title: Transformer efficiency, regulation and inrush
heading: Core and copper losses against load, the load at which a transformer is most efficient, all-day efficiency for a varying load, voltage regulation from the series impedance, and the inrush current when a transformer is switched on at the wrong instant
eyebrow: S12 · Lesson 3 · Transformer efficiency, regulation and inrush
xp: 50
---

::: hook
S10 used the transformer as a network element: an impedance, a tap and a phase shift. A machine designer asks different questions. How much energy does the transformer waste over a day when its load comes and goes? At what load is it most efficient? And why does the breaker sometimes trip when the transformer is switched on with nothing connected? The answers come from the same equivalent circuit, read with losses in mind.
:::

::: play
- The efficiency of a 50 kVA transformer against load (as a fraction of rating), with 200 W of core loss and 600 W of copper loss at full load.
- Core loss is constant whenever the transformer is energized; copper loss grows with the square of the load. Efficiency peaks where the two are equal.
- Lowering the power factor lowers the real power delivered for the same current, so the whole curve drops.
:::

```sim plot
view: graph
x: x = 0.02..1.5
y: e = 90..100 %
slider: c = 50..800 = 200 W
slider: u = 200..2000 = 600 W
slider: p = 0.5..1 = 0.8
plot: 100*x*50000*p/(x*50000*p + c + x^2*u) | samples: 400 | label: efficiency
readout: load at peak efficiency = sqrt(c/u) | digits: 3
readout: peak efficiency, % = 100*sqrt(c/u)*50000*p/(sqrt(c/u)*50000*p + 2*c) | digits: 4
```

::: predict
## A 50 kVA transformer has 200 W of core loss and 600 W of copper loss at full load. At what load is it most efficient?

- [ ] Full load
- [ ] One third of full load
- [x] About 58% of full load
- [ ] No load

::: reveal
Efficiency peaks where the copper loss, $x^2 \times 600$ W at load fraction x, equals the fixed 200 W of core loss: $x = \sqrt{200/600}$ = 0.577. Distribution transformers are designed this way on purpose, since they spend most of the day well below their rating.
:::
:::

::: nameit
## Losses

The **core loss** $P_c$ (hysteresis and eddy currents, lesson 2) depends on the voltage and frequency and is constant whenever the transformer is energized; the open-circuit test measures it. The **copper loss** at load fraction x is $x^2P_{cu}$, with $P_{cu}$ the full-load value from the short-circuit test. At rated kVA S and power factor pf:

$$\eta = \frac{xS\,\text{pf}}{xS\,\text{pf} + P_c + x^2P_{cu}}$$

## Maximum efficiency

Setting $d\eta/dx = 0$ gives $x^2P_{cu} = P_c$: the most efficient load is $x = \sqrt{P_c/P_{cu}}$, where the two losses are equal.

## All-day efficiency

For a load that varies over the day, the ratio of energy delivered to energy taken counts core loss for all 24 hours and copper loss according to each period's load.

## Regulation

With the series impedance $r + jx$ in per unit, the rise in secondary voltage from full load to no load is approximately $r\cos\theta + x\sin\theta$ for a lagging power factor $\cos\theta$ (S10 lesson 3 gives the exact form).

## Inrush

The flux is the integral of the voltage. Switched on at a voltage zero, the flux starts at zero (or at the residual flux) instead of at its negative peak, and climbs to twice its normal peak plus any residual. That drives the core deep into saturation, where only the air-core inductance limits the current, and the magnetizing current can reach many times rated current for a few cycles.
:::

::: example
## Find the 50 kVA transformer's efficiency at full load and at its best load, both at 0.8 power factor.

::: solution
1. **Efficiency at full load.**
   $$\begin{aligned} \eta &= \frac{40\,000}{40\,000 + 200 + 600} \\ &= 98.04\% \end{aligned}$$
2. **Efficiency at the best load.** At x = 0.577 the output is 23,094 W and the losses are 200 + 200 = 400 W, so
   $$\eta = 98.30\%$$
3. **Per-unit resistance.**
   $$\begin{aligned} R &= \frac{600}{50\,000} \\ &= 0.012\ \text{pu} \end{aligned}$$
4. **Regulation at 0.8 lagging.** With 0.04 pu reactance it's about
   $$\begin{aligned} \text{reg} &\approx 0.012 \times 0.8 \\ &\quad + 0.04 \times 0.6 \\ &= 3.36\% \end{aligned}$$
   or 3.39% exactly.

**Answer:** 98.04% at full load and 98.30% at its best load (x = 0.577). Its regulation at 0.8 lagging is about 3.36% (3.39% exactly).
:::
:::

::: example
## The same transformer runs 8 hours a day at full load and 16 at a quarter load, all at 0.8 power factor. Find its all-day efficiency.

::: solution
1. **Energy out.**
   $$\begin{aligned} W_\text{out} &= 8 \times 40 + 16 \times 10 \\ &= 480\ \text{kWh} \end{aligned}$$
2. **Core loss.** It's paid all 24 hours:
   $$\begin{aligned} W_\text{core} &= 24 \times 0.2 \\ &= 4.8\ \text{kWh} \end{aligned}$$
3. **Copper loss.**
   $$\begin{aligned} W_\text{cu} &= 8 \times 0.6 \\ &\quad + 16 \times 0.6 \times 0.25^2 \\ &= 5.4\ \text{kWh} \end{aligned}$$
4. **All-day efficiency.**
   $$\begin{aligned} \eta &= \frac{480}{490.2} \\ &= 97.92\% \end{aligned}$$
5. **A better match.** A transformer designed with lower core loss and higher copper loss would do better on this cycle.

**Answer:** the all-day efficiency is 97.92%.
:::
:::

::: example
## Two 100 kVA transformers are offered for a load that runs 6 hours a day at full load and 18 hours at 20%. A has 250 W of core loss and 1200 W of full-load copper loss; B has 400 W and 900 W. Which wastes less energy?

::: solution
1. **Transformer A.**
   $$\begin{aligned} W_\text{core} &= 24 \times 0.25 \\ &= 6.0\ \text{kWh} \\ W_\text{cu} &= 6 \times 1.2 \\ &\quad + 18 \times 1.2 \times 0.2^2 \\ &= 8.06\ \text{kWh} \end{aligned}$$
   14.06 kWh a day in all.
2. **Transformer B.**
   $$\begin{aligned} W_\text{core} &= 24 \times 0.4 \\ &= 9.6\ \text{kWh} \\ W_\text{cu} &= 6 \times 0.9 \\ &\quad + 18 \times 0.9 \times 0.04 \\ &= 6.05\ \text{kWh} \end{aligned}$$
   15.65 kWh a day in all.
3. **Compare.** A saves 1.58 kWh a day, 578 kWh a year, though B is more efficient at full load.
4. **What decides.** For lightly loaded transformers the core loss, paid around the clock, decides.

**Answer:** A wastes less: 14.06 kWh a day against B's 15.65 kWh, a saving of 1.58 kWh a day (578 kWh a year).
:::
:::

::: check
given: S = 25 | 100 | 500; c = 0.2 | 0.5; u = 0.8 | 1.5; x = 0.25 | 0.5 | 0.75; p = 0.8 | 1
answer: 100*x*S*p/(x*S*p + c*S/100 + x^2*u*S/100)
unit: %
tolerance: 0.5%

## A {S} kVA transformer has core loss {c}% and full-load copper loss {u}% of its rating. What's its efficiency at {x} of full load and power factor {p}?

::: right
Right. $xS\,\text{pf}/(xS\,\text{pf} + P_c + x^2P_{cu})$ = {answer}%.
:::

::: misses
- [any] Not yet. Output over output plus both losses.
:::
:::

::: check
given: c = 100 | 200 | 300; u = 400 | 900 | 2500
answer: sqrt(c/u)
tolerance: 0.5%

## A transformer has {c} W of core loss and {u} W of full-load copper loss. At what fraction of full load is it most efficient?

::: right
Right. $\sqrt{P_c/P_{cu}}$ = {answer}.
:::

::: misses
- [c/u] The copper loss at load x is $x^2P_{cu}$.
- [any] Not yet. Where copper loss equals core loss.
:::
:::

::: check
given: S = 25 | 100; c = 100 | 300; u = 400 | 1200; p = 0.8 | 1
answer: 100*sqrt(c/u)*S*1000*p/(sqrt(c/u)*S*1000*p + 2*c)
unit: %
tolerance: 0.5%

## A {S} kVA transformer with {c} W of core loss and {u} W of full-load copper loss runs at power factor {p}. What's its maximum efficiency?

::: right
Right. At $x = \sqrt{P_c/P_{cu}}$ the losses total $2P_c$: {answer}%.
:::

::: misses
- [any] Not yet. Find the best load first; there the copper loss equals the core loss.
:::
:::

::: check
given: S = 50 | 200; c = 0.3 | 0.6; u = 1 | 1.5; h = 4 | 8 | 12; x = 0.2 | 0.4
answer: 100*(h*S*0.9 + (24 - h)*x*S*0.9)/(h*S*0.9 + (24 - h)*x*S*0.9 + 24*c*S/100 + (h + (24 - h)*x^2)*u*S/100)
unit: %
tolerance: 0.5%

## A {S} kVA transformer (core loss {c}%, full-load copper loss {u}%) runs {h} hours a day at full load and the rest at {x} of full load, all at 0.9 power factor. What's its all-day efficiency?

::: right
Right. Energy out over energy in, with core loss for all 24 hours: {answer}%.
:::

::: misses
- [any] Not yet. Core loss runs all day; copper loss follows the load squared.
:::
:::

::: check
given: r = 0.005 | 0.012 | 0.02; x = 0.03 | 0.06 | 0.1; p = 0.6 | 0.85 | 0.95
answer: 100*(r*p + x*sqrt(1 - p^2))
unit: %
tolerance: 0.5%

## A transformer's series impedance is {r} + j\given{x} per unit. What's its approximate regulation at full load, power factor {p} lagging?

::: right
Right. $r\cos\theta + x\sin\theta$ = {answer}%.
:::

::: misses
- [100*(r*p + x*p)] The reactance multiplies $\sin\theta$, not the power factor.
- [any] Not yet. The in-phase part of the impedance drop.
:::
:::

::: check
given: B = 1.4 | 1.6 | 1.7; r = 0.2 | 0.5 | 0.8
answer: (2 + r)*B
unit: T
tolerance: 0.5%

## A transformer runs at a peak flux density of {B} T. It's switched on at a voltage zero with residual flux {r} of its normal peak, in the direction the flux is about to go. What peak flux density does the core reach in the first cycle (ignoring saturation)?

::: right
Right. The residual plus twice the normal peak: {answer} T, far beyond saturation.
:::

::: misses
- [2*B] Add the residual flux.
- [any] Not yet. The flux is the integral of the voltage, starting from the residual.
:::
:::

::: check
kind: parts
given: c = 0.2 | 0.4; u = 0.9 | 1.5; h = 4 | 8 | 12; x = 0.1 | 0.3

## A transformer has {c} kW of core loss and {u} kW of full-load copper loss. Each day it runs {h} hours at full load and the rest at {x} of full load.

::: part
answer: 24*c + h*u + (24 - h)*u*x^2
unit: kWh
tolerance: 0.5%

### How much energy does it lose per day?

::: misses
- [24*c + h*u + (24 - h)*u*x] Copper loss goes as the square of the load.
- [any] Core loss all day, plus copper loss scaled by load squared.
:::
:::

::: part
answer: (24*c + h*u + (24 - h)*u*x^2)*365
unit: kWh
tolerance: 0.5%

### And per year?

::: misses
- [any] Times 365.
:::
:::
:::

::: check
kind: derivation
vars: S = 1..1000, c = 0.001..0.02, u = 0.002..0.03, x = 0.1..1.2, p = 0.5..1

## A transformer rated S kVA has core loss c and full-load copper loss u, each as a fraction of S; it runs at load fraction x and power factor p.

::: step
answer: x*S*p/(x*S*p + c*S + x^2*u*S)

### What is its efficiency?
:::

::: step
answer: sqrt(c/u)

### At what load fraction is it most efficient?
:::

::: right
Right. The best load makes the copper loss equal the core loss.
:::
:::

::: explain
## Why is a distribution transformer designed to be most efficient well below its rated load?

::: model
A transformer's core loss is paid every hour it's energized, whether or not anything is drawing power, while its copper loss depends on the load squared. A distribution transformer on a residential street is energized all day but carries its rated load only during a few peak hours and runs lightly loaded the rest of the time. Its energy losses are dominated by the core, so the designer spends more on low-loss steel and accepts somewhat more copper loss, which puts the point where the two losses are equal, and the efficiency peak, at a fraction of the rating. That minimizes the energy wasted over a typical day, which is what the utility pays for.
:::
:::

::: practice

::: check
given: S = 10 | 300; c = 0.15 | 0.6; u = 0.7 | 2; x = 0.3 | 0.9; p = 0.75 | 1
answer: 100*x*S*p/(x*S*p + c*S/100 + x^2*u*S/100)
unit: %
tolerance: 0.5%

## Efficiency: {S} kVA, core {c}%, copper {u}%, load {x}, pf {p}?

::: misses
- [any] $xSp/(xSp + P_c + x^2P_{cu})$.
:::
:::

::: check
given: c = 50 | 250; u = 300 | 3000
answer: sqrt(c/u)
tolerance: 0.5%

## Best load fraction: {c} W core, {u} W copper?

::: misses
- [any] $\sqrt{P_c/P_{cu}}$.
:::
:::

::: check
given: r = 0.008 | 0.025; x = 0.04 | 0.12; p = 0.6 | 0.9
answer: 100*(r*p + x*sqrt(1 - p^2))
unit: %
tolerance: 0.5%

## Regulation: {r} + j\given{x} pu at pf {p} lagging?

::: misses
- [any] $r\cos\theta + x\sin\theta$.
:::
:::
:::