D15 of 9
0 XP
  1. Hook
  2. Play
  3. Predict
  4. Name it
  5. Check
  6. Explain

D1 · Lesson 5 · Power flow and reactive power

How real power flows between two points of a grid according to the angle between their voltages, the maximum a line can carry, reactive power and its link to voltage, and power-factor correction with capacitors

On a transmission line, power doesn't flow "downhill" from high voltage to low: both ends are held near the same voltage magnitude. Real power flows because one end's voltage leads the other's in phase, and a line can carry only so much before that angle reaches its limit. Reactive power is the other half of the story: it sloshes back and forth without doing work, but it sets the voltage, and too little of it was behind several of the largest blackouts.

  • Real power sent over a lossless line of reactance X between two buses with voltages V1 and V2, against the angle δ between them: P=V1V2sin⁡δ/X.
  • Power peaks at δ = 90°, the steady-state stability limit; operators keep angles well below it.
  • Raising the voltages or lowering the reactance (shorter lines, more circuits, series capacitors) raises the limit.

Predict

Two 230 kV buses are joined by a line of 50 Ω reactance. What's the most real power it can carry in steady state?

Name it

Real power and angle

Across a line of reactance X (resistance neglected),

P=V1V2Xsin⁡δ

with δ the angle by which the sending voltage leads the receiving one. With voltages in kV and X in ohms, P comes out in MW for three-phase line-to-line voltages.

Reactive power and voltage

The reactive power received at end 2 is

Q2=V1V2cos⁡δ−V22X

Reactive power flows from the higher voltage toward the lower one, roughly in proportion to the voltage difference, so voltage is controlled by supplying reactive power locally: generators' excitation, capacitor banks, and inverters.

Power factor

A load drawing P with power factor cos φ also draws reactive power Q=Ptan⁡φ, which loads the wires without delivering energy. A shunt capacitor supplying QC=P(tan⁡φ1−tan⁡φ2) raises the power factor from cos⁡φ1 to cos⁡φ2.

Worked example

On the 230 kV, 50 Ω line, what angle carries 500 MW, and what reactive power does the receiving end absorb at 30° with equal voltages?

Show the solution
  1. Angle for 500 MW. sin⁡δ=500×502302=0.473 so δ = 28.2°.
  2. Reactive power at 30°. Q2=2302cos⁡30°−230250=−142Mvar
  3. What the sign means. The receiving end must supply 142 Mvar into the line to hold its voltage, which is why heavily loaded lines need reactive support.

Answer an angle of 28.2° carries 500 MW, and at 30° the receiving end must supply 142 Mvar (Q2 = −142 Mvar).

Worked example

A 1 MW load runs at power factor 0.8. What capacitor raises it to 0.95?

Show the solution
  1. Power-factor angles. A power factor of 0.8 is an angle of 36.9°, and 0.95 is 18.2°. Their tangents are tan⁡36.9°=0.750tan⁡18.2°=0.329
  2. Capacitor size. QC=1000×(0.750−0.329)=421kvar

Answer a 421 kvar capacitor raises the power factor to 0.95.

Worked example

Two 138 kV buses are joined by a 40 Ω line. What power flows at a 10° angle, and what is the most the line can carry?

Show the solution
  1. Power at 10°. P=V1V2sin⁡δ/X=1382/40×sin⁡10°=476×0.174=82.7MW
  2. Maximum. At 90° the sine is 1, so the most the line can carry is 476 MW.
  3. Margin. In practice angles stay well below that to keep a margin for stability.

Answer 82.7 MW flows at 10°, and the line can carry at most 476 MW.

Check

Buses at 230 kV and 115 kV are joined by a 100 Ω line, with an angle of 60° between them. What real power flows?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

Check

Two 230 kV buses are joined by a 20 Ω line. What angle carries 300 MW?

Check

What's the steady-state transfer limit of a 150 Ω line between 230 kV and 115 kV buses?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

Check

A 500 kW load runs at power factor 0.7. What capacitor raises it to 1?

Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.

Check

Two 138 kV buses are joined by a line of 20 Ω reactance, at an angle of 30°.

(a)

What power flows?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

What is the most the line could carry?

Check

A 2 MW load runs at power factor 0.7, to be corrected to 1 with capacitors.

(a)

What reactive power does it draw now?

Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.

(b)

What capacitor rating does the correction need?

Explain why

Why is a transmission line's power limited by the angle between its end voltages as well as by its wires' heating?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.