D1 · Lesson 4 · Grid frequency and load balance

Why the grid's frequency tracks the balance of generation and load, the spinning inertia that slows a frequency change, droop control that shares a load step among generators, and how big a disturbance the grid can ride through

The grid stores almost no electrical energy, so every watt consumed must be generated at the same instant. The only buffer is the kinetic energy of thousands of generator rotors spinning in synchrony at exactly 60 Hz (50 Hz in much of the world). When a load switches on, the energy comes out of that rotation, and the whole grid's frequency starts to fall. Operators watch the frequency as a direct measure of whether supply matches demand, and governors on the generators respond to it automatically within seconds.

  • The grid's frequency after a sudden load increase ΔP, in a simplified model: inertia constant H (seconds of rated power stored as rotation) and governor droop R (the fractional speed change that brings a generator from no load to full output).
  • Right after the step the frequency falls at a rate set by inertia; it settles where the governors' extra output matches the load, a deviation set by droop.
  • Real grids dip lower before recovering, because governors and turbines take seconds to respond.

Predict

A 10 GW system with an inertia constant of 5 s suddenly loses 100 MW of generation. How fast does its frequency start falling?

Name it

Synchronous speed

A generator with p poles turns at n=120f/p rpm: 3600 rpm for a two-pole steam turbine at 60 Hz, 150 rpm for a 48-pole hydro unit. All synchronous generators on a grid share one electrical frequency.

Inertia

The inertia constant H is the rotating kinetic energy divided by the machine's rating, typically 2 to 9 s. A power imbalance ΔP changes the frequency at first at the rate of change of frequency

ROCOF=ΔPf02HS

Droop

Each governor raises its output in proportion to the frequency drop: a droop R of 5% means full output change for a 5% speed change. With all generators participating, a load step settles at

Δf=ΔPSRf0

shared in proportion to ratings. Slower secondary control (automatic generation control) then restores 60 Hz by adjusting setpoints over minutes.

Worked example

For the 10 GW system with 5% droop, where does the frequency settle after the 100 MW loss, and how big a loss would drop it by 0.5 Hz?

Show the solution
  1. Frequency drop. Δf=10010000×0.05×60=0.03Hz so the frequency settles at 59.97 Hz.
  2. Loss for a 0.5 Hz drop. ΔP=0.5×100000.05×60=1667MW
  3. How fast it settles. In this simple model the frequency settles with a time constant of 2HR=0.5s

Answer it settles at 59.97 Hz, and a 1667 MW loss would drop it by 0.5 Hz.

Worked example

The grid runs at 59.98 Hz for an hour. How much time does a clock that counts cycles lose?

Show the solution
  1. Cycles counted. In the hour the clock counts 3600×59.98 cycles.
  2. Time shown. It takes each 60 cycles as a second: t=3600×59.9860=3598.8s which is 1.2 s slow.
  3. Correcting it. Grid operators correct such time error by running slightly fast later.

Answer the clock loses 1.2 s.

Worked example

A 1000 MW, two-pole turbine-generator has H = 6 s. How much kinetic energy does it store, and what is its moment of inertia?

Show the solution
  1. Stored energy. E=HS=6×1000MW·s=6GJ
  2. Speed. Two poles at 60 Hz turn at 3600 rpm, ω=377 rad/s.
  3. Moment of inertia. J=2E/ω2=2×6×1093772=84400kg·m2

Answer it stores 6 GJ, and its moment of inertia is 84,400 kg·m².

Check

A 5000 MW system with H = 6 s loses 300 MW. What's the initial rate of change of frequency (60 Hz grid)?

Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.

Check

With 0.05 droop on all generators of a 5000 MW system, how far does a 300 MW load step drop the frequency in steady state?

Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.

Check

How fast does a 2-pole generator turn on a 50 Hz grid?

Check

A 500 MW generator has H = 5 s. How much kinetic energy do its rotor and turbine store?

Write units the way you normally would: 1.5 MJ, 1500 kJ and 0.0015 GJ are the same answer.

Check

The grid runs at 59.98 Hz for 1 hours.

(a)

How far off is a clock that counts cycles?

Write units the way you normally would: 1.5 s and 1500 ms are the same answer.

(b)

How many cycles occur?

Check

A 600 MW, 4-pole generator on a 60 Hz grid has H = 3 s.

(a)

What kinetic energy does it store?

Write units the way you normally would: 1.5 GJ, 1500 MJ and 0.0015 TJ are the same answer.

(b)

At what speed does it turn?

(c)

What is its moment of inertia?

Explain why

Why does the grid's frequency tell operators whether generation matches load?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.