S12 · Lesson 15 · Open-circuit and short-circuit tests
Measuring a synchronous machine's open-circuit characteristic and air-gap line, its short-circuit characteristic, the unsaturated and saturated synchronous reactances, the short-circuit ratio, and the losses and effective resistance the same tests reveal
The synchronous reactance can't be measured with an ohmmeter: it exists only when the machine turns and its own current sets up a field. Two tests on the running machine supply it. Spin it open-circuited and record terminal voltage against field current; then short its terminals and record current against field current. The ratio of the two curves at the same field current is the reactance, and because the iron saturates, the answer depends on where you read it.
- A 100 kVA, 480 V synchronous machine's open-circuit characteristic (terminal voltage, line to line, against field current), its air-gap line (the unsaturated slope continued), and its short-circuit characteristic (armature current against field current; same axis, in amperes).
- Rated voltage needs 3.2 A of field current on the saturating curve but would need only 2.64 A if the iron didn't saturate.
- The ratio of open-circuit phase voltage to short-circuit current at the same field current is the synchronous reactance; drag the field current to see it fall as saturation sets in.
Predict
On the short-circuit test, why does the armature current rise in a straight line with field current, even though the open-circuit voltage curve bends over?
With the terminals shorted, the internal voltage only has to drive current through the synchronous reactance. The armature current lags by nearly 90° and its reaction directly opposes the rotor's field, leaving a small net air-gap flux, enough to cover the leakage reactance drop. The iron stays unsaturated and the curve is a straight line.
Name it
The open-circuit test
Drive the machine at synchronous speed with the armature open and record terminal voltage against field current: the open-circuit characteristic (OCC). It is straight at first, along the air-gap line, then bends as the iron saturates. The input power, less field loss, is the rotational loss (friction, windage and core loss).
The short-circuit test
Short the three terminals and record armature current against field current: the short-circuit characteristic (SCC), a straight line. The input power above the rotational loss is the short-circuit load loss, giving an effective armature resistance (larger than the DC value because of eddy currents and skin effect).
The reactances
At any field current, .
- Unsaturated: use the air-gap line voltage. This value is constant.
- Saturated: use the OCC at the field current that gives rated voltage. This approximates the machine's behavior near rated voltage.
The short-circuit ratio
A high SCR means a smaller reactance, a stiffer machine with a larger steady-state power limit, and a bigger, costlier one.
Worked example
The 100 kVA, 480 V, Y-connected machine: rated voltage at = 3.2 A on the OCC; the air-gap line gives 400 V at 2.2 A; the SCC gives rated current, 120.3 A, at 2.5 A. Find the reactances and the SCR.
Show the solution
- SCC slope. The SCC gives 48.11 A per field ampere.
- Unsaturated reactance. At 2.2 A the air-gap line gives 400/√3 = 230.9 V and the SCC 105.8 A, so
- In per unit. The base impedance is so is 0.947 pu.
- Saturated reactance. At 3.2 A, 277.1 V and 154.0 A give which is 0.781 pu.
- Short-circuit ratio. which is 1/0.781.
Answer the unsaturated reactance is 2.18 Ω (0.947 pu), the saturated one 1.80 Ω (0.781 pu), and the SCR is 1.28.
Worked example
On the short-circuit test at rated current the machine takes 1.8 kW more than its rotational loss. Find its effective resistance.
Show the solution
- Effective resistance. per phase, 0.018 pu.
- Compare with the reactance. Against a reactance of 0.78 pu it's small, which is why the resistance is often neglected in the phasor diagram, though it still matters for efficiency.
Answer 0.0415 Ω per phase, or 0.018 pu.
Worked example
Estimate the field current the 100 kVA machine needs at rated load, 0.8 power factor lagging, using its saturated reactance of 0.781 pu.
Show the solution
- Excitation voltage in per unit. so = 1.596 pu.
- Treat the machine as linear. With the saturated reactance, the machine is treated as linear along a line from the origin through the rated-voltage point of the OCC, where 1 pu takes 3.2 A of field.
- Field current.
- How good the estimate is. The true OCC bends further at 1.6 pu, so the real requirement is somewhat higher, and careful designs use the Potier or two-reaction methods.
Answer about 5.1 A of field current, and in practice somewhat more.
Check
A machine's air-gap line reaches 480 V (line to line) at 2.2 A of field current, and its short-circuit current rises 30 A per field ampere. What's its unsaturated synchronous reactance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A machine reaches rated voltage, 4160 V, at 2.5 A of field current on its OCC. Its SCC rises 400 A per field ampere. What's its saturated synchronous reactance?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A generator needs 1.5 A of field current for rated voltage on open circuit and 2.5 A for rated current on short circuit. What's its short-circuit ratio?
Check
A generator's short-circuit ratio is 0.8. What's its saturated synchronous reactance in per unit?
Check
On the short-circuit test at 50 A the machine takes 1.8 kW above its rotational loss. What's its effective armature resistance per phase?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
What's the rated armature current of a 100 kVA, 220 V three-phase machine?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 200 kVA, 480 V, Y-connected machine reaches rated voltage on its OCC at 4 A of field current, and rated current on its SCC at 3.2 A.
(a)
What is its short-circuit ratio?
(b)
What is its saturated synchronous reactance per phase?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A machine with rated phase voltage V and rated current I reaches rated voltage on its OCC at field current a, and rated current on its SCC at field current b.
Step 1
What short-circuit current flows at field current a?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is its saturated synchronous reactance?
Explain why
Why is the saturated synchronous reactance smaller than the unsaturated one?
The synchronous reactance is mostly armature reaction: the voltage the armature current's own field induces back in the armature. That field, like the rotor's, runs through the iron. Near rated voltage the iron is partly saturated, so an increment of armature MMF produces less flux than it would in unsaturated iron, and the reaction voltage per ampere is smaller. The short-circuit test can't see this, since the iron is unsaturated during it; reading the open-circuit curve at rated voltage instead of the air-gap line folds the saturation into the ratio and gives a reactance closer to the machine's behavior at its operating point.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.