S10 · Lesson 13 · Line ampacity and sag

How much current a line can carry: the conductor's heat balance of resistive and solar heating against convection and radiation, why wind matters so much, and how heating lengthens a span and lowers its sag toward the ground

Short lines are limited not by stability or voltage but by heat. Current warms the conductor, sunshine adds more, and the breeze and radiation carry it away. Too hot, and the aluminum anneals and loses strength; long before that, the conductor expands, the span sags, and the line comes too close to the trees or the ground beneath it. A line's rating is the current that keeps it within a temperature limit under assumed weather, and since the weather is rarely that bad, utilities are learning to rate lines by the actual wind.

  • The curve is a Drake ACSR conductor's ampacity (28.1 mm diameter, 0.087 Ω/km at 75 °C) at a 75 °C limit in 25 °C air with full sun, against the convective heat-transfer coefficient h set by the wind.
  • In still air (h near 5 W/m²K) it carries under 600 A; in a steady breeze (h = 15) about 890 A; at h = 30, about 1250 A.
  • The rating depends far more on the wind than on anything about the conductor, which is why static ratings assume a cautious, light wind.

Predict

A line's static rating assumes a light breeze. On a day with twice the convective cooling, about how much more current can it carry at the same temperature?

Name it

The heat balance

In steady state, per meter of conductor with diameter D at temperature Tc in air at Ta:

I2R(Tc)+qs=qc+qr
  • Resistive heating with the AC resistance at the conductor temperature (aluminum's rises about 0.4% per °C).
  • Solar heating qs=αSD, with absorptivity α and irradiance S.
  • Convective cooling qc=hπD(Tc−Ta), with h of 5 to 10 W/m²K in still air and several times that in a breeze.
  • Radiative cooling qr=ϵσπD(Tc4−Ta4), temperatures in kelvin.

So the ampacity at a temperature limit is

I=qc+qr−qsR(Tc)

Real ratings (IEEE 738, CIGRE) compute h from wind speed and direction. The conductor's heat capacity gives a thermal time constant of 10 to 20 minutes, which lets operators run above the steady rating for short emergencies.

Sag

A span L with conductor weight w per meter and horizontal tension H hangs nearly as a parabola, with midspan sag and conductor length

d=wL28H,S=L+8d23L

Heating lengthens the conductor by αtSΔT (αt≈19×10−6 per °C for ACSR), and the sag follows from the length: d=3L(S−L)/8. Because S − L is small, a fraction of a meter of extra length adds meters of sag. Ignoring the conductor's elastic stretch gives an upper estimate; the tension falls as it sags, and the true increase is somewhat less.

Worked example

Find the ampacity of Drake ACSR (D = 28.1 mm, R = 0.087 Ω/km at 75 °C) at 75 °C in 25 °C air, with h = 15 W/m²K, ε = α = 0.5 and 1000 W/m² of sun.

Show the solution
  1. Convective cooling. qc=15π(0.0281)(50)=66.2W/m
  2. Radiative cooling. qr=0.5σπ(0.0281)×(348.154−298.154)=17.0W/m
  3. Solar heating. qs=0.5×1000×0.0281=14.1W/m
  4. Ampacity. The I2R heating, with R = 8.7 × 10⁻⁵ Ω/m, balances the net cooling: I=(qc+qr−qs)/R=892A
  5. What does the work. Convection does most of the work; radiation helps a little and the sun takes some back.

Answer about 892 A.

Worked example

A 300 m span of conductor weighing 15.97 N/m hangs at 28 kN horizontal tension. How much does its sag grow if the conductor heats by 50 °C, ignoring elastic stretch?

Show the solution
  1. Sag now. d=15.97×30028×28000=6.42m
  2. Conductor length. S=300+8(6.42)2/900=300.366m
  3. Thermal stretch. Heating adds ΔS=19×10−6×50×300.37=0.285m so S − L = 0.651 m.
  4. New sag. d=3×300×0.651/8=8.56m
  5. Compare. That's 2.1 m more sag from a stretch of only 9.5 cm per 100 m.

Answer the sag grows by 2.1 m, from 6.42 m to 8.56 m.

Worked example

On a day when the breeze doubles h to 30 W/m²K, what can the Drake conductor carry at the same 75 °C?

Show the solution
  1. Convection doubles. qc doubles to 132.4 W/m.
  2. New ampacity. I=132.4+17.0−14.18.7×10−5=1247A 40% more.
  3. Why ratings vary. The same conductor in still air would be good for less than two-thirds of its breezy rating, which is why a single static number is a compromise.

Answer 1247 A, 40% more than at h = 15 W/m²K.

Check

A conductor of diameter 28.1 mm with 0.05 Ω/km at its 100 °C limit sits in 25 °C air with h = 30 W/m²K, ε = α = 0.5 and 1000 W/m² of sun.

(a)

What net cooling is available per meter at the limit?

Write units the way you normally would: 1.5 W/m, 1500 mW/m and 0.0015 kW/m are the same answer.

(b)

What is its ampacity?

Check

A span of 150 m has conductor weighing 16 N/m at a horizontal tension of 50 kN.

(a)

What is its sag?

Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.

(b)

How much longer than the span is the conductor?

Check

A span of 300 m sags 4 m. Its ACSR conductor (αt = 19 × 10⁻⁶ per °C) heats by 80 °C; ignore elastic stretch.

(a)

How much longer does it get?

Write units the way you normally would: 1.5 cm, 15 mm and 0.015 m are the same answer.

(b)

What is the new sag?

Check

A conductor at its limit loses 50 W/m by convection and 10 W/m by radiation and gains 15 W/m from the sun. The wind then multiplies convection by 3.

(a)

By what factor does its ampacity rise?

Check

A conductor's resistance is 0.06 Ω/km at 20 °C, rising 0.0039 per °C.

(a)

What is it at 100 °C?

Write units the way you normally would: 1.5 Ω/km, 1500 mΩ/km and 0.0015 kΩ/km are the same answer.

Check

A conductor has 1.6 kg/m of mass with specific heat 900 J/kg·K, and its net cooling rises 4 W/m per kelvin near its operating point.

(a)

What is its thermal time constant?

Check

Why does a line's sag, rather than the conductor's own temperature limit, often set its rating?

Check

A span L (m) has conductor weight w (N/m) at tension H (N); the conductor then heats by t with expansion coefficient a.

Step 1

What is the sag?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Check

Write ampacity(D, R, h, Tc, Ta, eps, alpha, S) from the heat balance (D in m, R in Ω/m at Tc, temperatures in °C), and conductor_temp(I, D, R20, a, h, Ta, eps, alpha, S): the steady temperature for current I with R=R20(1+a(T−20)), by bisection between Ta and 300 °C.

Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.

Explain why

Why are dynamic line ratings able to unlock so much transmission capacity?