S12 · Lesson 26 · Unbalanced supply and induction motors
Voltage unbalance by NEMA's and IEC's definitions, symmetrical components of the supply, the motor's small negative-sequence impedance, the large currents a little unbalance drives, the extra heating and the derating it forces
Three-phase supplies are never perfectly balanced: single-phase loads spread unevenly, a blown capacitor fuse, a long feeder. An induction motor turns out to be very sensitive to this. A voltage unbalance of only 2% can drive 15% of rated current in a backward-rotating field that brakes the rotor and heats it at twice line frequency, which is why motor standards derate machines on unbalanced supplies and why protective relays watch the negative-sequence current.
- The line is the negative-sequence current, as a percentage of the positive-sequence current, against the supply's voltage unbalance, for a motor whose locked-rotor current is the multiple on the slider: .
- The dashed curve is the approximate extra temperature rise, percent for u percent unbalance.
- At 5% unbalance a typical motor carries a third of its rated current in the negative sequence.
Predict
A 460 V motor whose starting current is 7 times rated runs on a supply with 2% voltage unbalance. About how much negative-sequence current does it draw?
The backward field slips past the rotor at nearly twice synchronous speed, so to the negative-sequence voltage the motor looks like it does at standstill: its locked-rotor impedance, a seventh of its full-load impedance. So 2% of the voltage drives about 7 × 2% = 14% of rated current. For lesson 20's motor the equivalent circuit gives a ratio of 7.1 between the two impedances, and 14.2%.
Name it
Measuring unbalance
- NEMA: the largest deviation of a line voltage from the average of the three, as a percentage of the average.
- IEC (true unbalance): the ratio of negative- to positive-sequence voltage, . From the three line-voltage magnitudes alone, with ,
Symmetrical components
Any three phasors split into positive, negative and zero sequences:
with . A three-wire motor sees only and .
The motor's two impedances
The positive sequence drives the forward field at slip s, through the usual equivalent circuit. The negative sequence drives a backward field at slip , through the same circuit with in place of : nearly the locked-rotor impedance. So
Effects
The negative-sequence current heats the stator, and the rotor at twice line frequency, where deep bars' resistance is high. It also makes a small braking torque and a torque pulsation at twice line frequency. A common rule puts the extra temperature rise at about percent for u percent unbalance, and NEMA MG 1 derates motors to about 0.95 of their rating at 2% unbalance and 0.75 at 5%, recommending against running above 5%. A lost phase is the extreme case: .
Worked example
A motor's line voltages are 460, 467 and 450 V. Find the unbalance by NEMA's and IEC's definitions, and the approximate extra temperature rise.
Show the solution
- NEMA's definition. The average is 459 V and the largest deviation 9 V, so the unbalance is
- IEC's definition. β = 0.33364, so = 0.99908 and u = 2.15%. Constructing the triangle of line voltages and computing and directly gives the same 2.15%.
- Compare. The two definitions differ by about 10% here.
- Extra temperature rise. The rule of thumb gives about which on a motor rated for an 80 K rise is about 6 K more.
Answer the unbalance is 1.96% by NEMA's definition and 2.15% by IEC's, adding about 7.7% to the temperature rise (about 6 K on an 80 K motor).
Worked example
For lesson 20's 460 V motor at 2% slip, find the positive- and negative-sequence impedances, and the negative-sequence current with 2% voltage unbalance.
Show the solution
- Positive-sequence impedance. At s = 0.02 the input impedance is 6.50 + j3.29 Ω, 7.28 Ω.
- Negative-sequence impedance. At slip 1.98 the rotor branch is 0.076 + j0.5 Ω, which with the magnetizing branch and stator gives 0.272 + j0.988 Ω, 1.025 Ω: 7.1 times smaller.
- Negative-sequence current. With 2% of the 265.6 V phase voltage in the negative sequence, 14.2% of the 36.5 A rated current, flowing in the rotor at nearly 120 Hz.
Answer the positive-sequence impedance is 7.28 Ω and the negative-sequence one 1.025 Ω, so 2% unbalance drives 5.2 A of negative-sequence current.
Worked example
In the last example's motor, how unequal are the three phase currents, and what does that mean for the hottest winding?
Show the solution
- How the sequences add. Each phase current is the sum of the 36.5 A positive-sequence current and the 5.2 A negative-sequence current, but the negative sequence's phase order is reversed, so it adds at a different angle in each phase.
- The largest phase current. It lies between and = 41.7 A: 8 to 14% above balanced.
- Copper loss. Going as the square, its copper loss is 16 to 30% higher, and that winding's temperature, not the average, sets the motor's limit.
- Derating. That's why a few percent of voltage unbalance calls for a noticeable derating.
Answer the largest phase current is 39.3 to 41.7 A, 8 to 14% above balanced, so its winding has 16 to 30% more copper loss and sets the motor's limit.
Check
A motor's line voltages are 460, 462 and 452 V.
(a)
What is the NEMA voltage unbalance?
(b)
About how much more does the motor's temperature rise?
Check
A supply's line voltages are 400, 405 and 445 V.
(a)
What is its true (negative- to positive-sequence) unbalance?
Check
A motor rated 300 A has a locked-rotor current of 6.5 times rated and runs on a supply with 1% true unbalance.
(a)
About what negative-sequence current does it draw, as a percentage of rated?
(b)
In amperes?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
An induction motor on 50 Hz runs at slip 0.02.
(a)
What is its slip relative to the negative-sequence field?
(b)
At what frequency does negative-sequence current flow in its rotor?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
A motor's phase voltages are 265∠0°, 255∠−121° and 272∠117° V.
(a)
What is the positive-sequence voltage's magnitude?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
And the negative-sequence voltage's?
Check
Why does a small voltage unbalance drive a disproportionately large current in an induction motor?
Check
An induction motor has = R, = X, = M, = r and = x, running at slip s.
Step 1
What slip does the negative-sequence field see?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What rotor resistance term replaces in the negative-sequence circuit?
Check
Write sequences(Va, Vb, Vc) returning the magnitudes (V0, V1, V2) of complex phasors, iec_unbalance(a, b, c) from three line-voltage magnitudes, and neg_seq_current(V2, R1, X1, Xm, R2, X2, s): the negative-sequence current magnitude for a negative-sequence phase voltage V2.
Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.
Explain why
Why do motor standards derate induction motors on unbalanced supplies?
An unbalanced supply contains a negative-sequence voltage that drives a field rotating backward. The rotor slips past that field at nearly twice synchronous speed, so the motor presents its low locked-rotor impedance to it, and a small negative-sequence voltage drives a negative-sequence current several times larger in proportion. That current adds copper loss in the stator and, at twice line frequency where the rotor bars' resistance is higher, in the rotor, while producing no useful torque. To keep the windings within their temperature limits, the motor must carry less load, so standards specify a derating that grows quickly with the unbalance.
Practice
Keep practicing
8 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.