title: Starting, rotor design and induction generators
heading: Inrush current at start and ways to reduce it (wye-delta, autotransformer, soft starter), deep-bar and double-cage rotors that use skin effect to raise starting torque, the NEMA design classes, and the induction machine driven above synchronous speed as a generator
eyebrow: S12 · Lesson 25 · Starting, rotor design and induction generators
xp: 50
---

::: hook
Switched straight onto the line, an induction motor draws six or seven times its rated current until it gets up to speed, dimming lights and tripping breakers on a weak supply. Starters trade that current against starting torque. The rotor designer has a cleverer trick: shape the rotor bars so that at standstill, when the rotor current alternates at line frequency, skin effect pushes the current into a thin layer and raises the resistance, then lets it spread out once the motor is running. And drive the same machine faster than its field, and it becomes a generator.
:::

::: play
- Starting with a soft starter: the 460 V motor's torque–speed curve at a reduced voltage fraction v, against a fan load whose torque rises with the square of speed.
- Torque scales as v² and current as v. The motor accelerates wherever its curve is above the load's; the crossing is the running point.
- Too low a voltage leaves the motor stuck at a high slip, overheating its rotor.
:::

```sim plot
view: graph
x: n = 0..1800 rpm
y: T = 0..500 N·m
slider: v = 0.3..1 step 0.01 = 0.6
slider: k = 50..200 step 5 = 130 N·m
plot: 3*(259.09*v)^2*(0.15*1800/(1800 - n))/(188.496*((0.19034 + 0.15*1800/(1800 - n))^2 + (0.98966)^2)) | samples: 800 | label: motor
plot: k*(n/1800)^2 | color: ch3 | label: fan load
readout: starting current vs full voltage = v | digits: 3
readout: starting torque, N·m = 3*(259.09*v)^2*0.15/(188.496*((0.19034 + 0.15)^2 + 0.98966^2)) | digits: 4
readout: breakdown torque, N·m = 1.5*(259.09*v)^2/(188.496*(0.19034 + sqrt(0.19034^2 + 0.98966^2))) | digits: 4
```

::: predict
## A motor draws 6 times rated current starting directly on the line, with 1.5 times rated torque. Started in wye on a winding meant for delta, what line current and torque does it start with?

- [ ] 6 times and 1.5 times
- [ ] 3.5 times and 0.87 times
- [x] 2 times and 0.5 times
- [ ] 6 times and 0.5 times

::: reveal
In wye each phase winding gets $1/\sqrt{3}$ of its delta voltage, so its current falls by √3; and a wye line current equals the phase current, while a delta line current is √3 times it. Together the line current falls by 3, to 2 times rated. Torque goes as the square of the winding voltage, also 1/3: 0.5 times rated, enough for a fan or pump but not for a loaded conveyor.
:::
:::

::: nameit
## Reduced-voltage starting

Starting current is roughly proportional to the motor's voltage, and torque to its square.

- **Wye–delta:** a delta-rated winding started in wye: line current and torque both fall to 1/3.
- **Autotransformer** at tap a: the motor current falls to a times, the line current to $a^2$ times (the transformer steps it down again), and torque to $a^2$ times.
- **Soft starter** (thyristors trimming the voltage to v): motor and line current v times, torque $v^2$ times.
- A variable-frequency drive (lesson 27) avoids the trade by starting at low frequency.

## Rotor design

At standstill the rotor current alternates at line frequency, and in a deep bar its skin depth $\delta = \sqrt{2\rho/\omega\mu_0}$, about 11 mm in cast aluminum at 60 Hz, confines the current to the top of the bar: high resistance, high starting torque, lower starting current. At a running slip frequency of 1 or 2 Hz the depth is several times the bar and the current uses the whole bar: low resistance, high efficiency. Double-cage rotors do the same with a high-resistance outer cage and a low-resistance inner one.

## NEMA design classes

- **A:** normal starting torque, high starting current, low slip.
- **B:** normal torque, lower current (deep bars); the general-purpose motor.
- **C:** high starting torque (double cage), for loaded conveyors and compressors.
- **D:** very high starting torque and high slip (high-resistance rotor), for punch presses and hoists.

## The induction generator

Driven above synchronous speed, s is negative, $R_2/s$ is negative, and power flows from the shaft to the line. The machine still needs reactive power for its magnetizing current, from the grid or from capacitors. A capacitor bank alone can self-excite it if $C \ge 1/(\omega X_m)$ per phase, with the voltage settling where the magnetizing curve saturates.
:::

::: example
## A motor starts at 6 times rated current and 1.5 times rated torque. Compare an autotransformer starter on its 65% tap.

::: solution
1. **Motor current.** The motor sees 65% voltage, so its current is $0.65 \times 6 = 3.9$ times rated.
2. **Line current.** Stepped down by the transformer again, the line current is
   $$\begin{aligned} I_\text{line} &= 0.65^2 \times 6 \\ &= 2.54 \end{aligned}$$
   times rated.
3. **Starting torque.**
   $$\begin{aligned} T &= 0.4225 \times 1.5 \\ &= 0.63 \end{aligned}$$
   times rated.
4. **Compare with wye–delta.** That's slightly more torque than wye–delta's 0.5 for slightly more line current, and the tap can be chosen to suit the load.

**Answer:** the motor draws 3.9 times rated current, the line 2.54 times, and the starting torque is 0.63 times rated.
:::
:::

::: example
## How deep does the current penetrate a cast-aluminum rotor bar (ρ = 2.8 × 10⁻⁸ Ω·m) at standstill on 60 Hz, and at 2% slip?

::: solution
1. **Depth at 60 Hz.**
   $$\begin{aligned} \delta &= \sqrt{\frac{2 \times 2.8 \times 10^{-8}}{377 \times 4\pi \times 10^{-7}}} \\ &= 10.9\ \text{mm} \end{aligned}$$
2. **Depth at 2% slip.** The rotor frequency is 1.2 Hz and δ = 76.9 mm.
3. **In a real bar.** A 30 mm deep bar carries its starting current in roughly its top third, about tripling its effective resistance, then uses its whole depth once running.

**Answer:** 10.9 mm at standstill, and 76.9 mm at 2% slip.
:::
:::

::: example
## The 460 V motor ($X_m$ = 20 Ω per phase) is to run as a self-excited induction generator on 60 Hz. How much capacitance does it need, in Y and in Δ?

::: solution
1. **Capacitance in Y.** Self-excitation needs the capacitors to supply at least the magnetizing current:
   $$\begin{aligned} C &\ge \frac{1}{\omega X_m} \\ &= \frac{1}{377 \times 20} \\ &= 133\ \mu\text{F} \end{aligned}$$
   per phase in Y.
2. **Capacitance in Δ.** Each capacitor sees √3 times the voltage, so a third of the capacitance does: 44 µF.
3. **Under load.** Loading the generator draws more reactive power than the magnetizing branch alone, so practical machines carry more capacitance, and the voltage and frequency both sag as the load rises unless a controller trims the capacitors.

**Answer:** at least 133 µF per phase in Y, or 44 µF per phase in Δ.
:::
:::

::: check
given: I = 5 | 6.5 | 8; T = 1.2 | 1.8 | 2.5
answer: I/3
tolerance: 0.5%

## Direct on line, a motor draws {I} times rated current with {T} times rated torque. Started wye–delta, what line current (times rated) does it draw?

::: right
Right. A third: {answer} times rated.
:::

::: misses
- [I/sqrt(3)] That's the phase current's reduction; the line current also loses the delta's factor of √3.
- [any] Not yet. Line current and torque both fall to 1/3.
:::
:::

::: check
given: I = 5 | 6.5 | 8; a = 0.5 | 0.65 | 0.8
answer: a^2*I
tolerance: 0.5%

## A motor that draws {I} times rated current direct on line starts through an autotransformer on its {a} tap. What line current (times rated) flows?

::: right
Right. $a^2I_\text{DOL}$ = {answer} times rated.
:::

::: misses
- [a*I] That's the motor's current; the autotransformer steps it down again on the line side.
- [any] Not yet. Motor current a times, then the transformer ratio again.
:::
:::

::: check
given: T = 1.2 | 1.8 | 2.5; v = 0.4 | 0.6 | 0.75
answer: v^2*T
tolerance: 0.5%

## A motor's direct-on-line starting torque is {T} times rated. With a soft starter at {v} of rated voltage, what's its starting torque?

::: right
Right. $v^2T$ = {answer} times rated.
:::

::: misses
- [v*T] Torque goes as the square of voltage.
- [any] Not yet. Both flux and rotor current scale with voltage.
:::
:::

::: check
given: f = 1 | 2 | 50 | 60; r = 2.8 | 1.7
answer: sqrt(2*r*1e-8/(2*pi*f*4e-7*pi))*1000
unit: mm
tolerance: 0.5%

## How deep does {f} Hz current penetrate a rotor bar of resistivity {r} × 10⁻⁸ Ω·m?

::: right
Right. $\sqrt{2\rho/\omega\mu_0}$ = {answer} mm.
:::

::: misses
- [sqrt(r*1e-8/(2*pi*f*4e-7*pi))*1000] Skin depth has a factor of 2 under the root.
- [any] Not yet. Skin depth.
:::
:::

::: check
given: f = 50 | 60; P = 4 | 6; r = 0.01 | 0.03; let n = 120*f/P*(1 + r)
answer: (120*f/P - n)/(120*f/P)
tolerance: 0.5%

## A wind turbine drives a {P}-pole, {f} Hz induction generator at {n} rpm. What's its slip?

::: right
Right. {answer}: negative, so the machine generates.
:::

::: misses
- [-(120*f/P - n)/(120*f/P)] Above synchronous speed the slip is negative.
- [any] Not yet. $(n_s - n)/n_s$.
:::
:::

::: check
given: X = 10 | 20 | 40; f = 50 | 60
answer: 1/(2*pi*f*X)*1e6
unit: µF
tolerance: 0.5%

## An induction generator's magnetizing reactance is {X} Ω per phase at {f} Hz. What capacitance per phase lets it self-excite?

::: right
Right. At least $1/(\omega X_m)$ = {answer} µF.
:::

::: misses
- [any] Not yet. The capacitor's reactance must not exceed $X_m$.
:::
:::

::: check
kind: parts
given: k = 5 | 6 | 7; t = 1.2 | 1.5 | 2; a = 0.5 | 0.65 | 0.8

## A motor starts at {k} times rated current and {t} times rated torque. It's started through an autotransformer on its {a} tap.

::: part
answer: a*k
tolerance: 0.5%

### What starting current does the motor draw, in multiples of rated?

::: misses
- [any] Proportional to its voltage.
:::
:::

::: part
answer: a^2*k
tolerance: 0.5%

### What does the line supply?

::: misses
- [a*k] The transformer steps the current down again.
- [any] $a^2$ times the direct-on-line current.
:::
:::

::: part
answer: a^2*t
tolerance: 0.5%

### What starting torque results, in multiples of rated?

::: misses
- [any] Torque goes as voltage squared.
:::
:::
:::

::: check
kind: derivation
vars: r = 0.00000001..0.0000001, s = 0.005..1, f = 50..60

## A rotor bar of resistivity r runs at slip s on an f hertz supply.

::: step
answer: s*f

### What frequency does its current have?
:::

::: step
answer: sqrt(2*r/(2*pi*s*f*4*pi*1e-7))

### What is its skin depth, in meters?
:::

::: right
Right. At standstill the current crowds into the bar's top; in running it uses the whole bar.
:::
:::

::: explain
## How does a deep-bar rotor give high starting torque and low running slip at the same time?

::: model
An induction motor wants a high rotor resistance at standstill, for more starting torque per ampere, and a low one when running, since rotor loss is s times the air-gap power. The rotor current's frequency is the slip frequency, which is the full line frequency at standstill and only a hertz or two at running speed. In a deep, narrow bar, current at line frequency crowds into a thin layer near the surface, a skin depth of about 11 mm in aluminum at 60 Hz, so only part of the bar carries it and the effective resistance is high. At running slip the skin depth is several times the bar's depth, the current spreads over the whole cross-section, and the resistance falls to its low DC value. The rotor's resistance changes automatically with speed.
:::
:::

::: practice

::: check
given: I = 4 | 9; a = 0.5 | 0.85
answer: a^2*I
tolerance: 0.5%

## Line current, autotransformer tap {a}, {I}× DOL?

::: misses
- [any] $a^2I$.
:::
:::

::: check
given: f = 0.5 | 60; r = 1.7 | 3.2
answer: sqrt(2*r*1e-8/(2*pi*f*4e-7*pi))*1000
unit: mm
tolerance: 0.5%

## Skin depth: {f} Hz, ρ = {r} × 10⁻⁸ Ω·m?

::: misses
- [any] $\sqrt{2\rho/\omega\mu_0}$.
:::
:::

::: check
given: X = 5 | 60; f = 50 | 60
answer: 1/(2*pi*f*X)*1e6
unit: µF
tolerance: 0.5%

## Self-excitation capacitance: $X_m$ = {X} Ω, {f} Hz?

::: misses
- [any] $1/(\omega X_m)$.
:::
:::
:::