C3 · Lesson 17 · Power factor correction
Cancelling reactive current with capacitors
A workshop full of motors draws more current than its power alone requires, because motors are inductive: part of their current lags the voltage and only shuttles energy back and forth. That reactive current still flows through every cable, transformer and meter, heating them and using up their capacity, and utilities charge large customers for it. The fix is a bank of capacitors whose leading current cancels the motors' lagging current, supplying the reactive power locally. Sizing that bank uses the power triangle of lesson 16.
- The power triangle on the complex plane: real power along the horizontal axis, reactive power up. The longer arrow is the load alone; the other is with the correction capacitor.
- Raise the capacitance. The reactive part shrinks, the arrow swings toward the real axis, and the power factor rises toward 1.
- Too much capacitance overcorrects: the arrow swings below the axis and the power factor falls again, now leading.
Predict
A 10 kW load at power factor 0.7 is corrected to 0.95. By roughly what fraction do the losses in its supply cable fall?
About 45%. The current for the same real power goes as , so it falls by a factor of , and cable losses, , by : almost half the losses disappear, with no change to the work the motors do.
Name it
The problem
A load drawing real power at power factor (lagging, for inductive loads) also draws reactive power
and its current is : larger than the the work needs. The extra current costs cable capacity and losses all the way back to the generator.
The fix
A capacitor across the load draws leading current, which supplies reactive power (with RMS). To bring the power factor from to :
The real power is unchanged; only the reactive part shrinks.
Practice
- Correct to about 0.95, not 1: the last few percent need a lot more capacitance for little gain, and full correction risks overcorrecting when loads switch off.
- Large plants switch capacitor banks in steps as the load changes, or use electronic compensators.
- Capacitors and the supply's inductance form a resonant circuit; if it lands near a harmonic of 50 or 60 Hz (lesson 20), it can amplify distortion, so banks often include tuning inductors.
Worked example
A 10 kW load runs at power factor 0.7 from 230 V, 50 Hz. What capacitor raises it to 0.95, and what happens to the current?
Show the solution
- Reactive power before.
- Reactive power after.
- The capacitor supplies the difference.
- Capacitance.
- Current before.
- Current after.
Answer a 416 µF capacitor, and the current falls from 62.1 A to 45.8 A.
Worked example
What apparent power must the supply provide before and after?
Show the solution
- Before. Apparent power is , so
- After.
- What it frees up. The transformer feeding the plant could now carry about a third more load.
Answer 14.3 kVA before and 10.5 kVA after.
Worked example
A factory draws 50 kW at power factor 0.75. How much capacitive reactive power raises it to 0.95, and how much does the apparent power fall?
Show the solution
- Reactive power to supply. Since , the capacitors must supply
- Apparent power before.
- Apparent power after. That's 21% less current in every cable and transformer feeding the plant.
- Why utilities care. Utilities bill large customers for poor power factor for exactly this reason.
Answer 27.7 kvar of capacitors, and the apparent power falls from 66.7 kVA to 52.6 kVA, 21% less.
Check
A load takes 20 kW at power factor 0.6, lagging. How much reactive power does it draw?
Write units the way you normally would: 1.5 kVAR, 1500 VAR and 0.0015 MVAR are the same answer.
Check
A 10 kW load is to be corrected from pf 0.65 to 0.98. What capacitive reactive power is needed?
Write units the way you normally would: 1.5 kVAR, 1500 VAR and 0.0015 MVAR are the same answer.
Check
What capacitance supplies 5 kVAR at 230 V RMS and 60 Hz?
Write units the way you normally would: 1.5 µF, 1500 nF and 0.0015 mF are the same answer.
Check
A 5 kW load at pf 0.8 runs from 230 V (single phase). What current does it draw?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Correcting a load from pf 0.6 to 0.9, with the same real power, cuts the cable losses by what percentage?
Check
What apparent power does a 5 kW load at pf 0.7 draw?
Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.
Check
A 50 kW load runs at power factor 0.65 and is to be corrected to 0.97.
(a)
How much capacitive reactive power is needed?
Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.
(b)
By what percentage does the supply current fall?
Check
A load P at power factor a, corrected to b.
Step 1
What's its reactive power before?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
After?
Step 3
What must the capacitors supply?
Explain why
Why does a capacitor connected across an inductive load reduce the current in the supply cable, even though the load itself draws exactly the same current as before?
The load's current has two parts: one in phase with the voltage, doing the work, and one lagging by 90°, shuttling energy into and out of the motor's magnetic field. A capacitor draws a current that leads the voltage by 90°, opposite to the lagging part. At the junction, the capacitor's current supplies the load's reactive current locally: energy sloshes between the capacitor and the motor instead of travelling back and forth along the cable. The cable then carries mostly the in-phase part, so its current, and its losses, fall.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.