C3 · Lesson 16 · AC power

Power that does work, and power that only sloshes

Multiply the RMS voltage and current of a motor and you get a number in volt-amperes, but the electricity meter charges for less than that. Part of the current flows into the motor's magnetic field and back out again each cycle, doing no work but still heating the wires. Utilities care about that sloshing power, called reactive power, because their cables and transformers must carry it. The ratio of useful power to the total is the power factor.

Play

  • The curves are a voltage, a current lagging it by φ, and their product, the instantaneous power p(t). The dashed line is p's average.
  • At φ = 0, is p(t) ever negative? Now raise φ toward 90°. What happens to the average, and to the parts where p dips below zero?
  • The readouts give the real power P, the reactive power Q and the apparent power S.

Predict

A 120 V supply drives an ideal inductor, drawing 5 A RMS. What average power does it consume?

Name it

Power in AC circuits

Instantaneous power. With v=2Vcos⁡ωt and i=2Icos⁡(ωt−ϕ) (V and I are RMS values, φ the angle of the load's impedance):

p(t)=vi=VIcos⁡ϕ+VIcos⁡(2ωt−ϕ)

a constant plus a part at twice the frequency that averages to zero.

Three powers:

FormulaUnitMeaning
real (active) power PVIcos⁡ϕWaverage power doing work or making heat
reactive power QVIsin⁡ϕVARpower sloshing into fields and back
apparent power SVIVAwhat the wires and transformers must carry

They form the power triangle: S2=P2+Q2. In complex form, 𝐒=P+jQ=𝐕𝐈* (A3.21), using RMS phasors.

For a load of impedance R+jX: P=I2R and Q=I2X. Inductive loads (motors, transformers) have Q>0; capacitive ones have Q<0.

Power factor. pf=P/S=cos⁡ϕ, described as lagging (inductive) or leading (capacitive). A motor might run at 0.8 lagging; a resistive heater at 1.

Correction. A capacitor across an inductive load supplies the reactive power locally, so the line carries less current for the same real power. To cancel Q at voltage V (RMS) and frequency f:

C=Q2πfV2

Factories install banks of capacitors for exactly this.

Worked example

A load draws 5 A from 230 V with the current lagging by 30°. Find P, Q and S.

Show the solution
  1. Apparent power. S=230×5=1150VA
  2. Real power. P=Scos⁡30°=996W
  3. Reactive power. Q=Ssin⁡30°=575VAR
  4. Power factor. The power factor is cos⁡30°, or 0.87.

Answer P = 996 W, Q = 575 VAR and S = 1150 VA, at a power factor of 0.87.

Worked example

A 30 + j40 Ω load is connected to 100 V. Find the current and the powers.

Show the solution
  1. Impedance magnitude. |Z|=302+402=50Ω
  2. Current. I=10050=2A
  3. Real power. P=I2R=22×30=120W
  4. Reactive power. Q=I2X=22×40=160VAR
  5. Power factor. pf=R|Z|=0.6

Answer 2 A flows, with P = 120 W, Q = 160 VAR and a power factor of 0.6.

Worked example

A wattmeter reads 720 W on a load drawing 8 A from 120 V. What are its power factor and reactive power?

Show the solution
  1. Apparent power. S=VI=960VA
  2. Power factor. pf=PS=720960=0.75
  3. Reactive power. Q=S2−P2=9602−7202=635var
  4. What the meters give. A wattmeter and an ammeter and voltmeter together are all you need to find a load's whole power triangle.
  5. What they can't tell. They don't show whether the load is inductive or capacitive; that takes a phase measurement.

Answer a power factor of 0.75 and 635 var of reactive power.

Check

A load draws 5 A RMS from 120 V RMS, with the current lagging by 60°. How much real power does it consume?

Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.

Check

Same load: 120 V, 5 A, lagging by 60°. What is its reactive power?

Write units the way you normally would: 1.5 VAR, 1500 mVAR and 0.0015 kVAR are the same answer.

Check

A load takes 8 kW of real power and 4 kVAR of reactive power. What is its power factor?

Check

A load of 10 + j30 Ω carries 5 A RMS. How much real power does it consume?

Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.

Check

A motor on a 120 V, 60 Hz supply draws 2 kVAR of reactive power. What capacitor across it would cancel that?

Write units the way you normally would: 1.5 µF, 1500 nF and 0.0015 mF are the same answer.

Check

A load draws 2 A from 120 V, and a wattmeter reads 0.8 of the volt-amperes.

(a)

What real power does it take?

Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.

(b)

What's its reactive power?

Check

A load at voltage V draws current I lagging by angle p (radians).

Step 1

What's its apparent power?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does an inductive load draw more current from the supply than its real power alone would need, and how does a capacitor help?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.