S12 · Lesson 24 · Induction motor tests and parameters
Finding the equivalent circuit from three measurements, the DC test for stator resistance, the no-load test for magnetizing reactance and rotational loss, the blocked-rotor test at reduced frequency for the leakage impedances, and splitting the leakage reactance by design class
A motor's nameplate gives voltage, current, speed and power, but not the six numbers of its equivalent circuit. Three simple tests on the bench supply them, each designed so that one part of the circuit dominates: direct current sees only the stator copper, a free-running rotor at nearly zero slip leaves only the magnetizing branch, and a locked rotor shorts the magnetizing branch out with its small . The results feed every calculation in the last four lessons.
- The locus of the 460 V motor's stator current phasor as its slip goes from nearly zero to standstill: almost a circle (the classic circle diagram), with the voltage along the real axis.
- At no load the current is small and nearly 90° behind the voltage: magnetizing current. At full load it swings toward the voltage; at standstill it's large and lagging again, limited mainly by leakage reactance.
- The no-load and blocked-rotor tests measure the two ends of this curve.
Predict
On the blocked-rotor test, why can the magnetizing branch be ignored?
At standstill the rotor branch is , about 0.5 Ω here, in parallel with = 20 Ω. Nearly all the current goes through the rotor branch, so the measured impedance is essentially . The test is also run at reduced voltage, since full voltage would drive several times rated current.
Name it
DC test
Apply DC between two terminals of the Y-connected stator: . (AC resistance is a little higher; the difference is usually ignored.)
No-load test
Run at rated voltage with no load. The slip is tiny, is enormous, and the rotor branch carries almost nothing:
- per-phase reactance (the resistance is small);
- rotational loss (friction, windage and core) .
Blocked-rotor test
Lock the rotor and raise the voltage until rated current flows, at a reduced frequency (often 25% of rated) so the rotor's current frequency resembles that in normal running, where deep bars behave differently than at 60 Hz:
Scale the reactance to rated frequency, , and split it by the motor's NEMA design class: equally for classes A and D, 40/60 for class B, 30/70 for class C. Then .
Worked example
The 460 V motor's tests: DC 12 V at 30 A; no load 460 V, 13.0 A, 600 W; blocked rotor at 15 Hz, 26.8 V line, 36 A, 1361 W. Find its circuit (class A).
Show the solution
- Stator resistance. The DC test drives two phases in series:
- No-load test. = 265.6 V, so and the rotational loss is
- Blocked-rotor resistance. so = 0.150 Ω.
- Blocked-rotor reactance. = 15.47 V and |Z| = 0.430 Ω, so = 0.250 Ω at 15 Hz, 1.00 Ω at 60 Hz.
- Split the reactances (class A). = 0.50 Ω, and close to the 20 Ω the motor was built with.
Answer = 0.200 Ω, = 0.150 Ω, = 0.50 Ω and = 19.9 Ω, with 499 W of rotational loss.
Worked example
The same blocked-rotor data, but the motor is NEMA class B. How do the reactances split?
Show the solution
- Stator leakage reactance. Class B puts 40% of the 1.00 Ω in the stator: and = 0.60 Ω.
- Magnetizing reactance.
- Why the split matters. Class B rotors have deeper bars and more rotor leakage. The difference matters most for starting current and torque, which depend on and how it divides around the magnetizing branch.
Answer = 0.40 Ω, = 0.60 Ω and = 20.0 Ω.
Worked example
The 460 V motor's blocked-rotor test is repeated at 60 Hz instead of 15 Hz, and now gives = 0.42 Ω. What rotor resistance would that imply, and what would it do to the predicted full-load slip?
Show the solution
- Implied rotor resistance. 47% more than the 0.15 Ω measured at 15 Hz.
- Why it's higher. At 60 Hz the rotor current crowds into the tops of the bars (lesson 25's deep-bar effect), raising their resistance, but in normal running the rotor current alternates at only a hertz or two and uses the whole bar.
- Effect on the prediction. Since slip at a given torque is nearly proportional to , the 60 Hz value would predict a full-load slip about 47% too high, and an efficiency too low.
- The standard test. That's why the standard test uses a quarter of rated frequency.
Answer it implies = 0.22 Ω, 47% too high, so it would predict a full-load slip about 47% too high.
Check
A DC test applies 12 V between two terminals of a Y-connected stator and draws 10 A. What's ?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
On no load the motor draws 8 A and 857.6 W, with = 0.3 Ω. What's its rotational loss?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
On no load at 460 V (line, Y) the motor draws 5 A. About what is ?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A blocked-rotor test draws 40 A and 2160 W; = 0.05 Ω. What's ?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
At 20 Hz the blocked-rotor test needs 44 V (line, Y) for 30 A, and = 0.15 Ω. What's at 60 Hz?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A motor's no-load reactance is 20 Ω and its total leakage reactance 1.2 Ω, of which the stator takes a fraction 0.5. What's ?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A Y-connected motor's DC test reads 10 V at 10 A between two terminals; its no-load test at 460 V line takes 30 A and 200 W.
(a)
What is ?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
What is , approximately?
(c)
What is the rotational loss?
Check
A blocked-rotor test at f hertz takes P watts at I amperes per phase with phase voltage V; the motor is rated F hertz.
Step 1
What is ?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is at rated frequency?
Explain why
Why is the blocked-rotor test run at reduced frequency?
In normal running the rotor's currents alternate at slip frequency, a hertz or two, but on a blocked rotor at line frequency they'd alternate at 60 Hz. Rotor bars, especially the deep or double-cage bars of class B and C motors, behave very differently at those two frequencies: at 60 Hz the current crowds toward the top of each bar, raising its effective resistance and lowering its leakage inductance. Parameters measured at 60 Hz would describe the motor at starting, not at its operating point. Testing at about a quarter of rated frequency puts the rotor much closer to its running condition, and the reactance is simply scaled back up to rated frequency.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.