S9 · Lesson 8 · Higher-order systems, zeros and dominant poles
Step responses as sums of modes, when a far pole can be ignored, how a left-half-plane zero adds overshoot and a right-half-plane zero makes the response start the wrong way, and the slow tails of pole–zero dipoles
Real closed loops have more than two poles, and they have zeros too. Yet the second-order formulas from lesson 7 are used everywhere, because in a well-designed loop one pair of poles usually dominates and the rest add only small, fast corrections. This lesson shows when that's true, and it shows the two cases where it fails: a zero near the dominant poles, which can double the overshoot, and a zero in the right half-plane, which makes the response start off in the wrong direction.
- The step response of (ζ = 0.5, = 1), which is the original response plus a times its derivative.
- a > 0 puts a zero at −1/a in the left half-plane: the derivative term adds a kick, and overshoot rises (30% for a zero at −1).
- a < 0 puts the zero in the right half-plane at +1/|a|: the response first dips below zero before rising, because the derivative term starts out pulling the wrong way.
Predict
A third pole at −5 is added to a loop whose dominant poles are (ζ = 0.5). What happens to the 16.3% overshoot?
A pole ten times farther from the imaginary axis than the dominant pair contributes a small, fast term: its residue in the step response is = 0.048 and it dies out in about a second. Simulated, the overshoot becomes 15.9% and the peak comes 0.2 s later. Move the pole in to −1 and the overshoot halves to 8.1%: then it's no longer far.
Name it
Modes
A step response is a sum of terms, one per pole: , with residues from partial fractions. A pole's influence depends on its residue (how big its term starts) and its real part (how fast it dies).
Dominant poles
Poles much farther left than the dominant ones, five times or more, have small residues and die out fast. For a third pole at −p added to the standard second-order system (scaled to keep T(0) = 1), the step residue is . Simulated overshoots with ζ = 0.5, = 1:
| Extra pole at | none | −10 | −5 | −2 | −1 |
|---|---|---|---|---|---|
| Overshoot | 16.3% | 16.2% | 15.9% | 13.9% | 8.1% |
Zeros
A zero at −z multiplies the response by , adding times its derivative. Close zeros matter a lot:
| Zero at | −5 | −2 | −1 | −0.5 |
|---|---|---|---|---|
| Overshoot | 16.7% | 19.1% | 29.8% | 69.9% |
A right-half-plane zero, , subtracts the derivative, so the response starts by moving the wrong way: with a zero at +1 the example dips to −0.28. Plants with RHP zeros are nonminimum phase; a boost converter's control-to-output response and an aircraft's altitude response to the elevator both have one, and they limit how fast a loop can be (lesson 28).
Dipoles
A pole and zero close together barely change the fast response but leave a slow tail of amplitude about , decaying with the pole. A lag compensator (lesson 14) creates exactly this.
Worked example
What does a right-half-plane zero do to a first-order plant? Take .
Show the solution
- Just after the step. The output jumps the wrong way.
- The rest of the response. It then rises to 1:
- Put in numbers. With τ = 1 s and a zero at +2, the output starts at
- Speed costs more undershoot. The faster you try to make such a system respond, the bigger the wrong-way excursion.
Answer it makes the output start the wrong way, at , before rising to 1; with τ = 1 s and a zero at +2 it starts at −0.5.
Worked example
A loop's slow pole at −1 sits next to a zero at −1.1, with the rest of the loop . What does the tail look like?
Show the solution
- Residue of the slow pole. The step residue at −1 is
- Shape of the tail. The output reaches about 90% quickly, then creeps the last 10% with a 1 s time constant:
- Settling time. Getting within 2% takes about even though the fast part settles in a fraction of that.
Answer a quick rise to about 90%, then a slow creep with a 1 s time constant (0.963 at 1 s, 0.995 at 3 s), settling within 2% after about 1.6 s.
Worked example
A PI controller's zero cancels the plant pole of , giving L = 1/s and a fast, clean step response. What does a step disturbance at the plant's input do?
Show the solution
- What the reference sees.
- What the disturbance sees. It reaches the output through
- Its step response.
- Peak and tail. It peaks at at 0.077, and is still 0.015 at 20 s.
- Why it's slow. The cancelled pole at −0.1 is hidden from the reference but not from the disturbance, so cancelling a slow plant pole makes disturbance rejection as slow as the plant.
Answer the disturbance's effect peaks at 0.077 after 2.56 s and is still 0.015 at 20 s, as slow as the cancelled plant pole.
Check
A third pole at −10 is added to with = 1 and ζ = 0.3, keeping the DC gain at 1. How big is its term in the step response?
Check
A plant has τ = 0.5 s and a zero at +1. How far below zero does its step response start?
Check
A system has τ = 1 s and a zero at −0.5. To what value does its step response jump at t = 0⁺?
Check
A slow pole at −1 and a zero at −1.05×1 sit in a loop whose fast part is . How big is the slow tail in the step response?
Check
with a = 1 and b = 4. What's its step response at t = 1 s?
Check
. Where does its step response settle?
Check
A PI zero cancels the plant pole of with τ = 10 s, and the loop is with = 0.5 s. A unit step disturbance enters at the plant's input.
(a)
When does its effect on the output peak?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
How large is the peak?
Check
The closed loop gets a unit step.
Step 1
What is the coefficient of in the response?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
And of ?
Explain why
Why does a right-half-plane zero make a step response start in the wrong direction?
A zero at +z multiplies the transfer function by , so the output is the response without the zero minus times its derivative. Right after a step, the response without the zero is still near zero but already rising, so its derivative is large and positive while its value is tiny, and subtracting the derivative drives the output negative. Only later, once the rise slows, does the value term win and the output head toward its final value. A boost converter shows this: asking for more output voltage means first holding the switch on longer, which briefly starves the output of current before the inductor's extra energy arrives.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.