C3 AC circuits · Practice
Power factor correction
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A load takes 20 kW at power factor 0.6, lagging. How much reactive power does it draw?
Write units the way you normally would: 1.5 kVAR, 1500 VAR and 0.0015 MVAR are the same answer.
Check
A 10 kW load is to be corrected from pf 0.65 to 0.98. What capacitive reactive power is needed?
Write units the way you normally would: 1.5 kVAR, 1500 VAR and 0.0015 MVAR are the same answer.
Check
What capacitance supplies 5 kVAR at 230 V RMS and 60 Hz?
Write units the way you normally would: 1.5 µF, 1500 nF and 0.0015 mF are the same answer.
Check
A 5 kW load at pf 0.8 runs from 230 V (single phase). What current does it draw?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Correcting a load from pf 0.6 to 0.9, with the same real power, cuts the cable losses by what percentage?
Check
What apparent power does a 5 kW load at pf 0.7 draw?
Write units the way you normally would: 1.5 kVA, 1500 VA and 0.0015 MVA are the same answer.
Check
A 50 kW load runs at power factor 0.65 and is to be corrected to 0.97.
(a)
How much capacitive reactive power is needed?
Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.
(b)
By what percentage does the supply current fall?
Check
What phase angle does a power factor of 0.8 mean?
Check
How much reactive power does 100 µF supply at 230 V, 60 Hz?
Write units the way you normally would: 1.5 kVAR, 1500 VAR and 0.0015 MVAR are the same answer.
Check
A load draws 3 kW and 4 kVAR. What is its power factor?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in C3