S12 · Lesson 16 · Steady-state operating characteristics

How field current sets a synchronous machine's reactive power at fixed real power, the V-curves of armature current against excitation, the steady-state stability limit, the synchronous motor as a power-factor corrector, and the synchronous condenser

Connected to a stiff grid, a synchronous machine's real power is set by its shaft: the turbine's throttle for a generator, the load for a motor. Its field current is free, and it sets something else entirely: whether the machine supplies or absorbs reactive power. An overexcited synchronous motor can run a factory's compressor and correct the plant's power factor at the same time; with no shaft load at all, it becomes a synchronous condenser, a rotating capacitor bank that grids still use.

  • The V-curves of a synchronous motor on a 1 pu bus: armature current against excitation voltage Ef at three loads (P, P/2 and none), for synchronous reactance Xs.
  • Each curve's minimum is at unity power factor; to the right the motor is overexcited and draws leading current (supplying reactive power), to the left it's underexcited and draws lagging current.
  • Lower excitation pushes the load angle toward 90°, where the motor would pull out of step.

Predict

A synchronous motor (Xs = 1 pu) carries 0.8 pu of load on a 1 pu bus. Its field is raised until Ef = 1.5 pu. What does it do to the plant's reactive power?

Name it

Real power is fixed by the shaft

On an infinite bus V, the real power P=(VEf/Xs)sin⁡δ is set mechanically. Changing the field changes Ef, and δ adjusts to keep Efsin⁡δ constant.

Reactive power follows the field

The reactive power the machine supplies to the bus, per unit and with Ra neglected, is

Q=V(Efcos⁡δ−V)Xs

Overexcited (Efcos⁡δ>V), the machine supplies reactive power, as a capacitor would; underexcited, it absorbs it.

V-curves

Plotting armature current against field current at constant real power gives V-shaped curves, with the minimum current at unity power factor, where Ef=V2+(PXs)2 (motor or generator). The curves end on the left at the steady-state stability limit, δ = 90°, where Ef=PXs/V.

The synchronous condenser

With no shaft load, δ = 0 and the machine supplies Q=V(Ef−V)/Xs: continuously variable reactive power from a field rheostat, with real inertia and fault current that power-electronic compensators lack.

Worked example

The 0.8 pu motor (Xs = 1 pu) on a 1 pu bus: what excitation gives unity power factor, and what happens at Ef = 1.0?

Show the solution
  1. Excitation for unity power factor. Ef=1+0.82=1.281pu at δ = −38.7°, with the current at its minimum of 0.8 pu.
  2. At Ef = 1.0. δ = −53.1° and the current is 0.894 pu, now lagging: the motor absorbs 0.4 pu of reactive power.
  3. Pull-out. Below Ef = 0.8 it would pull out of step.

Answer Ef = 1.281 pu gives unity power factor, at δ = −38.7° and 0.8 pu of current. At Ef = 1.0 the load angle is −53.1° and the current rises to 0.894 pu lagging, as the motor absorbs 0.4 pu of reactive power.

Worked example

A 50 MVA synchronous condenser with Xs = 0.9 pu runs at Ef = 1.4 pu on a 1 pu bus. What does it supply?

Show the solution
  1. Reactive power. Q=1.4−10.9=0.444pu which is 22.2 Mvar.
  2. With a weak field. Dropping the field to Ef = 0.6 pu would make it absorb the same 22.2 Mvar, useful at night when long, lightly loaded lines generate excess reactive power.

Answer it supplies 0.444 pu of reactive power, 22.2 Mvar.

Worked example

A generator with Xs = 1.2 pu delivers 0.6 pu of real power to a 1 pu bus. What excitation gives unity power factor, how low can the field go before it loses synchronism, and what does it supply at Ef = 1.5?

Show the solution
  1. Excitation for unity power factor. Ef=1+(PXs)2=1+0.722=1.232pu
  2. Stability limit. The limit is δ = 90°, where Ef=PXs/V=0.72pu Below that the field can't hold 0.6 pu.
  3. Load angle at Ef = 1.5. sin⁡δ=0.72/1.5 gives δ = 28.7°.
  4. Reactive power at Ef = 1.5. Q=1.5cos⁡28.7°−11.2=0.263pu supplied to the bus.
  5. Margin. Operators keep the field well above the limit, since a fault that briefly lowers the voltage also lowers the power the machine can transfer.

Answer Ef = 1.232 pu gives unity power factor, and the field can fall to 0.72 pu before the machine loses synchronism. At Ef = 1.5 it runs at δ = 28.7° and supplies 0.263 pu of reactive power to the bus.

Check

A 100 MVA synchronous condenser with Xs = 0.8 pu runs at Ef = 1.3 pu on a 1 pu bus. How much reactive power does it supply?

Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.

Check

A synchronous motor with Xs = 0.6 pu carries 0.6 pu on a 1 pu bus. What excitation voltage gives unity power factor?

Check

A synchronous motor (Xs = 0.7 pu) carries 0.3 pu on a 1 pu bus at Ef = 1.8 pu. What armature current does it draw?

Check

A synchronous machine (Xs = 0.6 pu, Ef = 2 pu, 1 pu bus) carries 0.4 pu. What's the magnitude of its load angle?

Check

A machine with Xs = 0.7 pu carries 0.8 pu on a 1 pu bus. What's the least excitation voltage that keeps it in step?

Check

An overexcited synchronous motor (Xs = 0.7 pu, Ef = 2 pu, 1 pu bus) carries 0.3 pu. How much reactive power does it supply to the plant?

Check

A synchronous machine (Xs = 0.8 pu) delivers 0.6 pu of real power to a 1 pu bus with Ef = 2 pu.

(a)

What is its load angle?

(b)

What reactive power does it supply, in per unit?

Check

A synchronous machine with reactance X delivers real power P (per unit) to a 1 pu bus.

Step 1

What excitation gives unity power factor?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does raising a synchronous motor's field current change its power factor but not its speed or real power?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.