C3 · Lesson 16 · AC power
Power that does work, and power that only sloshes
Multiply the RMS voltage and current of a motor and you get a number in volt-amperes, but the electricity meter charges for less than that. Part of the current flows into the motor's magnetic field and back out again each cycle, doing no work but still heating the wires. Utilities care about that sloshing power, called reactive power, because their cables and transformers must carry it. The ratio of useful power to the total is the power factor.
Play
- The curves are a voltage, a current lagging it by φ, and their product, the instantaneous power p(t). The dashed line is p's average.
- At φ = 0, is p(t) ever negative? Now raise φ toward 90°. What happens to the average, and to the parts where p dips below zero?
- The readouts give the real power P, the reactive power Q and the apparent power S.
Predict
A 120 V supply drives an ideal inductor, drawing 5 A RMS. What average power does it consume?
0 W. With the current a quarter cycle behind the voltage, p(t) is positive for one quarter cycle and equally negative for the next: the inductor stores energy, then returns it. The 600 VA of apparent power is entirely reactive. The wires still carry 5 A and still heat up, which is why utilities penalize loads with a poor power factor.
Name it
Power in AC circuits
Instantaneous power. With and (V and I are RMS values, φ the angle of the load's impedance):
a constant plus a part at twice the frequency that averages to zero.
Three powers:
| Formula | Unit | Meaning | |
|---|---|---|---|
| real (active) power P | W | average power doing work or making heat | |
| reactive power Q | VAR | power sloshing into fields and back | |
| apparent power S | VA | what the wires and transformers must carry |
They form the power triangle: . In complex form, (A3.21), using RMS phasors.
For a load of impedance : and . Inductive loads (motors, transformers) have ; capacitive ones have .
Power factor. , described as lagging (inductive) or leading (capacitive). A motor might run at 0.8 lagging; a resistive heater at 1.
Correction. A capacitor across an inductive load supplies the reactive power locally, so the line carries less current for the same real power. To cancel at voltage (RMS) and frequency :
Factories install banks of capacitors for exactly this.
Worked example
A load draws 5 A from 230 V with the current lagging by 30°. Find P, Q and S.
Show the solution
- Apparent power.
- Real power.
- Reactive power.
- Power factor. The power factor is , or 0.87.
Answer P = 996 W, Q = 575 VAR and S = 1150 VA, at a power factor of 0.87.
Worked example
A 30 + j40 Ω load is connected to 100 V. Find the current and the powers.
Show the solution
- Impedance magnitude.
- Current.
- Real power.
- Reactive power.
- Power factor.
Answer 2 A flows, with P = 120 W, Q = 160 VAR and a power factor of 0.6.
Worked example
A wattmeter reads 720 W on a load drawing 8 A from 120 V. What are its power factor and reactive power?
Show the solution
- Apparent power.
- Power factor.
- Reactive power.
- What the meters give. A wattmeter and an ammeter and voltmeter together are all you need to find a load's whole power triangle.
- What they can't tell. They don't show whether the load is inductive or capacitive; that takes a phase measurement.
Answer a power factor of 0.75 and 635 var of reactive power.
Check
A load draws 5 A RMS from 120 V RMS, with the current lagging by 60°. How much real power does it consume?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
Same load: 120 V, 5 A, lagging by 60°. What is its reactive power?
Write units the way you normally would: 1.5 VAR, 1500 mVAR and 0.0015 kVAR are the same answer.
Check
A load takes 8 kW of real power and 4 kVAR of reactive power. What is its power factor?
Check
A load of 10 + j30 Ω carries 5 A RMS. How much real power does it consume?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A motor on a 120 V, 60 Hz supply draws 2 kVAR of reactive power. What capacitor across it would cancel that?
Write units the way you normally would: 1.5 µF, 1500 nF and 0.0015 mF are the same answer.
Check
A load draws 2 A from 120 V, and a wattmeter reads 0.8 of the volt-amperes.
(a)
What real power does it take?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
(b)
What's its reactive power?
Check
A load at voltage V draws current I lagging by angle p (radians).
Step 1
What's its apparent power?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
Real power?
Step 3
Reactive power?
Explain why
Why does an inductive load draw more current from the supply than its real power alone would need, and how does a capacitor help?
An inductive load's current lags the voltage, so for part of each cycle it's absorbing energy into its magnetic field and for part it's returning it. That back-and-forth reactive power does no work, but the current carrying it still flows through the supply wires, so the total current is larger than the real power requires. A capacitor nearby has the opposite phase: it absorbs energy when the inductor returns it and gives it back when the inductor wants it. The reactive power then circulates locally between the two, and the supply only delivers the real power, at a lower current.
Practice
Keep practicing
9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.