D1 Power systems and the grid · Practice
Grid frequency and load balance
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A 5000 MW system with H = 6 s loses 300 MW. What's the initial rate of change of frequency (60 Hz grid)?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
With 0.05 droop on all generators of a 5000 MW system, how far does a 300 MW load step drop the frequency in steady state?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
How fast does a 2-pole generator turn on a 50 Hz grid?
Check
A 500 MW generator has H = 5 s. How much kinetic energy do its rotor and turbine store?
Write units the way you normally would: 1.5 MJ, 1500 kJ and 0.0015 GJ are the same answer.
Check
The grid runs at 59.98 Hz for 1 hours.
(a)
How far off is a clock that counts cycles?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
How many cycles occur?
Check
A 600 MW, 4-pole generator on a 60 Hz grid has H = 3 s.
(a)
What kinetic energy does it store?
Write units the way you normally would: 1.5 GJ, 1500 MJ and 0.0015 TJ are the same answer.
(b)
At what speed does it turn?
(c)
What is its moment of inertia?
Check
ROCOF: 10 MW lost, 1000 MW system, H = 9 s?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
Droop deviation: 10 MW, 1000 MW, R = 0.08?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
Speed: 2 poles, 50 Hz?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in D1