A three-phase line at 69 kV carries 100 MW at unity power factor. What current flows in each phase?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A line's voltage is raised from 69 kV to 230 kV while carrying the same power. By what factor do its losses fall?
Check
A 138 kV line with 10 Ω per phase carries 50 MW. How much power is lost?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
What percentage of the 50 MW is lost on that 138 kV line with 10 Ω per phase?
Check
200 MW is sent over a three-phase line at 69 kV with 20 Ω per phase.
(a)
What current flows?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What fraction of the power is lost?
Check
A transformer takes 7200 V down to 240 V and is rated 75 kVA.
(a)
What is its turns ratio?
(b)
What secondary current does it deliver at full rating?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Line current: 1 MW at 12.47 kV?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Loss reduction from 12 kV to 115 kV?
Check
Loss: 5 MW, 69 kV, 20 Ω per phase?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.