title: Open-circuit and short-circuit tests
heading: Measuring a synchronous machine's open-circuit characteristic and air-gap line, its short-circuit characteristic, the unsaturated and saturated synchronous reactances, the short-circuit ratio, and the losses and effective resistance the same tests reveal
eyebrow: S12 · Lesson 15 · Open-circuit and short-circuit tests
xp: 50
---

::: hook
The synchronous reactance can't be measured with an ohmmeter: it exists only when the machine turns and its own current sets up a field. Two tests on the running machine supply it. Spin it open-circuited and record terminal voltage against field current; then short its terminals and record current against field current. The ratio of the two curves at the same field current is the reactance, and because the iron saturates, the answer depends on where you read it.
:::

::: play
- A 100 kVA, 480 V synchronous machine's open-circuit characteristic (terminal voltage, line to line, against field current), its air-gap line (the unsaturated slope continued), and its short-circuit characteristic (armature current against field current; same axis, in amperes).
- Rated voltage needs 3.2 A of field current on the saturating curve but would need only 2.64 A if the iron didn't saturate.
- The ratio of open-circuit phase voltage to short-circuit current at the same field current is the synchronous reactance; drag the field current to see it fall as saturation sets in.
:::

```sim plot
view: graph
x: f = 0..5 A
y: v = 0..700
slider: i = 0.5..5 step 0.05 = 3.2 A
plot: 714*tanh(0.25465*f) | samples: 300 | label: open-circuit voltage, V
plot: 181.82*f | dashed | color: ch3 | label: air-gap line, V
plot: 48.113*f | color: ch4 | label: short-circuit current, A
marker: x = i
readout: synchronous reactance at this field current, Ω = 714*tanh(0.25465*i)/sqrt(3)/(48.113*i) | digits: 4
readout: in per unit = 714*tanh(0.25465*i)/sqrt(3)/(48.113*i)/2.304 | digits: 3
```

::: predict
## On the short-circuit test, why does the armature current rise in a straight line with field current, even though the open-circuit voltage curve bends over?

- [ ] The test is run at low speed
- [x] With the terminals shorted, armature reaction cancels most of the field, so the iron runs far from saturation
- [ ] Short-circuit current doesn't depend on flux
- [ ] The resistance dominates

::: reveal
With the terminals shorted, the internal voltage only has to drive current through the synchronous reactance. The armature current lags by nearly 90° and its reaction directly opposes the rotor's field, leaving a small net air-gap flux, enough to cover the leakage reactance drop. The iron stays unsaturated and the curve is a straight line.
:::
:::

::: nameit
## The open-circuit test

Drive the machine at synchronous speed with the armature open and record terminal voltage against field current: the **open-circuit characteristic** (OCC). It is straight at first, along the **air-gap line**, then bends as the iron saturates. The input power, less field loss, is the **rotational loss** (friction, windage and core loss).

## The short-circuit test

Short the three terminals and record armature current against field current: the **short-circuit characteristic** (SCC), a straight line. The input power above the rotational loss is the **short-circuit load loss**, giving an effective armature resistance $R_{a,\text{eff}} = P_\text{sc}/(3I^2)$ (larger than the DC value because of eddy currents and skin effect).

## The reactances

At any field current, $X_s = V_\text{oc,phase}/I_\text{sc}$.

- **Unsaturated:** use the air-gap line voltage. This value is constant.
- **Saturated:** use the OCC at the field current that gives rated voltage. This approximates the machine's behavior near rated voltage.

## The short-circuit ratio

$$\text{SCR} = \frac{I_f\text{ for rated voltage on the OCC}}{I_f\text{ for rated current on the SCC}} = \frac{1}{X_{s,\text{sat}}\text{ (pu)}}$$

A high SCR means a smaller reactance, a stiffer machine with a larger steady-state power limit, and a bigger, costlier one.
:::

::: example
## The 100 kVA, 480 V, Y-connected machine: rated voltage at $I_f$ = 3.2 A on the OCC; the air-gap line gives 400 V at 2.2 A; the SCC gives rated current, 120.3 A, at 2.5 A. Find the reactances and the SCR.

::: solution
1. **SCC slope.** The SCC gives 48.11 A per field ampere.
2. **Unsaturated reactance.** At 2.2 A the air-gap line gives 400/√3 = 230.9 V and the SCC 105.8 A, so
   $$\begin{aligned} X_{s,u} &= \frac{230.9}{105.8} \\ &= 2.18\ \Omega \end{aligned}$$
3. **In per unit.** The base impedance is
   $$\begin{aligned} Z_b &= \frac{480^2}{100\,000} \\ &= 2.304\ \Omega \end{aligned}$$
   so $X_{s,u}$ is 0.947 pu.
4. **Saturated reactance.** At 3.2 A, 277.1 V and 154.0 A give
   $$\begin{aligned} X_s &= \frac{277.1}{154.0} \\ &= 1.80\ \Omega \end{aligned}$$
   which is 0.781 pu.
5. **Short-circuit ratio.**
   $$\begin{aligned} \text{SCR} &= \frac{3.2}{2.5} \\ &= 1.28 \end{aligned}$$
   which is 1/0.781.

**Answer:** the unsaturated reactance is 2.18 Ω (0.947 pu), the saturated one 1.80 Ω (0.781 pu), and the SCR is 1.28.
:::
:::

::: example
## On the short-circuit test at rated current the machine takes 1.8 kW more than its rotational loss. Find its effective resistance.

::: solution
1. **Effective resistance.**
   $$\begin{aligned} R_{a,\text{eff}} &= \frac{1800}{3 \times 120.3^2} \\ &= 0.0415\ \Omega \end{aligned}$$
   per phase, 0.018 pu.
2. **Compare with the reactance.** Against a reactance of 0.78 pu it's small, which is why the resistance is often neglected in the phasor diagram, though it still matters for efficiency.

**Answer:** 0.0415 Ω per phase, or 0.018 pu.
:::
:::

::: example
## Estimate the field current the 100 kVA machine needs at rated load, 0.8 power factor lagging, using its saturated reactance of 0.781 pu.

::: solution
1. **Excitation voltage in per unit.**
   $$\begin{aligned} \hat E_f &= 1 + j0.781(0.8 - j0.6) \\ &= 1.469 + j0.625 \end{aligned}$$
   so $E_f$ = 1.596 pu.
2. **Treat the machine as linear.** With the saturated reactance, the machine is treated as linear along a line from the origin through the rated-voltage point of the OCC, where 1 pu takes 3.2 A of field.
3. **Field current.**
   $$\begin{aligned} I_f &\approx 1.596 \times 3.2 \\ &= 5.1\ \text{A} \end{aligned}$$
4. **How good the estimate is.** The true OCC bends further at 1.6 pu, so the real requirement is somewhat higher, and careful designs use the Potier or two-reaction methods.

**Answer:** about 5.1 A of field current, and in practice somewhat more.
:::
:::

::: check
given: V = 380 | 480 | 4160; s = 30 | 60 | 120; b = 1.5 | 2.2
answer: (V/sqrt(3))/(s*b)
unit: Ω
tolerance: 0.5%

## A machine's air-gap line reaches {V} V (line to line) at {b} A of field current, and its short-circuit current rises {s} A per field ampere. What's its unsaturated synchronous reactance?

::: right
Right. $(V/\sqrt{3})/I_\text{sc}$ at the same field current = {answer} Ω.
:::

::: misses
- [V/(s*b)] Use the phase voltage, $V_{LL}/\sqrt{3}$.
- [any] Not yet. Open-circuit phase voltage over short-circuit current, same field current.
:::
:::

::: check
given: V = 480 | 4160 | 13800; f = 2.5 | 3.5; s = 40 | 100 | 400
answer: (V/sqrt(3))/(s*f)
unit: Ω
tolerance: 0.5%

## A machine reaches rated voltage, {V} V, at {f} A of field current on its OCC. Its SCC rises {s} A per field ampere. What's its saturated synchronous reactance?

::: right
Right. $(V/\sqrt{3})/I_\text{sc}(I_f)$ = {answer} Ω.
:::

::: misses
- [any] Not yet. Read both curves at the field current for rated voltage.
:::
:::

::: check
given: b = 1.6 | 2.5 | 28; r = 0.6 | 1.1 | 1.5; let a = b*r
answer: a/b
tolerance: 0.5%

## A generator needs {a} A of field current for rated voltage on open circuit and {b} A for rated current on short circuit. What's its short-circuit ratio?

::: right
Right. SCR = {answer}.
:::

::: misses
- [b/a] It's the open-circuit field current over the short-circuit one.
- [any] Not yet. Ratio of the two field currents.
:::
:::

::: check
given: R = 0.5 | 0.8 | 1.3 | 2
answer: 1/R
tolerance: 0.5%

## A generator's short-circuit ratio is {R}. What's its saturated synchronous reactance in per unit?

::: right
Right. $1/\text{SCR}$ = {answer} pu.
:::

::: misses
- [any] Not yet. SCR is the reciprocal of the saturated reactance in per unit.
:::
:::

::: check
given: P = 0.5 | 1.8 | 20; I = 50 | 120 | 1000
answer: P*1000/(3*I^2)
unit: Ω
tolerance: 0.5%

## On the short-circuit test at {I} A the machine takes {P} kW above its rotational loss. What's its effective armature resistance per phase?

::: right
Right. $P_\text{sc}/(3I^2)$ = {answer} Ω.
:::

::: misses
- [P*1000/I^2] The loss is in three phases.
- [any] Not yet. Load loss shared by three phases.
:::
:::

::: check
given: S = 45 | 100 | 5000; V = 220 | 480 | 13800
answer: S*1000/(sqrt(3)*V)
unit: A
tolerance: 0.5%

## What's the rated armature current of a {S} kVA, {V} V three-phase machine?

::: right
Right. $S/(\sqrt{3}V_{LL})$ = {answer} A.
:::

::: misses
- [S*1000/(3*V)] Use $\sqrt{3}V_{LL}$, or 3 times the phase voltage.
- [any] Not yet. Apparent power over $\sqrt{3}V_{LL}$.
:::
:::

::: check
kind: parts
given: S = 50 | 200 | 1000; V = 480 | 4160; a = 2.5 | 4; b = 2 | 3.2

## A {S} kVA, {V} V, Y-connected machine reaches rated voltage on its OCC at {a} A of field current, and rated current on its SCC at {b} A.

::: part
answer: a/b
tolerance: 0.5%

### What is its short-circuit ratio?

::: misses
- [b/a] Field for rated voltage over field for rated current.
- [any] $I_f(V_\text{rated})/I_f(I_\text{rated})$.
:::
:::

::: part
answer: b/a*V^2/(S*1e3)
unit: Ω
tolerance: 0.5%

### What is its saturated synchronous reactance per phase?

::: misses
- [any] $1/\text{SCR}$ per unit, times $V^2/S$.
:::
:::
:::

::: check
kind: derivation
vars: V = 100..20000, I = 1..5000, a = 0.5..50, b = 0.5..50

## A machine with rated phase voltage V and rated current I reaches rated voltage on its OCC at field current a, and rated current on its SCC at field current b.

::: step
answer: I*a/b

### What short-circuit current flows at field current a?
:::

::: step
answer: V*b/(I*a)

### What is its saturated synchronous reactance?
:::

::: right
Right. The SCC is a straight line, so the current at field a scales from the rated point.
:::
:::

::: explain
## Why is the saturated synchronous reactance smaller than the unsaturated one?

::: model
The synchronous reactance is mostly armature reaction: the voltage the armature current's own field induces back in the armature. That field, like the rotor's, runs through the iron. Near rated voltage the iron is partly saturated, so an increment of armature MMF produces less flux than it would in unsaturated iron, and the reaction voltage per ampere is smaller. The short-circuit test can't see this, since the iron is unsaturated during it; reading the open-circuit curve at rated voltage instead of the air-gap line folds the saturation into the ratio and gives a reactance closer to the machine's behavior at its operating point.
:::
:::

::: practice

::: check
given: V = 600 | 13800; f = 1.5 | 50; s = 20 | 500
answer: (V/sqrt(3))/(s*f)
unit: Ω
tolerance: 0.5%

## Saturated $X_s$: rated {V} V at {f} A, SCC {s} A/A?

::: misses
- [any] $(V/\sqrt{3})/(sI_f)$.
:::
:::

::: check
given: b = 1.2 | 45; r = 0.5 | 1.8; let a = b*r
answer: a/b
tolerance: 0.5%

## SCR: {a} A open circuit, {b} A short circuit?

::: misses
- [any] Ratio.
:::
:::

::: check
given: P = 0.3 | 50; I = 30 | 2000
answer: P*1000/(3*I^2)
unit: Ω
tolerance: 0.5%

## $R_{a,\text{eff}}$: {P} kW at {I} A?

::: misses
- [any] $P/(3I^2)$.
:::
:::
:::