title: Doubly fed induction generators
heading: A wound-rotor induction machine whose rotor is fed by a back-to-back converter at slip frequency, how power divides between stator and rotor, why the converter needs only the slip's share of the rating, rotor voltage and turns ratio, and control of reactive power
eyebrow: S12 · Lesson 28 · Doubly fed induction generators
xp: 50
---

::: hook
A wind turbine's rotor should turn faster in strong wind and slower in light wind to catch the most energy, but the grid wants a fixed 50 or 60 Hz. One answer is to pass all the power through a converter; the other, used in most of the large turbines built in the 2000s and 2010s, is the doubly fed induction generator. Its stator connects straight to the grid, and a converter feeds its rotor at whatever slip frequency the speed requires. The converter handles only the slip's share of the power, about a third of the rating, which made multi-megawatt variable-speed turbines affordable.
:::

::: play
- The curves are how a doubly fed generator delivering a fixed 2 MW to the grid splits it between stator and rotor converter, against slip (negative above synchronous speed), with no losses: $P_s = P/(1 - s)$ through the stator and $P_r = -sP_s$ through the rotor converter.
- Above synchronous speed (s < 0) both paths send power to the grid; below it, the rotor draws power back from the grid.
- The converter's share is the slip, so a ±30% speed range needs a converter rated near 30% of the stator power.
:::

```sim plot
view: graph
x: s = -0.35..0.35
y: P = -1..2.5
plot: 2/(1 - s) | label: stator power, MW
plot: -s*2/(1 - s) | label: rotor converter power, MW
```

::: predict
## A 4-pole, 50 Hz doubly fed generator turns at 1800 rpm and sends 2 MW to the grid, losses aside. How much of that passes through its rotor converter?

- [ ] None
- [x] About 0.33 MW
- [ ] 2 MW
- [ ] About 0.4 MW, drawn from the grid

::: reveal
Synchronous speed is 1500 rpm, so s = (1500 − 1800)/1500 = −0.2. The stator delivers $P/(1 - s)$ = 1.667 MW and the rotor converter $-sP_s$ = 0.333 MW, both to the grid. Below synchronous speed the converter would instead feed slip power into the rotor.
:::
:::

::: nameit
## The machine

A wound-rotor induction machine with its stator on the grid at frequency f and its rotor windings fed through slip rings by a back-to-back converter (a rotor-side and a grid-side inverter sharing a DC link). The rotor-side converter applies voltage at slip frequency sf, so the rotor's field turns at synchronous speed in space whatever the shaft speed $n = n_s(1 - s)$.

## Power flow

Neglecting losses, the stator power $P_s$, rotor power $P_r$ and mechanical power $P_m$ satisfy
$$P_r = -sP_s, \qquad P_m = (1 - s)P_s$$
(generator convention: positive means delivered to the grid). The grid receives $P_s + P_r = (1 - s)P_s = P_m$. Above synchronous speed, s is negative and the rotor converter also delivers power; below, it absorbs $sP_s$ from the grid and passes it to the rotor.

## Converter rating

The converter carries at most $|s_\max|P_s$: for a speed range of ±30% around synchronous speed, about 30% of the stator rating. A full-converter generator must instead pass the whole power through its converter.

## Rotor voltage

The rotor's induced voltage scales with slip: with rotor-to-stator turns ratio $N_r/N_s$, its open-circuit value is $|s|(N_r/N_s)V_s$ at frequency $|s|f$. The turns ratio is chosen so that this voltage at the largest slip suits the converter. Near standstill the rotor voltage would be far higher, which is why a DFIG can't be started from rest through its converter.

## Control and grid faults

Controlling the rotor current's d and q parts sets the stator's real and reactive power independently, much as in field-oriented control (lesson 41). During a grid fault the stator flux's transient induces large rotor voltages, and a **crowbar** or chopper protects the converter; modern grid codes require the turbine to ride through and supply reactive current.
:::

::: example
## A 4-pole, 50 Hz doubly fed generator delivers 2 MW to the grid at 1800 rpm. Find the stator and rotor powers, and the rotor frequency.

::: solution
1. **Slip.** At 1800 rpm, s = −0.2.
2. **Stator and rotor powers.**
   $$\begin{aligned} P_s &= \frac{2}{1.2} \\ &= 1.667\ \text{MW} \\ P_r &= 0.2 \times 1.667 \\ &= 0.333\ \text{MW} \end{aligned}$$
   both delivered.
3. **Rotor frequency.** The rotor currents alternate at $|s|f$ = 10 Hz.
4. **Phase sequence.** Since s is negative, the rotor-side converter makes their phase sequence opposite to the stator's, so that their field, turning backward relative to the rotor at 300 rpm, still turns forward at 1500 rpm in space.

**Answer:** the stator delivers 1.667 MW and the rotor 0.333 MW, and the rotor currents alternate at 10 Hz.
:::
:::

::: example
## The same machine runs at 1050 rpm (s = 0.3) delivering 1.2 MW. Where does the rotor power go, and what voltage does the rotor need if its turns ratio is 2.5 with a 690 V stator?

::: solution
1. **Stator power.**
   $$\begin{aligned} P_s &= \frac{1.2}{0.7} \\ &= 1.714\ \text{MW} \end{aligned}$$
2. **Rotor power.**
   $$\begin{aligned} P_r &= -0.3 \times 1.714 \\ &= -0.514\ \text{MW} \end{aligned}$$
   The grid-side converter draws 0.514 MW from the grid and passes it to the rotor, and the stator sends the sum of that and the shaft's 1.2 MW back out.
3. **Rotor voltage.** The rotor's open-circuit voltage is
   $$\begin{aligned} V_r &= 0.3 \times 2.5 \times 690 \\ &= 518\ \text{V} \end{aligned}$$
   line to line at 15 Hz, which a converter on a 1 kV-class DC link can supply.
4. **At standstill.** It would be 1725 V.

**Answer:** the grid-side converter draws 0.514 MW from the grid and feeds it to the rotor, and the stator sends 1.714 MW back out. The rotor needs 518 V line to line at 15 Hz.
:::
:::

::: example
## A turbine maker compares a 3 MW doubly fed generator with a ±30% speed range against a full-converter generator. How do the converter ratings compare?

::: solution
1. **Top of the speed range.** Here s = −0.3 and the grid receives 3 MW:
   $$\begin{aligned} P_s &= \frac{3}{1.3} \\ &= 2.31\ \text{MW} \end{aligned}$$
   and the converter carries 0.69 MW, 23% of the output.
2. **Bottom of the range.** Here s = +0.3 and the converter carries 30% of the stator power, but at that low speed the wind's power and the stator's are smaller.
3. **Converter rating.** So the converter is rated around a quarter to a third of the turbine, against 100% for a full converter.
4. **The price.** The price is slip rings and their maintenance, and the harder fault ride-through.

**Answer:** the doubly fed generator's converter is rated around a quarter to a third of the turbine's 3 MW, against 100% for the full converter.
:::
:::

::: check
kind: parts
given: P = 1.5 | 2 | 3; f = 50 | 60; n = 1.15 | 1.25 | 0.8

## A {f} Hz doubly fed generator turns at {n} times synchronous speed and sends {P} MW to the grid; neglect losses.

::: part
answer: P/(2 - n)
unit: MW
tolerance: 0.5%

### What does the stator deliver?

::: misses
- [P] Part of the output passes through the rotor.
- [any] $P/(1 - s)$ with $s = 1 - n/n_s$.
:::
:::

::: part
answer: -(1 - n)*P/(2 - n)
unit: MW
tolerance: 0.5%

### What does the rotor converter deliver to the grid (negative if it draws power)?

::: misses
- [any] $-sP_s$.
:::
:::

::: part
answer: abs(1 - n)*f
unit: Hz
tolerance: 0.5%

### At what frequency do the rotor currents alternate?

::: misses
- [any] $|s|f$.
:::
:::
:::

::: check
kind: parts
given: V = 400 | 690; k = 2 | 2.5 | 3; s = 0.2 | 0.3

## A doubly fed generator's stator is on {V} V; its rotor-to-stator turns ratio is {k}, and it runs at slip ±{s}.

::: part
answer: s*k*V
unit: V
tolerance: 0.5%

### What open-circuit voltage does its rotor develop?

::: misses
- [k*V] That's at standstill; the rotor voltage scales with slip.
- [any] $|s|(N_r/N_s)V_s$.
:::
:::

::: part
answer: k*V
unit: V
tolerance: 0.5%

### What would it be at standstill?

::: misses
- [any] Slip 1.
:::
:::
:::

::: check
kind: parts
given: P = 2 | 5; r = 0.2 | 0.3 | 0.35

## A doubly fed turbine rated {P} MW at the grid has a speed range of ±{r} around synchronous speed.

::: part
answer: P/(1 + r)
unit: MW
tolerance: 0.5%

### What does the stator carry at top speed and full output?

::: misses
- [P/(1 - r)] Top speed is above synchronous: s = −r.
- [any] $P/(1 - s)$ with s = −r.
:::
:::

::: part
answer: r*P/(1 + r)
unit: MW
tolerance: 0.5%

### What does the converter carry then?

::: misses
- [any] $|s|P_s$.
:::
:::
:::

::: check
kind: parts
given: p = 4 | 6; f = 50 | 60; r = 0.25 | 0.3

## A {p}-pole, {f} Hz doubly fed generator has a converter rated for slips up to ±{r}.

::: part
answer: 120*f/p*(1 - r)
unit: rpm
tolerance: 0.5%

### What is its lowest speed?

::: misses
- [any] $n_s(1 - s_\max)$.
:::
:::

::: part
answer: 120*f/p*(1 + r)
unit: rpm
tolerance: 0.5%

### And its highest?

::: misses
- [any] $n_s(1 + s_\max)$.
:::
:::
:::

::: check
kind: choice

## Why does a doubly fed generator need only a partly rated converter, while a full-converter wind generator needs one rated for the whole output?

- [ ] The doubly fed machine is more efficient
- [x] Its stator connects directly to the grid and carries most of the power; the rotor converter handles only the slip power, a fraction |s| of the stator's, which stays small over a ±30% speed range
- [ ] Its rotor has no current
- [ ] It runs only at synchronous speed

::: misses
- [1] Efficiency isn't the reason.
- [3] The rotor carries slip-frequency current.
- [4] It runs over a speed range around synchronous.
:::
:::

::: check
kind: derivation
vars: P = 0.1..10, s = -0.4..0.4, V = 100..1000, k = 1..4, f = 50..60

## A doubly fed generator sends P to the grid at slip s, with stator voltage V, rotor-to-stator turns ratio k and grid frequency f.

::: step
answer: P/(1 - s)

### What does the stator carry?
:::

::: step
answer: -s*P/(1 - s)

### What does the rotor converter deliver?
:::

::: step
answer: abs(s)*k*V

### What open-circuit voltage does the rotor develop?
:::

::: right
Right. Slip sets both the converter's power and its voltage, which is why the speed range sets its size.
:::
:::

::: check
kind: python

## Write `dfig_split(P, s)` returning (stator power, rotor converter power) for grid power P at slip s, lossless, and `converter_rating(P, smin, smax)`: the largest converter power over the slip range when the grid power at slip s is $P(1 - s)^3/(1 - s_\min)^3$, the cube-law wind curve reaching P at the top speed (most negative slip, smin).

```python starter
def dfig_split(P, s):
    return P, 0.0

def converter_rating(P, smin, smax):
    return 0.0
```

```python solution
def dfig_split(P, s):
    Ps = P / (1 - s)
    return Ps, -s * Ps

def converter_rating(P, smin, smax):
    best = 0.0
    n = 2000
    for k in range(n + 1):
        s = smin + (smax - smin) * k / n
        Pg = P * (1 - s) ** 3 / (1 - smin) ** 3
        best = max(best, abs(dfig_split(Pg, s)[1]))
    return best
```

```python tests
Ps, Pr = dfig_split(2.0, -0.2)
assert abs(Ps - 1.6667) < 1e-4 and abs(Pr - 0.3333) < 1e-4, "At 1800 rpm: 1.667 and 0.333 MW."
Ps2, Pr2 = dfig_split(1.2, 0.3)
assert abs(Pr2 + 0.5143) < 1e-4, "Below synchronous speed the rotor draws power."
r = converter_rating(3.0, -0.3, 0.3)
assert abs(r - 3.0 * 0.3 / 1.3) < 1e-9, "With a cube-law wind curve the converter peaks at top speed: 0.69 MW."
```

::: right
Right. Because the wind's power falls as the cube of speed, the low-speed end of the range demands far less of the converter than the slip alone suggests.
:::
:::

::: explain
## How can a doubly fed generator deliver fixed-frequency power while its shaft speed varies?

::: model
The stator's currents must be at grid frequency, which means the rotor's magnetic field must turn at synchronous speed in space. The rotor itself turns at a different speed, so the converter feeding the rotor winding supplies current at the slip frequency, chosen so that the field's speed relative to the rotor, added to the rotor's own speed, equals synchronous speed. Above synchronous speed the rotor field turns backward relative to the rotor, and below it forward. The power drawn or delivered through the rotor is the slip times the stator power, so a modest converter can cover a useful speed range.
:::
:::

::: practice
::: check
given: P = 1 | 4; n = 1.1 | 0.85
answer: P/(2 - n)
unit: MW
tolerance: 0.5%

## Stator power: {P} MW to the grid at {n} × synchronous?

::: misses
- [any] $P/(1 - s)$.
:::
:::

::: check
given: V = 575 | 690; k = 2.2 | 3; s = 0.25 | 0.33
answer: s*k*V
unit: V
tolerance: 0.5%

## Rotor voltage: {V} V stator, ratio {k}, slip {s}?

::: misses
- [any] $|s|(N_r/N_s)V_s$.
:::
:::

::: check
given: p = 4 | 6; f = 50 | 60; r = 0.2 | 0.35
answer: 120*f/p*(1 + r)
unit: rpm
tolerance: 0.5%

## Top speed: {p} poles, {f} Hz, slip range ±{r}?

::: misses
- [any] $n_s(1 + s_\max)$.
:::
:::
:::