title: "Problem set 1: conversion, materials, transformers and force"
heading: "Problem set 1: the linear machine, magnetic materials and permanent magnets, transformer efficiency and regulation, and forces from energy and coenergy"
eyebrow: S12 · Problem set 1
type: problems
---

::: hook
These problems cover lessons 1 to 5: the linear machine as motor and generator, core-loss separation and laminations, magnets on their load lines, transformer efficiency over a load cycle, regulation and inrush, and the forces and torques that follow from coenergy.
:::

::: pool
pick: 12

::: check
kind: parts
given: V = 24 | 120; B = 0.4 | 0.8; l = 0.5 | 1; R = 0.1 | 0.3; F = 4 | 12

## A linear machine: {V} V battery, {R} Ω, a {l} m bar in {B} T, carrying a {F} N load.

::: part
answer: F/(B*l)
unit: A
tolerance: 0.5%

### Current?

::: misses
- [any] $F/(Bl)$.
:::
:::

::: part
answer: (V - F*R/(B*l))/(B*l)
unit: m/s
tolerance: 0.5%

### Speed?

::: misses
- [any] $(V_B - iR)/(Bl)$.
:::
:::

::: part
answer: 100*(V - F*R/(B*l))/V
unit: %
tolerance: 0.5%

### Efficiency?

::: misses
- [any] $e/V_B$.
:::
:::
:::

::: check
kind: parts
given: V = 48 | 240; B = 0.5 | 1; l = 0.3 | 1; R = 0.05 | 0.2; v = 1.1 | 1.3

## The linear machine ({V} V, {B} T, {l} m, {R} Ω) is driven at {v} times its no-load speed.

::: part
answer: v*V
unit: V
tolerance: 0.5%

### Induced voltage?

::: misses
- [any] $Blv$.
:::
:::

::: part
answer: (v*V - V)/R
unit: A
tolerance: 0.5%

### Current into the battery?

::: misses
- [any] $(e - V_B)/R$.
:::
:::

::: part
answer: 100*V/(v*V)
unit: %
tolerance: 0.5%

### Generator efficiency?

::: misses
- [any] $V_B/e$.
:::
:::
:::

::: check
kind: parts
given: B = 0.4 | 1.2; m = 1.05 | 1.1; g = 0.5 | 1.5; l = 3 | 10

## A magnet with $B_r$ = {B} T and $\mu_r$ = {m}, {l} mm long, facing a {g} mm gap of equal area.

::: part
answer: B/(1 + m*g/l)
unit: T
tolerance: 0.5%

### Gap flux density?

::: misses
- [any] $B_r/(1 + \mu_rg/l_m)$.
:::
:::

::: part
answer: (B/(1 + m*g/l))*(B/(1 + m*g/l))*g/(4e-7*pi*l)/1000
unit: kJ/m³
tolerance: 0.5%

### Its energy product there?

::: misses
- [any] $B_m|H_m|$ with $|H_m| = B_gg/(\mu_0l_m)$.
:::
:::

::: part
answer: B^2/(4*4e-7*pi*m)/1000
unit: kJ/m³
tolerance: 0.5%

### The most it could be?

::: misses
- [any] $B_r^2/(4\mu_0\mu_r)$.
:::
:::
:::

::: check
kind: parts
given: P = 0.8 | 1.5; k = 1.25 | 1.35; F = 200 | 400

## A steel loses {P} W/kg at 50 Hz and {k} times as much at 60 Hz, same flux density.

::: part
answer: 50*(k*P*2500 - P*3600)/(60*2500 - 50*3600)
unit: W/kg
tolerance: 0.5%

### Hysteresis loss at 50 Hz?

::: misses
- [any] $50a$, from $P = af + bf^2$ at two frequencies.
:::
:::

::: part
answer: P - 50*(k*P*2500 - P*3600)/(60*2500 - 50*3600)
unit: W/kg
tolerance: 0.5%

### Eddy-current loss at 50 Hz?

::: misses
- [any] The rest of the 50 Hz loss.
:::
:::

::: part
answer: F*(k*P*2500 - P*3600)/(60*2500 - 50*3600) + F^2*(P - 50*(k*P*2500 - P*3600)/(60*2500 - 50*3600))/2500
unit: W/kg
tolerance: 0.5%

### Loss at {F} Hz?

::: misses
- [any] $aF + bF^2$.
:::
:::
:::

::: check
kind: parts
given: S = 25 | 150; c = 100 | 400; u = 500 | 1800; p = 0.8 | 0.95

## A {S} kVA transformer with {c} W core and {u} W full-load copper loss, at power factor {p}.

::: part
answer: 100*S*1000*p/(S*1000*p + c + u)
unit: %
tolerance: 0.5%

### Full-load efficiency?

::: misses
- [any] $Sp/(Sp + P_c + P_{cu})$.
:::
:::

::: part
answer: sqrt(c/u)
tolerance: 0.5%

### Load for peak efficiency?

::: misses
- [any] $\sqrt{P_c/P_{cu}}$.
:::
:::

::: part
answer: 100*sqrt(c/u)*S*1000*p/(sqrt(c/u)*S*1000*p + 2*c)
unit: %
tolerance: 0.5%

### Peak efficiency?

::: misses
- [any] Losses are $2P_c$ there.
:::
:::
:::

::: check
kind: parts
given: S = 50 | 300; c = 0.25 | 0.5; u = 1 | 2; h = 6 | 10; x = 0.15 | 0.35

## A {S} kVA transformer (core {c}%, full-load copper {u}% of rating) runs {h} h at full load and the rest of the day at {x} load, unity power factor.

::: part
answer: h*S + (24 - h)*x*S
unit: kWh
tolerance: 0.5%

### Energy delivered per day?

::: misses
- [any] Load × hours.
:::
:::

::: part
answer: 24*c*S/100 + (h + (24 - h)*x^2)*u*S/100
unit: kWh
tolerance: 0.5%

### Energy lost?

::: misses
- [any] Core all day, copper as load squared.
:::
:::

::: part
answer: 100*(h*S + (24 - h)*x*S)/(h*S + (24 - h)*x*S + 24*c*S/100 + (h + (24 - h)*x^2)*u*S/100)
unit: %
tolerance: 0.5%

### All-day efficiency?

::: misses
- [any] Out over out plus lost.
:::
:::
:::

::: check
kind: parts
given: r = 0.006 | 0.015; x = 0.04 | 0.08; p = 0.7 | 0.9; B = 1.5 | 1.7; e = 0.3 | 0.6

## A transformer with series impedance {r} + j\given{x} pu, normally at {B} T peak, with residual flux {e} of its peak.

::: part
answer: 100*(r*p + x*sqrt(1 - p^2))
unit: %
tolerance: 0.5%

### Approximate regulation at pf {p} lagging?

::: misses
- [any] $r\cos\theta + x\sin\theta$.
:::
:::

::: part
answer: 100*(sqrt((1 + r*p + x*sqrt(1 - p^2))^2 + (x*p - r*sqrt(1 - p^2))^2) - 1)
unit: %
tolerance: 0.5%

### Exact regulation?

::: misses
- [any] $|1 + (r + jx)(\cos\theta - j\sin\theta)| - 1$.
:::
:::

::: part
answer: (2 + e)*B
unit: T
tolerance: 0.5%

### Worst inrush flux density (no saturation)?

::: misses
- [any] Residual plus twice the peak.
:::
:::
:::

::: check
kind: parts
given: N = 200 | 600; i = 0.5 | 2; g = 1 | 2; A = 2 | 8

## An electromagnet: {N} turns, {i} A, two {g} mm gaps each of {A} cm².

::: part
answer: 4e-7*pi*N*i/(2*g*1e-3)
unit: T
tolerance: 0.5%

### Gap flux density?

::: misses
- [any] $\mu_0Ni/(2g)$.
:::
:::

::: part
answer: 4e-7*pi*N^2*A*1e-4/(2*g*1e-3)*1000
unit: mH
tolerance: 0.5%

### Inductance?

::: misses
- [any] $\mu_0N^2A/(2g)$.
:::
:::

::: part
answer: 4e-7*pi*N^2*A*1e-4*i^2/(4*(g*1e-3)^2)
unit: N
tolerance: 0.5%

### Force?

::: misses
- [any] $\frac{1}{2}i^2|dL/dg|$.
:::
:::
:::

::: check
kind: parts
given: i = 1 | 6; L = 10 | 50; t = 15 | 30 | 60

## A coil with $L(\theta) = L_0 + L_2\cos 2\theta$, $L_2$ = {L} mH, carries {i} A.

::: part
answer: i^2*L*1e-3
unit: N·m
tolerance: 0.5%

### Peak torque?

::: misses
- [any] $i^2L_2$.
:::
:::

::: part
answer: i^2*L*1e-3*sin(2*t*pi/180)
unit: N·m
tolerance: 0.5%

### Torque magnitude at θ = {t}°?

::: misses
- [any] $i^2L_2\sin 2\theta$.
:::
:::
:::

::: check
kind: parts
given: i = 0.5 | 3; a = 20 | 60; b = 2 | 4

## A plunger moves at constant {i} A and its coil's inductance grows from {a} mH to {b} times that.

::: part
answer: i^2*a*(b - 1)*1e-3
unit: J
tolerance: 0.5%

### Energy from the source?

::: misses
- [any] $i^2\Delta L$.
:::
:::

::: part
answer: 0.5*i^2*a*(b - 1)*1e-3
unit: J
tolerance: 0.5%

### Mechanical work?

::: misses
- [any] Half of it.
:::
:::
:::

::: check
kind: parts
given: B = 0.5 | 1.2 | 1.8; A = 5 | 50; P = 0.4 | 2; t = 0.5 | 0.35; T = 0.27 | 0.18; f = 50 | 60; F = 400 | 800

## A field of {B} T over {A} cm² of pole face; a lamination of {t} mm with {P} W/kg of eddy loss at {f} Hz.

::: part
answer: B^2*A*1e-4/(2*4e-7*pi)
unit: N
tolerance: 0.5%

### Force on the pole face?

::: misses
- [any] $B^2A/2\mu_0$.
:::
:::

::: part
answer: P*(F/f)^2*(T/t)^2
unit: W/kg
tolerance: 0.5%

### Eddy loss with {T} mm laminations at {F} Hz?

::: misses
- [any] $\propto f^2t^2$.
:::
:::
:::

::: check
kind: parts
given: G = 0.4 | 0.8; A = 10 | 40; g = 0.5 | 1.5; B = 1.2 | 1.4

## A gap {g} mm × {A} cm² needs {G} T from NdFeB with $B_r$ = {B} T, $\mu_r$ = 1.05.

::: part
answer: B^2/(4*4e-7*pi*1.05)/1000
unit: kJ/m³
tolerance: 0.5%

### Maximum energy product?

::: misses
- [any] $B_r^2/(4\mu_0\mu_r)$.
:::
:::

::: part
answer: G^2*A*1e-4*g*1e-3/(4e-7*pi*B^2/(4*4e-7*pi*1.05))*1e6
unit: cm³
tolerance: 0.5%

### Least magnet volume?

::: misses
- [any] $B_g^2V_g/(\mu_0(BH)_\text{max})$.
:::
:::
:::

::: check
kind: parts
given: M = 0.3 | 0.8; I = 6 | 15; b = 3 | 8; d = 30 | 60 | 90

## A single-phase stator carries {I} A peak of AC; the rotor, with {b} A DC and a mutual inductance of peak {M} H, turns synchronously {d}° behind the current's phase.

::: part
answer: 0.5*M*I*b*sin(d*pi/180)
unit: N·m
tolerance: 0.5%

### What average torque does it make?

::: misses
- [M*I*b*sin(d*pi/180)] Only the forward-rotating half of the alternating field keeps pace.
- [any] $\frac12MIi_2\sin\theta_0$.
:::
:::
:::

::: check
kind: parts
given: V = 100 | 250; R = 0.05 | 0.2; k = 1.05 | 1.1 | 1.2

## A linear machine on {V} V with {R} Ω of resistance is pushed at {k} times its no-load speed.

::: part
answer: (k - 1)*V/R
unit: A
tolerance: 0.5%

### What current flows into the battery?

::: misses
- [any] $(e - V_B)/R$ with $e = kV_B$.
:::
:::

::: part
answer: 100/k
unit: %
tolerance: 0.5%

### What fraction of the pushing power reaches the battery?

::: misses
- [any] $V_Bi/(ei) = 1/k$.
:::
:::
:::

::: check
kind: parts
given: S = 25 | 100 | 500; c = 0.2 | 0.35; u = 0.8 | 1.4; p = 0.8 | 1

## A {S} kVA transformer has core loss {c}% and full-load copper loss {u}% of its rating, at power factor {p}.

::: part
answer: sqrt(c/u)*S*p/(sqrt(c/u)*S*p + 2*c/100*S)*100
unit: %
tolerance: 0.5%

### What is its maximum efficiency?

::: misses
- [any] At $x = \sqrt{P_c/P_{cu}}$, where the losses are equal.
:::
:::
:::
:::