title: Inverter-fed motors
heading: What a PWM inverter does to a motor: fast edges reflecting on the cable and nearly doubling the terminal voltage, the critical cable length, insulation limits, common-mode voltage and bearing currents, harmonic losses and the filters and motors that cope with them
eyebrow: S12 · Lesson 45 · Inverter-fed motors
xp: 50
---

::: hook
Lessons 27, 41 and 42 treated the drive as a perfect source of sinusoidal currents. The motor sees something harsher: voltage steps of several hundred volts every few microseconds, each rising in a fraction of a microsecond. On a long cable those edges reflect and pile up to nearly twice the DC bus at the motor terminals; the inverter's common-mode voltage leaks through the motor's capacitances and arcs across its bearings; and the switching ripple adds losses. Motors designed for the line can fail in months on a drive, which is why "inverter duty" became a rating of its own.
:::

::: play
- The curve is the voltage at a motor's terminals when a 650 V step with a 100 ns rise arrives over a cable of the length on the slider, with the wave traveling at 150 m/µs, the motor reflecting 90% (Γ = 0.9) and the inverter end reflecting it back inverted (Γ = −1). Time is in microseconds.
- With a cable longer than the critical length, $v t_r/2$ = 7.5 m here, the wave reaches $1.9 \times 650$ = 1235 V before the inverted reflection returns.
- Shorter cables bring the inverted reflection back while the edge is still rising, which limits the overshoot.
:::

```sim plot
view: graph
x: t = 0..1
y: V = 0..1400
slider: l = 5..40 = 20
plot: 1235*(1*((t - 1*l/150)/0.1*step((t - 1*l/150))*step(0.1 - (t - 1*l/150)) + step((t - 1*l/150) - 0.1)) - 0.9*((t - 3*l/150)/0.1*step((t - 3*l/150))*step(0.1 - (t - 3*l/150)) + step((t - 3*l/150) - 0.1)) + 0.81*((t - 5*l/150)/0.1*step((t - 5*l/150))*step(0.1 - (t - 5*l/150)) + step((t - 5*l/150) - 0.1)) - 0.729*((t - 7*l/150)/0.1*step((t - 7*l/150))*step(0.1 - (t - 7*l/150)) + step((t - 7*l/150) - 0.1)) + 0.6561*((t - 9*l/150)/0.1*step((t - 9*l/150))*step(0.1 - (t - 9*l/150)) + step((t - 9*l/150) - 0.1)) - 0.59049*((t - 11*l/150)/0.1*step((t - 11*l/150))*step(0.1 - (t - 11*l/150)) + step((t - 11*l/150) - 0.1)) + 0.531441*((t - 13*l/150)/0.1*step((t - 13*l/150))*step(0.1 - (t - 13*l/150)) + step((t - 13*l/150) - 0.1)) - 0.478297*((t - 15*l/150)/0.1*step((t - 15*l/150))*step(0.1 - (t - 15*l/150)) + step((t - 15*l/150) - 0.1)) + 0.430467*((t - 17*l/150)/0.1*step((t - 17*l/150))*step(0.1 - (t - 17*l/150)) + step((t - 17*l/150) - 0.1)) - 0.38742*((t - 19*l/150)/0.1*step((t - 19*l/150))*step(0.1 - (t - 19*l/150)) + step((t - 19*l/150) - 0.1)) + 0.348678*((t - 21*l/150)/0.1*step((t - 21*l/150))*step(0.1 - (t - 21*l/150)) + step((t - 21*l/150) - 0.1)) - 0.313811*((t - 23*l/150)/0.1*step((t - 23*l/150))*step(0.1 - (t - 23*l/150)) + step((t - 23*l/150) - 0.1)) + 0.28243*((t - 25*l/150)/0.1*step((t - 25*l/150))*step(0.1 - (t - 25*l/150)) + step((t - 25*l/150) - 0.1)) - 0.254187*((t - 27*l/150)/0.1*step((t - 27*l/150))*step(0.1 - (t - 27*l/150)) + step((t - 27*l/150) - 0.1)) + 0.228768*((t - 29*l/150)/0.1*step((t - 29*l/150))*step(0.1 - (t - 29*l/150)) + step((t - 29*l/150) - 0.1))) | label: motor terminal voltage, V
```

::: predict
## A 460 V drive with a 650 V bus and IGBTs switching in 100 ns feeds a motor through 50 m of cable. About what peak voltage reaches the motor's terminals?

- [ ] 650 V
- [ ] 460 V
- [x] About 1200 V
- [ ] About 2600 V

::: reveal
The cable is a transmission line, and the motor's high-frequency impedance is far above the cable's, so the edge reflects with Γ ≈ 0.9 and the terminal voltage jumps to about (1 + 0.9) × 650 = 1235 V. That's above the 1 kV peak that NEMA MG 1 Part 30 allows general-purpose motors, but within Part 31's 3.1 times rated voltage, 1426 V, for inverter-duty motors.
:::
:::

::: nameit
## Reflected waves

A cable of characteristic impedance $Z_0$ (tens of ohms) feeding a motor whose winding looks like several hundred ohms or more to a fast edge reflects with $\Gamma_L = (Z_m - Z_0)/(Z_m + Z_0)$, close to 1. If the reflection returns to the motor after the edge has finished rising, the terminal voltage reaches $(1 + \Gamma_L)V_\text{dc}$. That happens when the cable exceeds the **critical length**
$$l_c = \frac{vt_r}{2}$$
with v the wave speed in the cable (roughly 150 to 200 m/µs) and $t_r$ the edge's rise time. Faster switches (SiC, GaN) make the critical length a few meters, so almost every cable counts as long.

## Insulation

The turn-to-turn insulation near the line end of each winding sees most of the steep front. NEMA MG 1 limits general-purpose motors to 1 kV peak with rise times of at least 2 µs; inverter-duty motors (Part 31) withstand 3.1 times rated voltage with rise times down to 0.1 µs. Repeated partial discharges in the air pockets of an inadequate winding erode its insulation within months.

## Common-mode voltage and bearings

A two-level inverter's three outputs can never sum to zero, so the voltage of the motor's neutral relative to ground steps by $V_\text{dc}/3$ at every switching. Through the stray capacitances from the windings to the rotor and from the rotor to the frame, a fraction of it, the **bearing voltage ratio** (a few percent), appears across the bearings' grease film; when it breaks down, discharge pits the races (electrical discharge machining). Remedies include shaft grounding brushes or rings, insulated or ceramic bearings, and common-mode filters.

## Harmonic losses and filters

The PWM ripple adds copper and iron losses at the switching frequency, typically a few percent of the motor's losses. Long cables, high-voltage motors and old windings call for **dv/dt filters** (slowing the edges below the critical length's rise time) or **sine filters** (LC filters below the switching frequency), at the cost of their own losses and voltage drop.
:::

::: example
## A drive's IGBTs switch in 100 ns and its cable carries waves at 150 m/µs. What is the critical length, and what reaches a motor on 50 m of cable from a 650 V bus, with Γ = 0.9 at the motor?

::: solution
1. **Critical length.**
   $$\begin{aligned} l_c &= \frac{150 \times 0.1}{2} \\ &= 7.5\ \text{m} \end{aligned}$$
2. **Voltage at the motor.** At 50 m the reflection returns 0.67 µs after the edge arrives, long after it has finished rising, so the terminal voltage reaches
   $$\begin{aligned} V &= 1.9 \times 650 \\ &= 1235\ \text{V} \end{aligned}$$
3. **Against the motor's limits.** A general-purpose motor's 1 kV limit is exceeded; an inverter-duty motor's 3.1 × 460 = 1426 V is not.
4. **A dv/dt filter.** A filter that stretches the rise to 1 µs would raise the critical length to 75 m.

**Answer:** the critical length is 7.5 m, and on 50 m of cable 1235 V reaches the motor.
:::
:::

::: example
## The same drive switches to SiC MOSFETs with 20 ns edges. What happens to the critical length and the dv/dt?

::: solution
1. **Critical length.**
   $$\begin{aligned} l_c &= \frac{150 \times 0.02}{2} \\ &= 1.5\ \text{m} \end{aligned}$$
   Almost any installed cable is now long, and the motor sees the full 1.9 times overshoot.
2. **dv/dt.** The edge's slope rises from 650 V/100 ns = 6.5 kV/µs to 32.5 kV/µs, pushing more of the voltage onto the first turns of the winding.
3. **The trade-off.** Wide-bandgap drives bring lower losses and higher switching frequencies, but motors fed by them need inverter-duty insulation or filters, or the drive must be mounted on the motor.

**Answer:** the critical length falls to 1.5 m, and the dv/dt rises from 6.5 to 32.5 kV/µs.
:::
:::

::: example
## A 650 V bus drive feeds a motor whose bearing voltage ratio is 4%. How large are the voltage steps across the bearings, and why do they matter?

::: solution
1. **Common-mode step.** The common-mode voltage steps by 650/3 = 217 V at each switching.
2. **Bearing voltage.**
   $$\begin{aligned} V_b &= 0.04 \times 217 \\ &= 8.7\ \text{V} \end{aligned}$$
3. **Film breakdown.** A bearing's lubricating film, a few micrometers thick, can break down at voltages in this range, and each breakdown discharges the stored charge through a tiny spot on the race.
4. **Fluting.** Thousands of such discharges a second etch the races into a washboard pattern (fluting) within months, which is why large drive-fed motors use insulated bearings or a shaft grounding ring.

**Answer:** the bearings see steps of 8.7 V, enough to break down the lubricating film and, over months, flute the races.
:::
:::

::: check
kind: parts
given: t = 20 | 50 | 100 | 200; v = 150 | 180

## A drive's edges rise in {t} ns and its cable carries waves at {v} m/µs.

::: part
answer: v*t*1e-3/2
unit: m
tolerance: 0.5%

### What is the critical cable length?

::: misses
- [v*t*1e-3] The reflection makes a round trip.
- [any] $vt_r/2$.
:::
:::
:::

::: check
kind: parts
given: V = 540 | 650 | 800; g = 0.8 | 0.9 | 0.95; r = 230 | 400 | 460

## A drive with a {V} V bus feeds a {r} V motor over a long cable; the motor reflects with Γ = {g}.

::: part
answer: (1 + g)*V
unit: V
tolerance: 0.5%

### What peak voltage reaches the motor?

::: misses
- [2*V] Γ is a little below 1.
- [any] $(1 + \Gamma)V_\text{dc}$.
:::
:::

::: part
answer: (1 + g)*V/(3.1*r)*100
unit: %
tolerance: 0.5%

### What percentage of an inverter-duty motor's 3.1 × rated limit is that?

::: misses
- [any] Over $3.1V_\text{rated}$.
:::
:::
:::

::: check
kind: parts
given: m = 100 | 300 | 800; Z = 30 | 50 | 80

## A motor's winding presents {m} Ω to a fast edge arriving on a cable of {Z} Ω.

::: part
answer: (m - Z)/(m + Z)
tolerance: 0.5%

### What is the reflection coefficient at the motor?

::: misses
- [(Z - m)/(m + Z)] Load minus line, over the sum.
- [any] $(Z_m - Z_0)/(Z_m + Z_0)$.
:::
:::
:::

::: check
kind: parts
given: V = 540 | 650 | 1100; b = 2 | 4 | 6

## A two-level drive on a {V} V bus feeds a motor whose bearing voltage ratio is {b}%.

::: part
answer: V/3
unit: V
tolerance: 0.5%

### By how much does the common-mode voltage step at each switching?

::: misses
- [V/2] Each switching moves one of three legs.
- [any] $V_\text{dc}/3$.
:::
:::

::: part
answer: V/3*b/100
unit: V
tolerance: 0.5%

### How large are the steps across the bearings?

::: misses
- [any] The bearing voltage ratio times that.
:::
:::
:::

::: check
kind: parts
given: V = 400 | 650 | 1000; t = 20 | 100 | 500

## An inverter's {V} V edges rise in {t} ns.

::: part
answer: V/t
unit: kV/µs
tolerance: 0.5%

### What is the dv/dt?

::: misses
- [any] Voltage over rise time.
:::
:::
:::

::: check
kind: choice

## Why does mounting the drive on the motor itself remove the reflected-wave problem?

- [ ] The motor's frame shields the edges
- [x] With a cable of a few tens of centimeters, the reflection returns long before the edge finishes rising, so the cable never acts as a transmission line and the voltage can't build up beyond the bus
- [ ] Integrated drives switch more slowly
- [ ] The motor's impedance becomes matched

::: misses
- [1] Shielding doesn't change the reflection.
- [3] Integrated drives often switch faster.
- [4] The motor's impedance is unchanged; the cable is too short to matter.
:::
:::

::: check
kind: derivation
vars: V = 100..1500, t = 0.00000001..0.000002, v = 100000000..200000000, m = 50..2000, Z = 10..100

## A drive's V-volt edges rise in t seconds on a cable with wave speed v and impedance Z, feeding a motor that presents m ohms to fast edges.

::: step
answer: v*t/2

### What is the critical length, in meters?
:::

::: step
answer: (m - Z)/(m + Z)

### What is the reflection coefficient at the motor?
:::

::: step
answer: (1 + (m - Z)/(m + Z))*V

### What peak voltage reaches the motor on a long cable?
:::

::: right
Right. A long cable and a high motor impedance together nearly double the bus at the terminals.
:::
:::

::: check
kind: python

## Write `terminal_voltage(t, V, tr, length, v, gl, gs)`: the motor's terminal voltage at time t for a ramped step of V rising in tr, launched at t = 0 into a cable of the given length and wave speed, with reflection coefficients gl at the motor and gs at the inverter, by summing the successive reflections; and `peak_voltage(V, tr, length, v, gl, gs)`: its maximum over the time it takes the reflections to die away.

```python starter
def terminal_voltage(t, V, tr, length, v, gl, gs):
    return V if t > 0 else 0.0

def peak_voltage(V, tr, length, v, gl, gs):
    return V
```

```python solution
def ramp(x, tr):
    return 0.0 if x <= 0 else (x / tr if x < tr else 1.0)

def terminal_voltage(t, V, tr, length, v, gl, gs):
    tau = length / v
    s, c, k = 0.0, 1.0, 0
    while t - (2 * k + 1) * tau > 0 and k < 1000:
        s += c * ramp(t - (2 * k + 1) * tau, tr)
        c *= gs * gl
        k += 1
    return V * (1 + gl) * s

def peak_voltage(V, tr, length, v, gl, gs):
    tau = length / v
    T = 120 * tau + tr
    n = 6000
    return max(terminal_voltage(T * i / n, V, tr, length, v, gl, gs) for i in range(n + 1))
```

```python tests
assert abs(peak_voltage(650, 100e-9, 50, 150e6, 0.9, -1) - 1235) < 1, "A long cable: 1.9 times the bus."
assert peak_voltage(650, 100e-9, 2, 150e6, 0.9, -1) < 750, "A short cable: little overshoot."
assert abs(terminal_voltage(1e-3, 650, 100e-9, 20, 150e6, 0.9, -1) - 650) < 1, "Eventually the motor sees the bus voltage."
assert abs(peak_voltage(650, 100e-9, 2, 150e6, 0.9, 0) - 1235) < 1, "With a matched source nothing returns to cancel the overshoot."
```

::: right
Right. The inverter's low impedance sends each reflection back inverted, which is what keeps short cables safe and why longer ones are not.
:::
:::

::: explain
## Why can a motor that runs for decades on the line fail within months on a PWM drive with a long cable?

::: model
Each switching edge travels down the cable as a wave and reflects from the motor, whose impedance to fast edges is much higher than the cable's, so the terminal voltage overshoots to nearly twice the DC bus whenever the cable is longer than about half the distance the wave travels during the edge's rise. These overshoots arrive thousands of times a second, and the steep fronts concentrate across the first turns of the winding. In insulation not designed for them, partial discharges in tiny voids erode the enamel a little at each edge, until a turn-to-turn short burns the winding. Inverter-duty insulation, filters that slow the edges, or a short cable prevent it.
:::
:::

::: practice
::: check
given: t = 30 | 150; v = 160 | 190
answer: v*t*1e-3/2
unit: m
tolerance: 0.5%

## Critical length: {t} ns rise, {v} m/µs?

::: misses
- [any] $vt_r/2$.
:::
:::

::: check
given: V = 560 | 700; g = 0.85 | 0.92
answer: (1 + g)*V
unit: V
tolerance: 0.5%

## Peak at the motor: {V} V bus, Γ = {g}, long cable?

::: misses
- [any] $(1 + \Gamma)V_\text{dc}$.
:::
:::

::: check
given: V = 600 | 900; b = 3 | 5
answer: V/3*b/100
unit: V
tolerance: 0.5%

## Bearing voltage steps: {V} V bus, ratio {b}%?

::: misses
- [any] $(V_\text{dc}/3) \times$ ratio.
:::
:::
:::