S10 · Lesson 15 · Line lab
Computing a line's inductance and capacitance from its geometry, its exact ABCD constants, the sending-end conditions for a load, and the voltages a Bewley lattice predicts as surges bounce between the ends
Lessons 4 to 14 turned a line's geometry into parameters, its parameters into ABCD constants, and its ends into reflection coefficients. In this lab you'll write the code a line-design or switching study runs: parameters from the tower layout, exact long-line constants with complex hyperbolic functions, the sending-end voltage a load demands, and a lattice that follows a switching surge as it bounces between the ends.
- The curve is the receiving-end voltage of a lossless line energized through a source resistance onto an open end, as a Bewley lattice predicts it, in units of the source voltage, against time in one-way travel times.
- With the source matched to the line (ρ_S = 0), the far end jumps to 1 at t = 1 and stays; with a stiff source (ρ_S = −1) it jumps to 2 and swings between 2 and 0 forever, since nothing absorbs energy.
- In between, the swings decay geometrically, by the factor ρ_S at each round trip.
Predict
A stiff 1 pu source (zero internal impedance) energizes an unloaded line. What does the far end's voltage do in the lossless model?
The wave of 1 pu doubles on reflection at the open end, so the far end jumps to 2 pu. The reflected wave returns to the source, which reflects it with ρ = −1, and the cancelling wave reaches the far end two travel times later, doubled again: 2 − 2 = 0. With no loss and no resistance, the far end alternates 2, 0, 2, 0, which is why closing resistors and real losses matter so much in switching studies.
Name it
What the lab computes
- Parameters: , bundle GMR and equivalent radius for two conductors; and .
- Long line: with z and y per kilometer, , , , , , and AD − BC = 1.
- Sending end: with receiving-end line-to-neutral voltage and current , and .
- Lattice: a step V through source resistance launches ; each arrival at the far end multiplies by there and returns with ; each return to the source reflects with .
Check
Write line_LC(D12, D23, D31, Ds, r, d): the per-meter L and C of a transposed line with two-conductor bundles (conductor GMR Ds, radius r, bundle spacing d, all in meters).
Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.
Check
Write abcd_long(z, y, l): the exact (A, B, C, D) of a line with complex series impedance z (Ω/km) and shunt admittance y (S/km), l km long.
Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.
Check
Write sending_end(A, B, C, D, VLL_kV, P_MW, Q_Mvar): the sending-end line-to-line voltage magnitude in kV for a receiving end at VLL_kV delivering P + jQ (three-phase).
Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.
Check
Write lattice(V, Zc, Rs, rho_R, t, T): the receiving-end voltage at time t of a lossless line (one-way travel time T) energized at t = 0 by a step V through source resistance Rs, with receiving-end reflection coefficient rho_R. Sum the arrivals at t = T, 3T, 5T, and so on.
Python 3.14 with numpy and matplotlib, running in your browser. Tab indents; press Esc and then Tab to move on.
Explain why
Why do switching studies care about the source impedance behind a breaker when energizing a long, unloaded line?
When a breaker closes onto a line, the wave launched down the line is set by the source voltage divided between the source impedance and the line's surge impedance, and the open far end doubles it. That reflection travels back to the source, which reflects it again with a coefficient set by how the source impedance compares with the surge impedance. A stiff source with almost no impedance reflects with a negative sign and nearly full strength, so the waves keep reinforcing and cancelling at the far end and the overvoltage persists, while a source impedance close to the surge impedance absorbs the returning wave. That's why breakers on long lines use closing resistors briefly inserted at the moment of closing, and why losses and the timing of the closing relative to the voltage wave matter so much.