D1 Power systems and the grid · Practice
Transformers and voltage levels
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Check
A transformer steps 12470 V down to 120 V. What's its turns ratio, primary to secondary?
Check
A single-phase transformer rated 50 kVA has a 120 V secondary. What's its full-load secondary current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 5 Ω load sits on the secondary of a transformer with turns ratio 10:1. What impedance does the primary see?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A 25 kVA transformer has 0.1 kW of core loss and 1.2 kW of full-load copper loss. What's its efficiency, in percent, at 0.75 of rated load and unity power factor?
Check
A 25 kVA transformer has 0.2% core loss and 4% copper loss at full load (as fractions of its rating); it runs at full load for 12 hours a day and is idle otherwise, at unity power factor.
(a)
How much energy does it deliver a day?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
(b)
What is its all-day efficiency?
Check
A transformer with turns ratio 30 has 0.05 Ω on its low-voltage side.
(a)
What impedance does that look like from the high-voltage side?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
By what factor would a load on the low side appear larger?
Check
Turns ratio: 2400 V to 120 V?
Check
Reflected impedance: 0.5 Ω, ratio 2?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
Load fraction for peak efficiency: core 0.05 kW, full-load copper 0.2 kW?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in D1