400 V; its rotor-to-stator turns ratio is 2, and it runs at slip ±0.3.

(a)

What open-circuit voltage does its rotor develop?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

(b)

What would it be at standstill?

Check

A doubly fed turbine rated 2 MW at the grid has a speed range of ±0.2 around synchronous speed.

(a)

What does the stator carry at top speed and full output?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

What does the converter carry then?

Check

A 4-pole, 50 Hz doubly fed generator has a converter rated for slips up to ±0.3.

(a)

What is its lowest speed?

(b)

And its highest?

Check

Why does a doubly fed generator need only a partly rated converter, while a full-converter wind generator needs one rated for the whole output?

Check

A doubly fed generator sends P to the grid at slip s, with stator voltage V, rotor-to-stator turns ratio k and grid frequency f.

Step 1

What does the stator carry?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Check

Write dfig_split(P, s) returning (stator power, rotor converter power) for grid power P at slip s, lossless, and converter_rating(P, smin, smax): the largest converter power over the slip range when the grid power at slip s is P(1−s)3/(1−smin⁡)3, the cube-law wind curve reaching P at the top speed (most negative slip, smin).

Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.

Explain why

How can a doubly fed generator deliver fixed-frequency power while its shaft speed varies?

Practice

Keep practicing

7 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.