C3 · Lesson 19 · Split-phase power and home wiring

Two 120 V legs and a 240 V pair, what the neutral carries, and what happens when it breaks

A North American house gets three wires from the pole: two "hot" legs and a neutral. Lamps and outlets use 120 V between a hot and the neutral; a dryer, range or heat pump uses 240 V between the two hots. Lesson 18 showed how three phases share their return; split-phase power does something similar with two legs that are exactly opposite, so the neutral carries only the difference between them. That's efficient until the neutral connection corrodes or breaks, when some rooms' lights glow brighter and others dim, and electronics on the bright side can be destroyed. The same arithmetic sizes the wires: how much voltage a long run loses, and why big loads run on 240 V.

  • The pole transformer's secondary is drawn as two 120 V rms sources (170 V peak) in series, with the center tap grounded. A 1200 W load (12 Ω) sits on leg 1, a 600 W load (24 Ω) on leg 2, and the neutral wire runs from the center tap to the point where the two loads meet.
  • With a good neutral (a fraction of an ohm), each load sees its 170 V peak. Slide the neutral's resistance up toward an open connection and watch the voltages separate: the two loads end up in series across 240 V.

Predict

A house's neutral connection fails open. Leg 1 has 1200 W of heaters turned on; leg 2 has only a 60 W lamp. Roughly what voltage does the lamp see?

Name it

Split-phase service

The distribution transformer's secondary has a center tap. Each end, L1 and L2, is 120 V rms from the center, and they're 180° apart, so L1 to L2 is 240 V. The center tap is the neutral, bonded to earth at the transformer and at the house's service panel.

What the neutral carries

Loads on L1 return current through the neutral in one direction, loads on L2 in the other. For resistive loads, the neutral current is

IN=|I1−I2|

so a perfectly balanced house puts no current on the neutral. Loads wired from L1 to L2 at 240 V draw from both hots and never touch the neutral. With reactive loads, the currents are phasors: since the two legs' voltages are opposite, IN=|I1e−jφ1−I2e−jφ2|, with φ each load's power-factor angle.

The open neutral

If the neutral opens between the panel and the transformer, the 120 V loads on the two legs end up in series across 240 V. The voltage divides by impedance: with resistive loads of power ratings P1 and P2 (at 120 V), leg 2's loads get

V2=240P1P1+P2

so the lightly loaded leg sees the higher voltage.

Voltage drop

A branch circuit's drop is its current times the round-trip resistance of its wire: hot out, neutral back. Copper 14, 12 and 10 AWG have about 8.28, 5.21 and 3.28 mΩ per meter at 20 °C. The U.S. electrical code (NEC) recommends no more than 3% drop on a branch circuit and 5% overall, and it pairs 15 A breakers with 14 AWG and 20 A with 12 AWG. For the same power, a 240 V load draws half the current of a 120 V one, so the same wire loses a quarter of the percentage.

Neutral and ground

The neutral is a current-carrying conductor; the equipment ground isn't. They're bonded together only at the service panel, so normal return current flows on the neutral alone, and the ground carries current only during a fault, long enough to trip the breaker. A GFCI compares the hot and neutral currents and trips when they differ by about 5 mA (4 to 6 mA), which means current is leaking somewhere else, possibly through a person. Europe uses a different system: 230 V from each phase of a 400 V three-phase supply to neutral.

Worked example

A house runs a 1200 W heater on L1, a 600 W heater on L2 and a 4800 W dryer element from L1 to L2. Find each hot's current and the neutral's.

Show the solution
  1. Heater on L1. I1=1200120=10A
  2. Heater on L2. I2=600120=5A
  3. Dryer. It draws its current through both hots: ID=4800240=20A
  4. Hot currents. So L1 carries 10 + 20 = 30 A, and L2 carries 5 + 20 = 25 A.
  5. Neutral. The neutral carries only IN=10−5=5A
  6. Why the dryer adds nothing. The dryer adds nothing to the neutral: its current goes out on one hot and back on the other.

Answer L1 carries 30 A, L2 carries 25 A, and the neutral carries 5 A.

Worked example

In the same house, minus the dryer, the neutral opens. What voltage and power does each heater get?

Show the solution
  1. Heater resistances. At 120 V, R=V2/P: R1=12021200=12ΩR2=1202600=24Ω
  2. Series current. In series across 240 V they carry I=24036=6.67A
  3. Voltage across each. V1=6.67×12=80VV2=6.67×24=160V
  4. Power in the 600 W heater. P2=160224=1067W 78% over its rating.
  5. Power in the 1200 W heater. P1=80212=533W
  6. What survives. A heater may survive that for a while; a TV power supply rated 132 V maximum won't.

Answer the 1200 W heater gets 80 V and 533 W, and the 600 W heater gets 160 V and 1067 W, 78% over its rating.

Worked example

A 15 A load runs on 30 m of 12 AWG cable from the panel at 120 V. What's the voltage drop? And a 4800 W, 240 V load on 30 m of 10 AWG?

Show the solution
  1. Resistance of the 12 AWG run. The round trip is 60 m, so R=60×5.21mΩ=0.313Ω
  2. Drop on the 15 A load. ΔV=15×0.313=4.69V That's 3.9% of 120 V: over the 3% recommendation, so a run this long should use 10 AWG.
  3. Drop on the 240 V load. It draws 20 A through two 30 m conductors of 3.28 mΩ/m: ΔV=20×60×0.00328=3.94V only 1.6% of 240 V.
  4. The same load at 120 V. It would draw 40 A and lose 7.9 V, 6.6%.
  5. Why the higher voltage helps. Doubling the voltage halves the current, halves the drop and doubles the base it's compared with.

Answer the 15 A load loses 4.69 V (3.9%), and the 240 V load loses 3.94 V (1.6%).

Check

A house draws 1200 W of resistive load on L1 and 300 W on L2, at 120 V each. What current does the neutral carry?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

L1 has 1500 W of 120 V loads, L2 has 500 W, and a 7200 W load runs from L1 to L2 at 240 V.

(a)

What current does L1 carry?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

And the neutral?

Check

The neutral opens while L1 has 1200 W of resistive load (rated at 120 V) and L2 has 100 W.

(a)

What voltage does L2's load see?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

(b)

What power does L2's load dissipate?

Check

A 15 A load runs at 120 V on 15 m of cable with 3.28 mΩ/m conductors. What percentage of 120 V is lost in the wiring?

Check

L1 carries 12 A at power factor 0.9 lagging, and L2 carries 6 A at power factor 0.6 lagging.

(a)

What's the neutral current's magnitude?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

Why is the neutral bonded to the equipment ground only at the main service panel, and not at every outlet?

Check

Find the voltage across leg 2's loads with the neutral open, from the loads' 120 V power ratings.

Step 1

What is leg 2's resistance?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Check

Model a split-phase panel. The service conductors (each hot and the neutral) have Rs = 0.05 Ω from the transformer. Write panel(loads), where loads is a list of (leg, watts) with leg 1, 2 or 12 (a 240 V load) and watts rated at 120 V or 240 V, all resistive. Solve the circuit with the transformer as two ideal 120 V sources and return (v1, v2), the voltages across leg 1's and leg 2's 120 V loads. Use numpy.linalg.solve on the node equations. Also set open_v to panel_open([(1, 1200), (2, 600)])'s result for an open neutral (the neutral conductor's resistance infinite).

Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.

Explain why

An electrician finds that when a 1500 W space heater turns on in one room, the lights in another room get noticeably brighter. Explain what's probably wrong, and why it's dangerous.

Practice