D1 · Lesson 3 · Transformers and voltage levels

How a transformer trades voltage for current through its turns ratio, the pole transformer that feeds a house, kVA ratings, impedances seen through a transformer, and core and copper losses with the load where efficiency peaks

A transformer is two coils on an iron core, with no moving parts, and it's the reason the grid uses alternating current. It changes voltage in proportion to its turns, changes current in the inverse proportion, and does it at 98 to 99.5% efficiency. The gray can on a utility pole takes 7.2 kV from the distribution line and delivers 240 V to a few houses, and the same principle, scaled up, steps a power plant's output up to 345 kV.

  • Efficiency of a 50 kVA distribution transformer against its load, as a fraction of rated: η=xS/(xS+Pcore+x2Pcu), with constant core loss and copper loss rising as the square of the load.
  • The efficiency peaks where the two losses are equal, at x=Pcore/Pcu.
  • Utilities design distribution transformers to peak near their typical load, often well below full rating.

Predict

A pole transformer steps 7.2 kV down to 240 V and is rated 50 kVA. At full load, what current flows on the 240 V side?

Name it

The ideal transformer

With N1 turns on the primary and N2 on the secondary,

V2V1=N2N1,I2I1=N1N2

so power in equals power out. An impedance Z2 on the secondary looks like Z2(N1/N2)2 from the primary.

Ratings

Transformers are rated in volt-amperes (kVA or MVA), because their heating depends on current and voltage regardless of power factor. Rated current on a side is the rating divided by that side's voltage (by 3VL for three-phase).

Losses

  • Core loss (hysteresis and eddy currents in the iron) depends on voltage and is nearly constant whenever the transformer is energized.
  • Copper loss in the windings goes as current squared, x2Pcu at a fraction x of rated load.

Efficiency peaks where they're equal. A real transformer also has leakage reactance, usually quoted as a percent impedance, which limits fault current (lesson 6).

Worked example

The 50 kVA transformer has 150 W of core loss and 600 W of copper loss at full load. Find its efficiency at full and half load at unity power factor.

Show the solution
  1. Full load. η=5000050000+150+600=98.5%
  2. Half load. The copper loss is now 150 W: η=2500025000+150+150=98.8%
  3. Why half load is the peak. The two losses are equal at x=150/600=0.5
  4. Referred load. A 2.4 Ω load on the 240 V side looks like this from the 7.2 kV line: 2.4×302=2160Ω

Answer 98.5% at full load and 98.8% at half load, which is the peak.

Worked example

The 50 kVA transformer (150 W core loss, 600 W copper loss at full load) runs at full load for 8 hours a day and quarter load for 16. What is its efficiency over the day?

Show the solution
  1. Energy out. E=8×50+16×12.5=600kWh
  2. Core loss. It runs all day: 0.15×24=3.6kWh
  3. Copper loss. It scales with the square of the load. At full load: 0.6×8=4.8kWh and at quarter load: 0.6×0.0625×16=0.6kWh
  4. Efficiency. The losses total 9.0 kWh: η=600600+9.0=98.5%

Answer the transformer is 98.5% efficient over the day.

Worked example

A 30:1 transformer has 0.1 Ω of winding resistance referred to its secondary. What does that look like from the primary?

Show the solution
  1. Scale by the turns ratio squared. Impedances transform by the square of the turns ratio: 0.1×302=90Ω
  2. What that means. A transformer makes the load look n2 times bigger from the high-voltage side, which is why the same per-unit impedance describes it from either side.

Answer from the primary, the winding resistance looks like 90 Ω.

Check

A transformer steps 12470 V down to 120 V. What's its turns ratio, primary to secondary?

Check

A single-phase transformer rated 50 kVA has a 120 V secondary. What's its full-load secondary current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A 5 Ω load sits on the secondary of a transformer with turns ratio 10:1. What impedance does the primary see?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

Check

A 25 kVA transformer has 0.1 kW of core loss and 1.2 kW of full-load copper loss. What's its efficiency, in percent, at 0.75 of rated load and unity power factor?

Check

A 25 kVA transformer has 0.2% core loss and 4% copper loss at full load (as fractions of its rating); it runs at full load for 12 hours a day and is idle otherwise, at unity power factor.

(a)

How much energy does it deliver a day?

Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.

(b)

What is its all-day efficiency?

Check

A transformer with turns ratio 30 has 0.05 Ω on its low-voltage side.

(a)

What impedance does that look like from the high-voltage side?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

(b)

By what factor would a load on the low side appear larger?

Explain why

Why does a transformer's efficiency peak at partial load?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.