S12 · Lesson 16 · Steady-state operating characteristics
How field current sets a synchronous machine's reactive power at fixed real power, the V-curves of armature current against excitation, the steady-state stability limit, the synchronous motor as a power-factor corrector, and the synchronous condenser
Connected to a stiff grid, a synchronous machine's real power is set by its shaft: the turbine's throttle for a generator, the load for a motor. Its field current is free, and it sets something else entirely: whether the machine supplies or absorbs reactive power. An overexcited synchronous motor can run a factory's compressor and correct the plant's power factor at the same time; with no shaft load at all, it becomes a synchronous condenser, a rotating capacitor bank that grids still use.
- The V-curves of a synchronous motor on a 1 pu bus: armature current against excitation voltage at three loads (P, P/2 and none), for synchronous reactance .
- Each curve's minimum is at unity power factor; to the right the motor is overexcited and draws leading current (supplying reactive power), to the left it's underexcited and draws lagging current.
- Lower excitation pushes the load angle toward 90°, where the motor would pull out of step.
Predict
A synchronous motor ( = 1 pu) carries 0.8 pu of load on a 1 pu bus. Its field is raised until = 1.5 pu. What does it do to the plant's reactive power?
The real power fixes = 0.8, so δ = −32.2°. The current is = 0.8 + j0.269 pu: leading, so the motor supplies divided by = 0.269 pu of reactive power while still drawing its 0.8 pu of real power. The armature current rises to 0.844 pu, at 0.948 power factor leading.
Name it
Real power is fixed by the shaft
On an infinite bus V, the real power is set mechanically. Changing the field changes , and δ adjusts to keep constant.
Reactive power follows the field
The reactive power the machine supplies to the bus, per unit and with neglected, is
Overexcited (), the machine supplies reactive power, as a capacitor would; underexcited, it absorbs it.
V-curves
Plotting armature current against field current at constant real power gives V-shaped curves, with the minimum current at unity power factor, where (motor or generator). The curves end on the left at the steady-state stability limit, δ = 90°, where .
The synchronous condenser
With no shaft load, δ = 0 and the machine supplies : continuously variable reactive power from a field rheostat, with real inertia and fault current that power-electronic compensators lack.
Worked example
The 0.8 pu motor ( = 1 pu) on a 1 pu bus: what excitation gives unity power factor, and what happens at = 1.0?
Show the solution
- Excitation for unity power factor. at δ = −38.7°, with the current at its minimum of 0.8 pu.
- At = 1.0. δ = −53.1° and the current is 0.894 pu, now lagging: the motor absorbs 0.4 pu of reactive power.
- Pull-out. Below = 0.8 it would pull out of step.
Answer = 1.281 pu gives unity power factor, at δ = −38.7° and 0.8 pu of current. At = 1.0 the load angle is −53.1° and the current rises to 0.894 pu lagging, as the motor absorbs 0.4 pu of reactive power.
Worked example
A 50 MVA synchronous condenser with = 0.9 pu runs at = 1.4 pu on a 1 pu bus. What does it supply?
Show the solution
- Reactive power. which is 22.2 Mvar.
- With a weak field. Dropping the field to = 0.6 pu would make it absorb the same 22.2 Mvar, useful at night when long, lightly loaded lines generate excess reactive power.
Answer it supplies 0.444 pu of reactive power, 22.2 Mvar.
Worked example
A generator with = 1.2 pu delivers 0.6 pu of real power to a 1 pu bus. What excitation gives unity power factor, how low can the field go before it loses synchronism, and what does it supply at = 1.5?
Show the solution
- Excitation for unity power factor.
- Stability limit. The limit is δ = 90°, where Below that the field can't hold 0.6 pu.
- Load angle at = 1.5. gives δ = 28.7°.
- Reactive power at = 1.5. supplied to the bus.
- Margin. Operators keep the field well above the limit, since a fault that briefly lowers the voltage also lowers the power the machine can transfer.
Answer = 1.232 pu gives unity power factor, and the field can fall to 0.72 pu before the machine loses synchronism. At = 1.5 it runs at δ = 28.7° and supplies 0.263 pu of reactive power to the bus.
Check
A 100 MVA synchronous condenser with = 0.8 pu runs at = 1.3 pu on a 1 pu bus. How much reactive power does it supply?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A synchronous motor with = 0.6 pu carries 0.6 pu on a 1 pu bus. What excitation voltage gives unity power factor?
Check
A synchronous motor ( = 0.7 pu) carries 0.3 pu on a 1 pu bus at = 1.8 pu. What armature current does it draw?
Check
A synchronous machine ( = 0.6 pu, = 2 pu, 1 pu bus) carries 0.4 pu. What's the magnitude of its load angle?
Check
A machine with = 0.7 pu carries 0.8 pu on a 1 pu bus. What's the least excitation voltage that keeps it in step?
Check
An overexcited synchronous motor ( = 0.7 pu, = 2 pu, 1 pu bus) carries 0.3 pu. How much reactive power does it supply to the plant?
Check
A synchronous machine ( = 0.8 pu) delivers 0.6 pu of real power to a 1 pu bus with = 2 pu.
(a)
What is its load angle?
(b)
What reactive power does it supply, in per unit?
Check
A synchronous machine with reactance X delivers real power P (per unit) to a 1 pu bus.
Step 1
What excitation gives unity power factor?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is the least excitation that can hold P?
Explain why
Why does raising a synchronous motor's field current change its power factor but not its speed or real power?
A synchronous motor turns at exactly synchronous speed whatever its excitation, because its rotor is locked to the stator's rotating field; and the real power it draws is whatever the shaft load demands. Raising the field current raises the internal voltage . With the real power fixed, must stay constant, so the load angle shrinks as grows, and the extra length of appears along V. That in-phase surplus over the bus voltage drives a reactive current through the synchronous reactance, leading the voltage, so the motor begins to supply reactive power. Lowering the field reverses it, until at too little excitation the angle reaches 90° and the motor pulls out of step.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.