S10 · Lesson 26 · Generator capability and excitation

The capability chart's armature, field, turbine and stability limits, how they move with terminal voltage, voltage regulators and their steady error, and how parallel generators share reactive power

Lesson 25 modeled a generator as a voltage behind a reactance. Its operator sees it as a point on a chart: real power across, reactive power up and down, inside a boundary drawn by the machine's heating and stability. Push past the boundary and a winding overheats or the rotor slips. The automatic voltage regulator moves the point up and down as the grid's voltage changes, and when several machines share a bus, something must decide who supplies the vars. This lesson draws the boundary and sets up the controls that keep a generator inside it.

  • The curves bound the reactive power of a generator with Xs = 1.2 pu and a field limit of E = 2.2 pu, rated 1 pu, at the terminal voltage V set by the slider.
  • The armature limit (solid) is a circle of radius V·I_max about the origin; the field limit (dashed) a circle about (0,−V2/Xs) of radius Emax⁡V/Xs. The machine may supply the smaller of the two.
  • At rated voltage and 0.8 pu of real power the armature limit binds at 0.6 pu of vars. At 0.95 pu voltage it drops to 0.51, just when the grid needs vars most.

Predict

A generator is limited by its armature current, and the grid voltage sags from 1.0 to 0.95 pu. What happens to the reactive power it can supply at the same real power?

Name it

The capability chart

In the P–Q plane at the terminals, at terminal voltage V:

  • Armature heating: P2+Q2≤(VImax⁡)2, a circle about the origin.
  • Field heating: the field current sets E, and P2+(Q+V2/Xs)2≤(Emax⁡V/Xs)2: a circle about (0,−V2/Xs). It limits vars at low power factor, when the machine is overexcited.
  • Turbine: a vertical line at the prime mover's maximum power.
  • Underexcitation: absorbing vars weakens the field and the machine's grip on the grid. For a machine behind Xs connected through Xe to a stiff bus, the steady-state stability limit is a circle with center (0,V22(1Xe−1Xs)) and radius V22(1Xe+1Xs), and the operating point must stay above its lower arc. Practical limits add margin and end-region heating.

Excitation control

The automatic voltage regulator (AVR) compares the terminal voltage with its setpoint and drives the exciter. With a proportional gain KA around a generator of open-circuit gain 1, the steady error is 1/(1+KA); modern static exciters reach their ceiling voltage (often two to three times rated field voltage) in milliseconds, which helps hold the machine in synchronism after faults. Over-excitation limiters let the field run above its continuous limit for tens of seconds, then pull it back.

Sharing vars

Two machines regulating the same bus voltage with pure integral control would fight over the vars. Reactive droop (reactive current compensation) lowers each machine's voltage setpoint in proportion to its vars, ΔV=−RqΔQ, so a change in demand divides in inverse proportion to the droops, just as real power divides under governor droop.

Worked example

The generator above (Xs = 1.2 pu, Emax⁡ = 2.2 pu, rated 1 pu) delivers 0.8 pu. How many vars can it supply at 1.0 and at 0.95 pu terminal voltage, and which limit binds?

Show the solution
  1. Armature limit at 1.0 pu. Q=1−0.64=0.600
  2. Field limit at 1.0 pu. Q=−0.833+1.8332−0.64=0.816 so the armature binds, at 0.60 pu.
  3. Armature limit at 0.95 pu. Q=0.9025−0.64=0.512
  4. Field limit at 0.95 pu. The field circle's center is at −0.952/1.2=−0.752 and its radius is 2.2×0.95/1.2=1.742, giving 0.795.
  5. Which binds. The armature still binds, now at 0.51 pu.

Answer 0.60 pu at 1.0 pu terminal voltage and 0.51 pu at 0.95 pu; the armature limit binds both times.

Worked example

The same machine (Xs = 1.2 pu) connects to a stiff 1 pu bus through Xe = 0.3 pu. How many vars can it absorb at 0.8 pu before reaching the steady-state stability limit, and at no load?

Show the solution
  1. Center of the stability circle. Q0=12(1/0.3−1/1.2)=1.25
  2. Its radius. r=12(1/0.3+1/1.2)=2.083
  3. At P = 0.8. The lower arc sits at Q=1.25−2.0832−0.64=−0.674pu so it can absorb 0.67 pu.
  4. At no load. Q=1.25−2.083=−0.833=−V2/Xs With no field at all, the machine absorbs V2/Xs and still holds on.

Answer it can absorb 0.67 pu at P = 0.8, and 0.833 pu (V2/Xs) at no load.

Worked example

Two generators share a bus. One has a reactive droop of 4% and the other 6% (each on its own rating, both 100 MVA). The bus needs 50 Mvar more. How do they share it?

Show the solution
  1. Same voltage change. Both machines see it: ΔV=−R1ΔQ1=−R2ΔQ2
  2. Ratio of the shares. ΔQ1/ΔQ2=R2/R1=6/4
  3. Split the 50 Mvar. The 4% machine takes 0.6 × 50 = 30 Mvar and the 6% machine 20 Mvar.
  4. Other settings. Equal droops on equal machines would split it evenly; without droop, small differences in setpoints would drive the two in opposite directions.

Answer the 4% machine supplies 30 Mvar and the 6% machine 20 Mvar.

Check

A generator rated 1 pu with Xs = 1.2 pu and a field limit of E = 1.8 pu runs at 0.8 pu and 1.05 pu terminal voltage.

(a)

What reactive power does the armature limit allow?

(b)

What does the field limit allow?

Check

A machine with Xs = 1.2 pu connects to a stiff 1 pu bus through Xe = 0.2 pu and delivers 0.9 pu.

(a)

At what reactive power (negative is absorbing) does it reach the steady-state stability limit?

Check

Two equal generators with reactive droops of 4% and 6% share a 100 Mvar increase in demand.

(a)

How much does the first one take?

Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.

Check

A proportional voltage regulator with gain 20 controls a generator of open-circuit gain 1.

(a)

What steady voltage error does it leave?

Check

A 500 MVA generator is rated to deliver its full apparent power at power factor 0.85.

(a)

What real power does that correspond to?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

How many vars can it supply at that point?

Check

A generator with Xs = 1.5 pu runs at no load and 0.9 pu terminal voltage.

(a)

How many vars can it absorb before the steady-state stability limit, with its field at zero?

Check

Why does a generator's reactive capability fall when the terminal voltage sags?

Check

A generator rated 1 pu with Xs = X and field limit E runs at real power P and terminal voltage V.

Step 1

What vars does the armature limit allow?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Check

Write q_limit(P, V, Xs, Emax, Imax): the most reactive power a generator can supply at real power P and terminal voltage V (the smaller of the armature and field limits), and q_min(P, V, Xs, Xe): the steady-state stability limit's reactive power for connection through Xe to a stiff bus.

Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.

Explain why

Why do grid operators care about generators' reactive reserves, and not just their real power reserves?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.