D1 Power systems and the grid · Practice
Power flow and reactive power
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
Buses at 230 kV and 115 kV are joined by a 100 Ω line, with an angle of 60° between them. What real power flows?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Two 230 kV buses are joined by a 20 Ω line. What angle carries 300 MW?
Check
What's the steady-state transfer limit of a 150 Ω line between 230 kV and 115 kV buses?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 500 kW load runs at power factor 0.7. What capacitor raises it to 1?
Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.
Check
Two 138 kV buses are joined by a line of 20 Ω reactance, at an angle of 30°.
(a)
What power flows?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
What is the most the line could carry?
Check
A 2 MW load runs at power factor 0.7, to be corrected to 1 with capacitors.
(a)
What reactive power does it draw now?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
What capacitor rating does the correction need?
Check
P: 69 and 69 kV, 300 Ω, 60°?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Transfer limit: 69 and 69 kV, 300 Ω?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Correction: 10 kW from pf 0.6 to 0.99?
Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in D1