S1240 of 55
0 XP
  1. Hook
  2. Play
  3. Predict
  4. Name it
  5. Check
  6. Explain

S12 · Lesson 40 · Synchronous machine transients

What the field and damper windings do in the first cycles of a fault, the subtransient and transient reactances from the dq equivalent circuits, their time constants, the decaying envelope of a three-phase short-circuit current, and the DC offset

S10 used the subtransient reactance to size circuit breakers without saying where it comes from. Here's the machine's side of the story. When a fault suddenly demands a large armature current, the flux linking the rotor's closed circuits, the field winding and the damper bars, can't change instantly. They react with currents of their own that hold the flux out of the rotor, so at first the armature sees a small reactance. As those rotor currents decay, first in the dampers and then in the field, the reactance grows through two stages to its steady-state value.

  • The current in one phase of a generator after a three-phase short circuit from 1 pu open-circuit voltage, with the worst-case DC offset, and the AC envelope (dashed).
  • The AC component starts at E/X′′d, decays with T′′d (a few cycles) to the transient level E/X′d, then with T′d (around a second) to the steady E/Xd.
  • The DC offset, up to the AC component's initial peak, decays with the armature time constant Ta.

Predict

A generator with X′′d = 0.19, X′d = 0.33 and Xd = 1.8 pu is shorted from 1 pu open-circuit voltage. What's the AC current a few seconds later?

Name it

The dq equivalent circuits

On the d axis, the armature's leakage reactance Xl is followed by the magnetizing (armature-reaction) reactance Xad, in parallel with the rotor circuits: the field winding's leakage Xfl and the d-axis damper's Xkdl, each with its resistance.

Three reactances

  • Steady state, rotor currents gone: Xd=Xl+Xad.
  • Transient, the field winding still holding flux (dampers decayed): X′d=Xl+XadXflXad+Xfl.
  • Subtransient, both field and dampers holding: X′′d=Xl+11/Xad+1/Xfl+1/Xkdl.

So X′′d<X′d<Xd.

The short-circuit current

From open circuit at voltage E, the RMS AC component is

Iac(t)=EXd+(EX′d−EXd)e−t/T′d+(EX′′d−EX′d)e−t/T′′d

with T′′d around 0.02 to 0.05 s and T′d around 0.5 to 2 s. A DC offset of up to 2E/X′′d, depending on the instant of the fault, decays with the armature time constant Ta (0.1 to 0.3 s), so the first peak can approach twice the symmetrical peak.

Worked example

A machine has Xl = 0.15, Xad = 1.65, Xfl = 0.20 and Xkdl = 0.05 pu. Find its three d-axis reactances.

Show the solution
  1. Synchronous reactance. Xd = 1.80 pu.
  2. Transient reactance. X′d=0.15+1.65×0.201.85=0.328pu
  3. Subtransient reactance. X′′d=0.15+10.606+5+20=0.189pu
  4. Why it's close to Xl. The small damper leakage dominates the parallel combination, so X′′d is barely above Xl.

Answer Xd = 1.80 pu, X′d = 0.328 pu and X′′d = 0.189 pu.

Worked example

Shorted from 1 pu with T′′d = 0.035 s and T′d = 1.2 s: what's the AC current at 0.1 s (6 cycles), when a breaker might open?

Show the solution
  1. Current levels. The three levels are 5.29, 3.05 and 0.556 pu.
  2. AC current at 0.1 s. I=0.556+2.490×e−0.1/1.2+2.244×e−0.1/0.035=0.556+2.291+0.129=2.98pu RMS.
  3. What has decayed. The subtransient part has nearly gone; the transient part has barely started to decay.

Answer 2.98 pu RMS.

Worked example

The same machine, at 60 Hz with an armature time constant of 0.15 s, is shorted at the worst instant. How high is the first current peak, half a cycle later?

Show the solution
  1. AC component at 8.3 ms. Iac=0.556+2.473+1.769=4.80pu RMS, a peak of 6.78 pu.
  2. DC offset. It starts at 2×5.29=7.48 pu and has decayed only to 7.08 pu.
  3. First peak. Together they peak at 13.9 pu, 1.85 times the symmetrical subtransient peak.
  4. Why it matters. Breakers and bus bracing are rated for this first peak, and the forces on the stator end windings, which go as its square, are what make faults close to generators so violent.

Answer the first peak reaches 13.9 pu, 1.85 times the symmetrical subtransient peak.

Check

A machine has Xl = 0.15, Xad = 1 and Xfl = 0.25 pu. What's its transient reactance X′d?

Check

Add a damper with leakage 0.08 pu to the machine (Xl = 0.15, Xad = 1, Xfl = 0.25 pu). What's X′′d?

Check

A generator at 1.05 pu internal voltage with X′′d = 0.12 pu is shorted at its terminals. What's the initial symmetrical current?

Check

A machine with X′′d = 0.15, X′d = 0.3, Xd = 2 pu, T′′d = 0.03 s and T′d = 0.8 s is shorted from 1 pu. What's the RMS AC current at t = 1 s?

Check

A generator (1 pu, X′′d = 0.12 pu) is faulted at the worst instant. What's the largest possible initial DC offset, in per-unit peak?

Check

After all transients have decayed, what short-circuit current does a generator with Ef = 1.2 pu and Xd = 1.1 pu supply?

Check

A generator at 1 pu open-circuit voltage (Xd = 1.2, X′d = 0.25, X′′d = 0.2 pu; T′d = 1.5 s, T′′d = 0.025 s) is suddenly shorted.

(a)

What is the initial symmetrical (RMS) current, in per unit?

(b)

What is the symmetrical current 0.05 s later?

Check

A machine's d axis has leakage reactance l, magnetizing reactance a, field leakage f and damper leakage k (per unit).

Step 1

What is Xd?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why is a synchronous machine's subtransient reactance so much smaller than its synchronous reactance?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.