title: Synchronous machine transients
heading: What the field and damper windings do in the first cycles of a fault, the subtransient and transient reactances from the dq equivalent circuits, their time constants, the decaying envelope of a three-phase short-circuit current, and the DC offset
eyebrow: S12 · Lesson 40 · Synchronous machine transients
xp: 50
---

::: hook
S10 used the subtransient reactance to size circuit breakers without saying where it comes from. Here's the machine's side of the story. When a fault suddenly demands a large armature current, the flux linking the rotor's closed circuits, the field winding and the damper bars, can't change instantly. They react with currents of their own that hold the flux out of the rotor, so at first the armature sees a small reactance. As those rotor currents decay, first in the dampers and then in the field, the reactance grows through two stages to its steady-state value.
:::

::: play
- The current in one phase of a generator after a three-phase short circuit from 1 pu open-circuit voltage, with the worst-case DC offset, and the AC envelope (dashed).
- The AC component starts at $E/X''_d$, decays with $T''_d$ (a few cycles) to the transient level $E/X'_d$, then with $T'_d$ (around a second) to the steady $E/X_d$.
- The DC offset, up to the AC component's initial peak, decays with the armature time constant $T_a$.
:::

```sim plot
view: graph
x: t = 0..0.5 s
y: i = -16..10
slider: x = 0.12..0.3 step 0.01 = 0.19
slider: p = 0.3..2 step 0.05 = 1.2 s
plot: sqrt(2)*(0.5556 + (3.045 - 0.5556)*exp(-t/p) + (1/x - 3.045)*exp(-t/0.035))*cos(377*t) - sqrt(2)/x*exp(-t/0.25) | samples: 3000 | label: phase current, pu
plot: sqrt(2)*(0.5556 + (3.045 - 0.5556)*exp(-t/p) + (1/x - 3.045)*exp(-t/0.035)) | dashed | color: ch3 | label: AC envelope
readout: initial symmetrical current, pu RMS = 1/x | digits: 3
readout: AC current at 0.1 s, pu RMS = 0.5556 + (3.045 - 0.5556)*exp(-0.1/p) + (1/x - 3.045)*exp(-0.1/0.035) | digits: 3
```

::: predict
## A generator with $X''_d$ = 0.19, $X'_d$ = 0.33 and $X_d$ = 1.8 pu is shorted from 1 pu open-circuit voltage. What's the AC current a few seconds later?

- [ ] 5.3 pu
- [ ] 3.0 pu
- [x] 0.56 pu
- [ ] Zero

::: reveal
Once the damper and field transients have decayed, the machine is back to its steady-state model, a voltage behind $X_d$: 1/1.8 = 0.56 pu, less than rated current. The first cycles see 1/0.19 = 5.3 pu. In practice the voltage regulator raises the field to hold more current, so relays have something to see.
:::
:::

::: nameit
## The dq equivalent circuits

On the d axis, the armature's leakage reactance $X_l$ is followed by the magnetizing (armature-reaction) reactance $X_{ad}$, in parallel with the rotor circuits: the field winding's leakage $X_{fl}$ and the d-axis damper's $X_{kdl}$, each with its resistance.

## Three reactances

- **Steady state**, rotor currents gone: $X_d = X_l + X_{ad}$.
- **Transient**, the field winding still holding flux (dampers decayed): $X'_d = X_l + \dfrac{X_{ad}X_{fl}}{X_{ad} + X_{fl}}$.
- **Subtransient**, both field and dampers holding: $X''_d = X_l + \dfrac{1}{1/X_{ad} + 1/X_{fl} + 1/X_{kdl}}$.

So $X''_d < X'_d < X_d$.

## The short-circuit current

From open circuit at voltage E, the RMS AC component is

$$I_\text{ac}(t) = \frac{E}{X_d} + \left(\frac{E}{X'_d} - \frac{E}{X_d}\right)e^{-t/T'_d} + \left(\frac{E}{X''_d} - \frac{E}{X'_d}\right)e^{-t/T''_d}$$

with $T''_d$ around 0.02 to 0.05 s and $T'_d$ around 0.5 to 2 s. A DC offset of up to $\sqrt{2}E/X''_d$, depending on the instant of the fault, decays with the armature time constant $T_a$ (0.1 to 0.3 s), so the first peak can approach twice the symmetrical peak.
:::

::: example
## A machine has $X_l$ = 0.15, $X_{ad}$ = 1.65, $X_{fl}$ = 0.20 and $X_{kdl}$ = 0.05 pu. Find its three d-axis reactances.

::: solution
1. **Synchronous reactance.** $X_d$ = 1.80 pu.
2. **Transient reactance.**
   $$\begin{aligned} X'_d &= 0.15 + \frac{1.65 \times 0.20}{1.85} \\ &= 0.328\ \text{pu} \end{aligned}$$
3. **Subtransient reactance.**
   $$\begin{aligned} X''_d &= 0.15 + \frac{1}{0.606 + 5 + 20} \\ &= 0.189\ \text{pu} \end{aligned}$$
4. **Why it's close to $X_l$.** The small damper leakage dominates the parallel combination, so $X''_d$ is barely above $X_l$.

**Answer:** $X_d$ = 1.80 pu, $X'_d$ = 0.328 pu and $X''_d$ = 0.189 pu.
:::
:::

::: example
## Shorted from 1 pu with $T''_d$ = 0.035 s and $T'_d$ = 1.2 s: what's the AC current at 0.1 s (6 cycles), when a breaker might open?

::: solution
1. **Current levels.** The three levels are 5.29, 3.05 and 0.556 pu.
2. **AC current at 0.1 s.**
   $$\begin{aligned} I &= 0.556 + 2.490 \times e^{-0.1/1.2} \\ &\quad + 2.244 \times e^{-0.1/0.035} \\ &= 0.556 + 2.291 + 0.129 \\ &= 2.98\ \text{pu} \end{aligned}$$
   RMS.
3. **What has decayed.** The subtransient part has nearly gone; the transient part has barely started to decay.

**Answer:** 2.98 pu RMS.
:::
:::

::: example
## The same machine, at 60 Hz with an armature time constant of 0.15 s, is shorted at the worst instant. How high is the first current peak, half a cycle later?

::: solution
1. **AC component at 8.3 ms.**
   $$\begin{aligned} I_\text{ac} &= 0.556 + 2.473 + 1.769 \\ &= 4.80\ \text{pu} \end{aligned}$$
   RMS, a peak of 6.78 pu.
2. **DC offset.** It starts at $\sqrt2 \times 5.29 = 7.48$ pu and has decayed only to 7.08 pu.
3. **First peak.** Together they peak at 13.9 pu, 1.85 times the symmetrical subtransient peak.
4. **Why it matters.** Breakers and bus bracing are rated for this first peak, and the forces on the stator end windings, which go as its square, are what make faults close to generators so violent.

**Answer:** the first peak reaches 13.9 pu, 1.85 times the symmetrical subtransient peak.
:::
:::

::: check
given: l = 0.1 | 0.15 | 0.2; a = 1 | 1.6 | 2.2; f = 0.1 | 0.25
answer: l + a*f/(a + f)
tolerance: 0.5%

## A machine has $X_l$ = {l}, $X_{ad}$ = {a} and $X_{fl}$ = {f} pu. What's its transient reactance $X'_d$?

::: right
Right. $X_l + X_{ad} \parallel X_{fl}$ = {answer} pu.
:::

::: misses
- [l + a] That's $X_d$; the field winding shunts $X_{ad}$ at first.
- [any] Not yet. The field's leakage in parallel with $X_{ad}$.
:::
:::

::: check
given: l = 0.1 | 0.15 | 0.2; a = 1 | 1.6 | 2.2; f = 0.1 | 0.25; k = 0.03 | 0.08
answer: l + 1/(1/a + 1/f + 1/k)
tolerance: 0.5%

## Add a damper with leakage {k} pu to the machine ($X_l$ = {l}, $X_{ad}$ = {a}, $X_{fl}$ = {f} pu). What's $X''_d$?

::: right
Right. $X_l$ plus all three in parallel: {answer} pu.
:::

::: misses
- [l + a*f/(a + f)] That's $X'_d$; include the damper.
- [any] Not yet. Three branches in parallel.
:::
:::

::: check
given: E = 1 | 1.05 | 1.1; x = 0.12 | 0.2 | 0.28
answer: E/x
tolerance: 0.5%

## A generator at {E} pu internal voltage with $X''_d$ = {x} pu is shorted at its terminals. What's the initial symmetrical current?

::: right
Right. $E/X''_d$ = {answer} pu RMS.
:::

::: misses
- [sqrt(2)*E/x] That's the peak; the question asks for RMS.
- [any] Not yet. The subtransient reactance limits the first cycles.
:::
:::

::: check
given: x = 0.15 | 0.22; y = 0.3 | 0.4; X = 1.2 | 2; t = 0.05 | 0.2 | 1; T = 0.8 | 1.5
answer: 1/X + (1/y - 1/X)*exp(-t/T) + (1/x - 1/y)*exp(-t/0.03)
tolerance: 0.5%

## A machine with $X''_d$ = {x}, $X'_d$ = {y}, $X_d$ = {X} pu, $T''_d$ = 0.03 s and $T'_d$ = {T} s is shorted from 1 pu. What's the RMS AC current at t = {t} s?

::: right
Right. {answer} pu.
:::

::: misses
- [any] Not yet. Three levels with two decays.
:::
:::

::: check
given: E = 1 | 1.1; x = 0.12 | 0.2 | 0.28
answer: sqrt(2)*E/x
tolerance: 0.5%

## A generator ({E} pu, $X''_d$ = {x} pu) is faulted at the worst instant. What's the largest possible initial DC offset, in per-unit peak?

::: right
Right. $\sqrt{2}E/X''_d$ = {answer} pu.
:::

::: misses
- [E/x] The offset equals the AC component's peak, not its RMS.
- [any] Not yet. The current must start from zero.
:::
:::

::: check
given: E = 1 | 1.2 | 1.5; X = 1.1 | 1.6 | 2.2
answer: E/X
tolerance: 0.5%

## After all transients have decayed, what short-circuit current does a generator with $E_f$ = {E} pu and $X_d$ = {X} pu supply?

::: right
Right. $E_f/X_d$ = {answer} pu.
:::

::: misses
- [any] Not yet. The steady-state model.
:::
:::

::: check
kind: parts
given: d = 1.2 | 1.8; p = 0.25 | 0.35; s = 0.15 | 0.2; T = 0.8 | 1.5; u = 0.025 | 0.04; t = 0.05 | 0.1 | 0.25

## A generator at 1 pu open-circuit voltage ($X_d$ = {d}, $X'_d$ = {p}, $X''_d$ = {s} pu; $T'_d$ = {T} s, $T''_d$ = {u} s) is suddenly shorted.

::: part
answer: 1/s
tolerance: 0.5%

### What is the initial symmetrical (RMS) current, in per unit?

::: misses
- [1/p] That's the transient level; the dampers hold flux at first.
- [any] $E/X''_d$.
:::
:::

::: part
answer: 1/d + (1/p - 1/d)*exp(-t/T) + (1/s - 1/p)*exp(-t/u)
tolerance: 0.5%

### What is the symmetrical current {t} s later?

::: misses
- [any] Steady, transient and subtransient terms, each decaying with its own time constant.
:::
:::
:::

::: check
kind: derivation
vars: l = 0.05..0.3, a = 0.5..3, f = 0.05..0.5, k = 0.01..0.2

## A machine's d axis has leakage reactance l, magnetizing reactance a, field leakage f and damper leakage k (per unit).

::: step
answer: l + a

### What is $X_d$?
:::

::: step
answer: l + a*f/(a + f)

### What is $X'_d$?
:::

::: step
answer: l + 1/(1/a + 1/f + 1/k)

### What is $X''_d$?
:::

::: right
Right. Each rotor circuit that still holds flux shunts the magnetizing reactance.
:::
:::

::: explain
## Why is a synchronous machine's subtransient reactance so much smaller than its synchronous reactance?

::: model
The synchronous reactance is large because armature MMF along the d axis drives flux through the rotor iron, a low-reluctance path, and that flux links the armature heavily. When the armature current changes suddenly, the rotor's closed windings, the field and the damper bars, react according to Lenz's law: currents are induced in them that keep their own flux linkages constant, which means they push the armature's new flux out of the rotor. That flux is forced into the leakage paths around the rotor's windings, which have high reluctance, so the same armature current produces much less flux and the reactance is small. As the damper currents decay through their resistance the flux penetrates the dampers (transient), and as the field current's disturbance decays it penetrates the whole rotor (steady state).
:::
:::

::: practice

::: check
given: l = 0.08 | 0.25; a = 0.8 | 2.5; f = 0.08 | 0.3
answer: l + a*f/(a + f)
tolerance: 0.5%

## $X'_d$: $X_l$ = {l}, $X_{ad}$ = {a}, $X_{fl}$ = {f}?

::: misses
- [any] $X_l + X_{ad} \parallel X_{fl}$.
:::
:::

::: check
given: E = 0.95 | 1.15; x = 0.1 | 0.35
answer: E/x
tolerance: 0.5%

## Initial symmetrical current: {E} pu, $X''_d$ = {x}?

::: misses
- [any] $E/X''_d$.
:::
:::

::: check
given: x = 0.12 | 0.25; y = 0.28 | 0.45; X = 1 | 2.4; t = 0.1 | 2; T = 0.5 | 2
answer: 1/X + (1/y - 1/X)*exp(-t/T) + (1/x - 1/y)*exp(-t/0.03)
tolerance: 0.5%

## AC current at {t} s: $X''_d$ = {x}, $X'_d$ = {y}, $X_d$ = {X}, $T'_d$ = {T} s?

::: misses
- [any] Three levels, two decays ($T''_d$ = 0.03 s).
:::
:::
:::