S12 · Problem set 11
Problem set 11: design problems for transformers, magnets and electromagnets, synchronous generators and condensers on a grid, induction motors from their tests and curves, induction generators and machine sizing
Each problem starts from a specification or a test report and asks for the choice an engineer would make: which transformer, how much magnet, how much field current, how much rotor resistance, how much capacitance. They draw on the whole course, mostly on the first two thirds. Write down the requirement before reaching for a formula.
Check
A 50 kVA transformer with core loss 0.2% and full-load copper loss 1.4% of its rating runs 12 hours a day at full load and the rest at 0.15 of full load, all at power factor 0.85.
(a)
What is its all-day efficiency?
(b)
At what load fraction would it be most efficient?
Check
A 1.5 mm × 20 cm² gap needs 0.4 T from an NdFeB magnet with = 1.1 T and = 1.05, operated at its maximum energy product.
(a)
What is that energy product?
Write units the way you normally would: 1.5 kJ/m^3, 1500 J/m^3 and 0.0015 MJ/m^3 are the same answer.
(b)
What magnet volume does it need?
Check
An electromagnet must hold 20 kg with a safety factor of 2, across two poles of 4 cm² each and 0.8 mm of air at each.
(a)
What gap flux density does it need?
Write units the way you normally would: 1.5 T, 1500 mT and 0.0015 kT are the same answer.
(b)
How many ampere-turns?
Check
A generator ( = 1.1 pu, saturated) needs 5 A of field for rated voltage on its modified air-gap line, and delivers rated current at 0.8 power factor lagging.
(a)
Approximately what field current does it need?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What fraction of its pull-out power is it then delivering?
Check
A synchronous condenser rated 100 MVA ( = 1.3 pu) on a 1 pu bus must supply 0.3 pu of reactive power.
(a)
What excitation does it need?
(b)
How much is that in megavars?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A 60 Hz generator ( = 1.3, = 1 pu, H = 3 s) delivers 0.7 of its pull-out power to a 1 pu bus through 0.5 pu of external reactance.
(a)
How much power does it deliver, in per unit?
(b)
At what frequency does it swing?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A Y-connected 60 Hz motor's DC test gives = 0.15 Ω. Its blocked-rotor test at 15 Hz takes 20 A at 8 V per phase and 336 W.
(a)
What is ?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
What is at 60 Hz?
Check
A 4-pole, 60 Hz motor's Thévenin circuit is 260 V behind 0.1 Ω with 0.8 Ω of total leakage; its rotor resistance is 0.15 Ω.
(a)
What external rotor resistance (referred) gives breakdown torque at standstill?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
What starting torque does that give?
Check
An induction motor on 230 V (line, Y) has = 0.1, = 0.8 and = 0.3 Ω, at slip 0.02. Use the approximate circuit with the magnetizing branch at the terminals.
(a)
What rotor current flows?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What air-gap power?
Check
An induction generator with = 25 Ω per phase is to self-excite on 50 Hz.
(a)
What capacitance per phase, in Y?
Write units the way you normally would: 1.5 µF, 1500 nF and 0.0015 mF are the same answer.
(b)
And in Δ?
Check
A 55 kW, 2-pole, 60 Hz induction motor (about 3% slip) is sized for a 30 kPa shear stress and a length-to-diameter ratio of 1.
(a)
What torque must it make?
Write units the way you normally would: 1.5 N·m, 1500 mN·m and 0.0015 kN·m are the same answer.
(b)
What rotor diameter?
Check
A motor rated 50 A (locked-rotor current 7.5 times rated) sees line voltages of 455, 468 and 450 V.
(a)
What is the true voltage unbalance?
(b)
About how much negative-sequence current does it draw?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A doubly fed wind generator rated 3.6 MW at the grid must cover a speed range of ±0.25.
(a)
What must its converter carry at top speed and full output?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A salient-pole generator ( = 0.9, = 0.55 pu) delivers rated current at power factor 0.9 lagging to a 1 pu bus.
(a)
What excitation does it need?
(b)
At what load angle?
Check
A plant draws 500 kW at 0.7 power factor lagging. A synchronous motor that will drive a new 400 kW load is to be overexcited so that the plant's total power factor becomes 1.
(a)
How much reactive power must the motor supply?
Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.
(b)
What apparent power must the motor be rated for?
(c)
At what leading power factor does it run?
Have paper and a calculator ready. Work each problem out by hand, then enter the answer. Your first try on each one counts toward your score.