S4 Computer architecture · Practice
Warehouse-scale computers
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 11 kinds solid
Check
A data center draws 12 MW in total while its IT equipment draws 8 MW. What's its PUE?
Check
A server peaks at 200 W and idles at 0.3 of that. What does it draw at 0.5 utilization?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A server idles at 0.2 of its peak power. At 0.3 utilization, what's its energy efficiency relative to full load?
Check
10000 servers average 180 W in a facility with PUE 1.5. At 100 dollars per MWh, what does a 730-hour month of electricity cost, in dollars?
Check
A request fans out to 20 servers and waits for all. Each is slow with probability 0.01, independently. What fraction of requests are slow?
Check
A data center has 20000 servers, each with an MTTF of 3 years. How many fail per day, on average?
Check
10000 servers peak at 300 W and idle at 0.5 of peak, running at 0.5 utilization in a facility with PUE 1.1; electricity costs 50 dollars per MWh.
(a)
What does each server draw?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
(b)
What is the monthly electricity bill, in dollars (730 hours)?
Check
A request fans out to 100 servers, each slow with probability 0.001. Separately, a facility has 100000 servers with an MTTF of 5 years.
(a)
What fraction of requests are slow?
(b)
How many servers fail per day?
Check
Server power: peak 250 W, idle 0.4, utilization 0.45?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
Slow requests: fan-out 50, each slow with 0.005?
Check
Efficiency at 0.2 utilization, idle at 0.3?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in S4