S10 · Lesson 46 · Inverter-based resources and the changing grid
How solar, wind and batteries connect through power electronics, falling inertia and faster frequency swings, grid-following and grid-forming inverters, synthetic inertia and fast frequency response, weak grids and short-circuit ratio, and limited fault current
Everything so far assumed that power comes from big spinning synchronous machines, whose inertia steadies frequency, whose internal voltages hold up the grid, and whose huge fault currents trip relays. Solar panels, batteries and most modern wind turbines connect through inverters instead: no inertia unless programmed, fault current limited to little more than rated, and behavior set by control software. On some grids they already supply most of the power at times, and the tools of this course are being rethought around them.
- The frequency of the system of lesson 30 after losing 5% of its generation, as a growing share of it comes from inverter-based plants that provide no inertia (H scales down with the synchronous share). Dashed: all synchronous.
- At 60% inverter-based generation the inertia is 2 s instead of 5: frequency falls 2.5 times as fast at first and the nadir deepens from −0.41 to −0.59 Hz.
- Inverters can do better than nothing: programmed to inject power in proportion to the rate of change of frequency, or simply very fast, they can arrest a fall sooner than any turbine.
Predict
A 300 MW solar plant's inverters can supply 1.2 times rated current during a fault. On a 230 kV bus, how much fault current does the plant contribute?
Rated current is 300 MW/(√3 × 230 kV) = 0.75 kA, and 1.2 times that is 0.90 kA. A synchronous machine of the same rating would deliver five to seven times rated. Relays set for big fault currents can fail to see faults on grids dominated by inverters, so protection must be redesigned around them.
Name it
Inverter-based resources
Solar, batteries and most wind turbines (type 3 doubly fed and type 4 full-converter) connect through voltage-source converters whose output is set by fast current control. Their semiconductors can't tolerate overcurrent, so fault current is held to about 1 to 1.5 pu.
Grid-following and grid-forming
- Grid-following inverters measure the grid's voltage and angle with a phase-locked loop and inject a commanded current: a controlled current source that needs a strong grid voltage to follow.
- Grid-forming inverters behave as a voltage source behind an impedance, setting their own frequency by droop or by emulating a synchronous machine. They can run islanded and stabilize weak grids, and are being adopted for batteries.
Inertia and frequency
Inverter plants add no stored kinetic energy, so as they displace synchronous units, H falls and the rate of change of frequency rises: (lesson 30). Inverters can supply synthetic inertia, power proportional to df/dt, , or fast frequency response, a quick step of power when frequency falls.
Weak grids
The short-circuit ratio at a plant's connection measures grid strength. Below about 3 a grid is weak: voltage swings with the plant's output, and grid-following controls can become unstable.
Ride-through
Grid codes require plants to stay connected through voltage and frequency excursions (low-voltage ride-through), since thousands of inverters tripping at once on a fault can turn a small event into a large loss of generation, as happened in Southern California in 2016 and 2017.
Worked example
A 50 GW system's synchronous fleet has H = 5 s. When 40% of the generation is inverter-based, what's the rate of change of frequency after a 1.5 GW loss?
Show the solution
- Remaining inertia. On the 50 GW base:
- Rate of change of frequency. against 0.18 Hz/s with an all-synchronous fleet.
- Consequence. Many protection schemes for distributed generation trip on high ROCOF, so the threshold settings have had to be raised.
Answer 0.30 Hz/s.
Worked example
A 100 MW battery should emulate H = 5 s of inertia on its own rating. How much power must it inject while frequency falls at 0.5 Hz/s?
Show the solution
- Power to inject.
- A better use. A battery can deliver its full 100 MW within a fraction of a second, so fast frequency response, a near-step of power rather than inertia emulation, is often the more effective use of it.
Answer 8.3 MW.
Worked example
A 200 MW solar plant connects at a bus with a 600 MVA short-circuit level. What is its short-circuit ratio, and what does a 300 MVA synchronous condenser with X″ = 0.2 pu (on its rating) do?
Show the solution
- Short-circuit ratio. a weak connection, where grid-following inverters risk control interactions.
- The condenser's contribution. It contributes 300/0.2 = 1500 MVA of fault level, raising the bus to 2100 MVA.
- New ratio.
- Other benefits. It also adds inertia and voltage support, which is why condensers are returning to grids with high inverter shares.
Answer an SCR of 3, which the condenser raises to 10.5.
Check
A system's synchronous units have H = 5 s. If 0.3 of the generation becomes inverter-based with no inertia, what's the system H on the same base?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A 30 GW system with H = 5 s loses 1.5 GW. What's the initial ROCOF?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
A 100 MW wind farm connects at a bus with a 1500 MVA short-circuit level. What's its short-circuit ratio?
Check
An inverter of 50 MW rating emulates H = 2 s. How much power does it inject while frequency falls at 1 Hz/s?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 100 MW inverter plant limits its fault current to 1.5 times rated. How much does it contribute at 69 kV?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A 30 GW system with H = 2.5 s must keep ROCOF below 0.8 Hz/s when it loses 4 GW. How much fast frequency response must act immediately?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 100 MW inverter plant connects at a bus with an 800 MVA short-circuit level; a synchronous condenser of 300 MVA with X″ = 0.25 pu is added there.
(a)
What was the short-circuit ratio?
(b)
What is it with the condenser?
Check
A system's synchronous units have inertia H; a fraction s of its S GW of generation is inverter-based with no inertia, and it loses P GW.
Step 1
What is the system's effective inertia constant?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is the initial ROCOF, in Hz/s?
Explain why
Why does replacing synchronous generators with inverter-based plants make frequency fall faster after a disturbance?
Right after a generator trips, nothing in the control systems has acted yet, so the missing power has to come from somewhere instantly. In a synchronous system it comes from the kinetic energy of every spinning rotor, which slows down together, and the more stored energy there is, the more slowly frequency falls for a given deficit. An inverter-based plant has no rotating mass coupled to the grid, and a grid-following inverter simply keeps injecting its commanded current, so it contributes nothing to that first response. With less total stored energy, the same deficit drains it faster, and frequency falls faster, unless the inverters are programmed to respond to frequency themselves.