D1 · Lesson 1 · From power plant to outlet

The journey of electric power from a generator through step-up transformers, high-voltage transmission, substations and distribution feeders to the 120/240 V outlet, and why each stage uses the voltage it does

The electricity in a wall outlet was, a fraction of a second earlier, spinning a generator tens or hundreds of kilometers away. Between the two it was transformed up to hundreds of thousands of volts, carried across the country on steel towers, and stepped down several times through substations and pole transformers. Every one of those voltage changes exists for the same reason: the power lost in a wire grows with the square of the current, and higher voltage carries the same power with less current.

  • The voltage at each stage of a typical North American system: generator (20 kV), transmission (345 kV), subtransmission (69 kV), distribution (12.47 kV), and the service to a home (240 V).
  • The second set of stems shows the line current each stage needs to carry the power P, for a three-phase system: I=P/(3V).
  • High voltage carries the bulk power with modest currents; only near the customer does the current become large, over short distances.

Predict

A 100 MW power plant sends its output over a line with 10 Ω per phase. How much less power is lost if the line runs at 345 kV instead of the generator's 20 kV?

Name it

The stages

  • Generation: synchronous generators make three-phase power at 10 to 25 kV.
  • Transmission: step-up transformers raise it to 115 to 765 kV for long distances.
  • Subtransmission: substations step down to 35 to 138 kV for regional delivery.
  • Distribution: substations feed 4 to 35 kV lines (12.47 kV is common) along streets.
  • Service: a pole or pad transformer steps down to 120/240 V split phase for homes, or 208 or 480 V three-phase for businesses.

Why high voltage

A balanced three-phase line carrying power P at line voltage V and power factor 1 needs current

I=P3V

per phase, and loses 3I2R in its conductors. For the same power and wire, loss scales as 1/V2. Above a few hundred kilovolts, insulation, tower size and corona discharge set the practical limit.

Worked example

A 100 MW plant transmits at 345 kV. What current flows, and what fraction is lost in a line of 10 Ω per phase?

Show the solution
  1. Line current. I=100MW3×345kV=167A
  2. Line loss. Ploss=3×1672×10=0.84MW which is 0.84% of the power.
  3. Compare with 20 kV. At 20 kV the same line would need 2887 A and lose 250 MW.

Answer 167 A flows, and the line loses 0.84 MW, 0.84% of the power.

Worked example

Send the same 100 MW over the same 10 Ω-per-phase line at 138 kV instead of 345 kV. What current flows, and what fraction is lost?

Show the solution
  1. Line current. I=100MW3×138kV=418A
  2. Line loss. Ploss=3I2R=3×4182×10=5.25MW which is 5.25% of the power.
  3. Compare with 345 kV. At 345 kV the current is 167 A and the loss 0.84 MW. The ratio is (345/138)2=6.25 so loss falls with the square of the voltage.

Answer 418 A flows, and the line loses 5.25 MW, 5.25% of the power.

Worked example

A pole transformer takes 7.2 kV (one phase of a 12.47 kV feeder, line to neutral) down to 240 V. What is its turns ratio, and what current does it deliver at its 25 kVA rating?

Show the solution
  1. Turns ratio. 7200/240=30
  2. Secondary current at 25 kVA. I2=25000/240=104A
  3. Primary current. I1=104/30=3.5A
  4. What it serves. A handful of houses share one such transformer.

Answer the turns ratio is 30, and at 25 kVA the transformer delivers 104 A at 240 V while drawing only 3.5 A from the 7.2 kV line.

Check

A three-phase line at 69 kV carries 100 MW at unity power factor. What current flows in each phase?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A line's voltage is raised from 69 kV to 230 kV while carrying the same power. By what factor do its losses fall?

Check

A 138 kV line with 10 Ω per phase carries 50 MW. How much power is lost?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

Check

What percentage of the 50 MW is lost on that 138 kV line with 10 Ω per phase?

Check

200 MW is sent over a three-phase line at 69 kV with 20 Ω per phase.

(a)

What current flows?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

What fraction of the power is lost?

Check

A transformer takes 7200 V down to 240 V and is rated 75 kVA.

(a)

What is its turns ratio?

(b)

What secondary current does it deliver at full rating?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Explain why

Why does the power grid use such high transmission voltages?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.