title: The synchronous machine and its equivalent circuit
heading: A DC-excited rotor turning in step with the stator field, the excitation voltage set by field current, armature reaction and the synchronous reactance, the equivalent circuit and phasor diagram for generating and motoring, the load angle, and power transfer
eyebrow: S12 · Lesson 10 · The synchronous machine and its equivalent circuit
xp: 50
---

::: hook
Nearly every large generator in the world is a synchronous machine: a rotor carrying DC field current (or magnets), turned by a turbine at exactly the speed of the stator's rotating field. Its armature current sets up a field of its own that adds to the rotor's, and that reaction shows up in the equivalent circuit as a single, large reactance. With it, a machine that weighs hundreds of tons reduces to a voltage source behind a reactance, the same model S10 used for the grid.
:::

::: play
- The phasor diagram of a synchronous generator: terminal voltage V (on the real axis), armature current I at power factor angle φ, the drop $jX_sI$ across the synchronous reactance, and the excitation voltage $E_f = V + jX_sI$ (resistance neglected), all in per unit.
- Lagging current (positive φ) needs a much larger $E_f$, so more field current; leading current needs less.
- The angle δ between $E_f$ and V is the load angle; the real power is $VE_f\sin\delta/X_s$.
:::

```sim plot
view: complex
range: 2
axes: real, imaginary
slider: i = 0..1.2 step 0.05 = 1
slider: p = -60..60 step 1 = 26 °
slider: x = 0.3..1.5 step 0.05 = 0.84
arrow: 1 | label: V
arrow: i*exp(-j*p*pi/180) | color: ch2 | label: I
arrow: j*x*i*exp(-j*p*pi/180) | from: 1 | color: ch3 | label: jXsI
arrow: 1 + j*x*i*exp(-j*p*pi/180) | color: ch4 | label: Ef
readout: Ef, pu = sqrt((1 + x*i*sin(p*pi/180))^2 + (x*i*cos(p*pi/180))^2) | digits: 3
readout: load angle, ° = atan(x*i*cos(p*pi/180)/(1 + x*i*sin(p*pi/180)))*180/pi | digits: 3
readout: real power, pu = i*cos(p*pi/180) | digits: 3
```

::: predict
## A generator with 0.84 pu synchronous reactance delivers rated current at 0.9 power factor lagging. What excitation voltage does it need?

- [ ] 1.0 pu
- [ ] 1.2 pu
- [x] About 1.56 pu
- [ ] About 1.84 pu

::: reveal
$E_f = V + jX_sI$ = 1 + j0.84(0.9 − j0.436) = 1.366 + j0.756, which has magnitude 1.56 at δ = 29°. The reactance drop is nearly perpendicular to the current, so with lagging current it adds almost directly to V: a generator supplying reactive power needs a lot of field current.
:::
:::

::: nameit
## Excitation voltage

The rotor's DC field current $I_f$ produces a rotating flux that induces in each phase the **excitation voltage** (or internal voltage) $E_f = \omega L_{af}I_f/\sqrt{2}$, proportional to field current and speed.

## Synchronous reactance

The armature current's own rotating field induces a further voltage in the armature, proportional to the current and 90° behind it: a reactance $X_\varphi$ (armature reaction), plus the leakage reactance $X_{al}$. Together $X_s = X_{al} + X_\varphi$, typically 1 to 2 pu in large machines.

## The equivalent circuit

Per phase, with armature resistance $R_a$ (often neglected):

$$\text{generator: } \hat{E}_f = \hat{V} + \hat{I}(R_a + jX_s), \qquad \text{motor: } \hat{V} = \hat{E}_f + \hat{I}(R_a + jX_s)$$

## Load angle and power

The angle δ by which $E_f$ leads V (positive for a generator, negative for a motor) measures how far the rotor is ahead of the resultant field. With $R_a$ neglected, three-phase power is

$$P = \frac{3VE_f}{X_s}\sin\delta$$

with a maximum of $3VE_f/X_s$ at 90°: the **pull-out** power.
:::

::: example
## A 50 MVA, 13.8 kV, Y-connected generator has $X_s$ = 3.2 Ω per phase. Find $E_f$ and δ at rated load, 0.9 power factor lagging.

::: solution
1. **Phase voltage and current.**
   $$\begin{aligned} V &= \frac{13.8\ \text{kV}}{\sqrt3} \\ &= 7967\ \text{V} \\ I &= \frac{50\ \text{MVA}}{3 \times 7967\ \text{V}} \\ &= 2092\ \text{A} \end{aligned}$$
   at −25.8°.
2. **Reactance drop.** $jX_sI$ = 6694 V at 64.2°.
3. **Excitation voltage.**
   $$\begin{aligned} \hat E_f &= 7967 + 2918 + j6025 \\ &= 12\,441\ \text{V} \end{aligned}$$
   at δ = 29.0°.
4. **In per unit.** That's 1.56 pu, with $X_s$ = 3.2/3.809 = 0.84 pu.
5. **Check.**
   $$\begin{aligned} P &= \frac{3VE_f\sin\delta}{X_s} \\ &= 45.0\ \text{MW} \end{aligned}$$
   which is 50 MVA × 0.9. The pull-out power at this excitation is 92.9 MW.

**Answer:** $E_f$ = 12,441 V per phase (1.56 pu) at δ = 29.0°.
:::
:::

::: example
## A 460 V synchronous motor with $X_s$ = 2.5 Ω takes 15 kW at unity power factor. Find its excitation voltage and load angle.

::: solution
1. **Phase voltage and current.** V = 265.6 V per phase, and
   $$\begin{aligned} I &= \frac{15\,000}{3 \times 265.6} \\ &= 18.83\ \text{A} \end{aligned}$$
   in phase with it.
2. **Excitation voltage.**
   $$\begin{aligned} \hat E_f &= V - jX_sI \\ &= 265.6 - j47.1 \end{aligned}$$
3. **Magnitude and angle.** $E_f$ = 269.7 V at δ = −10.0°: the rotor lags the resultant field, pulled along by it.

**Answer:** $E_f$ = 269.7 V per phase, at a load angle of −10.0°.
:::
:::

::: example
## Run the 50 MVA, 13.8 kV generator ($X_s$ = 3.2 Ω) at rated current and unity power factor instead. How do its excitation and load angle change?

::: solution
1. **The reactance drop.** The current, 2092 A, is now in phase with the 7967 V phase voltage, so $jX_sI$ = j6694 V adds at right angles.
2. **Excitation voltage.**
   $$\begin{aligned} E_f &= \sqrt{7967^2 + 6694^2} \\ &= 10\,406\ \text{V} \end{aligned}$$
   at δ = 40.0°.
3. **Compare with 0.9 lagging.** Delivering 50 MW instead of 45 MW, the machine needs less field current (1.31 pu against 1.56 pu) but runs 11° closer to pull-out, because it no longer supplies reactive power.
4. **Why ratings are lagging.** Generators are usually rated at 0.85 or 0.9 lagging so that they can supply vars at full load.

**Answer:** $E_f$ falls to 10,406 V (1.31 pu, down from 1.56 pu) and δ rises to 40.0° (from 29.0°).
:::
:::

::: check
given: x = 0.6 | 1 | 1.6; i = 0.5 | 1; p = 0.8 | 0.9 | 0.95
answer: sqrt((1 + x*i*sqrt(1 - p^2))^2 + (x*i*p)^2)
tolerance: 0.5%

## A generator with $X_s$ = {x} pu delivers {i} pu current at power factor {p} lagging, at 1 pu terminal voltage. What's $E_f$?

::: right
Right. $|V + jX_sI|$ = {answer} pu.
:::

::: misses
- [1 + x*i] The reactance drop isn't in phase with V unless the power factor is zero.
- [any] Not yet. $E_f = V + jX_sI$ with I lagging V by φ.
:::
:::

::: check
given: x = 0.6 | 1 | 1.6; i = 0.5 | 1; p = 0.8 | 0.9 | 0.95
answer: atan(x*i*p/(1 + x*i*sqrt(1 - p^2)))*180/pi
unit: °
tolerance: 0.5%

## For the same generator ($X_s$ = {x} pu, {i} pu current at power factor {p} lagging), what's the load angle?

::: right
Right. δ = {answer}°.
:::

::: misses
- [any] Not yet. The angle of $E_f = V + jX_sI$.
:::
:::

::: check
given: V = 2400 | 7967; E = 1.2 | 1.6; X = 2 | 5; d = 15 | 30 | 45
answer: 3*V*E*V*sin(d*pi/180)/X/1e6
unit: MW
tolerance: 0.5%

## A generator's phase voltage is {V} V and its excitation voltage {E} times that, with $X_s$ = {X} Ω, at δ = {d}°. What three-phase power does it deliver?

::: right
Right. $3VE_f\sin\delta/X_s$ = {answer} MW.
:::

::: misses
- [V*E*V*sin(d*pi/180)/X/1e6] That's one phase; there are three.
- [any] Not yet. Power-angle equation.
:::
:::

::: check
given: V = 230 | 460 | 4160; P = 10 | 75 | 500; X = 1 | 3 | 8
answer: sqrt((V/sqrt(3))^2 + (X*P*1000/(sqrt(3)*V))^2)
unit: V
tolerance: 0.5%

## A synchronous motor on {V} V (line to line) with $X_s$ = {X} Ω per phase takes {P} kW at unity power factor. What's its excitation voltage per phase?

::: right
Right. $|V - jX_sI|$ = {answer} V.
:::

::: misses
- [any] Not yet. At unity power factor the drop $X_sI$ is perpendicular to V.
:::
:::

::: check
given: x = 0.8 | 1.2 | 1.8; V = 4.16 | 13.8 | 24; S = 10 | 100 | 800
answer: x*V^2/S
unit: Ω
tolerance: 0.5%

## A {S} MVA, {V} kV, Y-connected generator has $X_s$ = {x} pu. How many ohms per phase is that?

::: right
Right. $Z_b = V_{LL}^2/S$, so $X_s$ = {answer} Ω.
:::

::: misses
- [x*V^2/S/3] With line-to-line voltage and three-phase power, $V_{LL}^2/S_{3\phi}$ is already the per-phase base.
- [any] Not yet. Multiply by the base impedance.
:::
:::

::: check
given: V = 2400 | 7967; E = 1.1 | 1.5; X = 2 | 6
answer: 3*V*E*V/X/1e6
unit: MW
tolerance: 0.5%

## What's the pull-out power of a generator with {V} V per phase, $E_f$ = {E} times that, and $X_s$ = {X} Ω?

::: right
Right. $3VE_f/X_s$ = {answer} MW, at δ = 90°.
:::

::: misses
- [any] Not yet. The power-angle curve's peak.
:::
:::

::: check
kind: parts
given: X = 0.8 | 1.2 | 1.8; p = 0.8 | 0.85 | 0.9

## A generator with a synchronous reactance of {X} per unit delivers rated current at rated voltage and power factor {p} lagging.

::: part
answer: sqrt((1 + X*sqrt(1 - p^2))^2 + (X*p)^2)
tolerance: 0.5%

### What is its excitation voltage, in per unit?

::: misses
- [sqrt(1 + X^2)] That's at unity power factor.
- [any] $|1 + jX\hat I|$ with $\hat I = p - j\sqrt{1 - p^2}$.
:::
:::

::: part
answer: atan(X*p/(1 + X*sqrt(1 - p^2)))*180/pi
unit: °
tolerance: 0.5%

### What is its load angle?

::: misses
- [any] The angle of $E_f$.
:::
:::
:::

::: check
kind: derivation
vars: V = 100..20000, E = 100..30000, X = 0.1..20, d = 1..85

## A synchronous machine with phase voltage V, excitation voltage E and synchronous reactance X runs at load angle d degrees.

::: step
answer: 3*V*E*sin(d*pi/180)/X

### What three-phase real power does it deliver?
:::

::: step
answer: 3*(V*E*cos(d*pi/180) - V^2)/X

### What reactive power does it deliver?
:::

::: step
answer: 3*V*E/X

### What is its pull-out power?
:::

::: right
Right. Excitation sets the reactive power; the load angle sets the real power.
:::
:::

::: explain
## Why must a generator's field current rise when it supplies more reactive power at the same real power?

::: model
With the terminal voltage held by the grid, the excitation voltage is $E_f = V + jX_sI$. The real-power part of the current, in phase with V, produces a reactance drop perpendicular to V, which mostly rotates $E_f$ forward and opens the load angle. The reactive part of a lagging current lags V by 90°, so its drop $jX_sI$ points along V and adds directly to its length. Supplying more lagging reactive power therefore needs a longer $E_f$, and since $E_f$ is proportional to field current, more field current. Underexcited, with $E_f$ smaller than V, the same machine absorbs reactive power instead.
:::
:::

::: practice

::: check
given: x = 0.8 | 1.8; i = 0.3 | 1.1; p = 0.75 | 0.98
answer: sqrt((1 + x*i*sqrt(1 - p^2))^2 + (x*i*p)^2)
tolerance: 0.5%

## $E_f$: $X_s$ = {x} pu, {i} pu at pf {p} lagging?

::: misses
- [any] $|V + jX_sI|$.
:::
:::

::: check
given: V = 1000 | 5000; E = 1.05 | 1.8; X = 1.5 | 9; d = 10 | 60
answer: 3*V*E*V*sin(d*pi/180)/X/1e6
unit: MW
tolerance: 0.5%

## Power: {V} V per phase, $E_f$ = {E} × V, {X} Ω, δ = {d}°?

::: misses
- [any] $3VE_f\sin\delta/X_s$.
:::
:::

::: check
given: x = 0.7 | 2; V = 0.48 | 22; S = 0.5 | 600
answer: x*V^2/S
unit: Ω
tolerance: 0.5%

## Ohms per phase: {x} pu, {V} kV, {S} MVA?

::: misses
- [any] $xV_{LL}^2/S$.
:::
:::
:::