S10 · Lesson 6 · Transmission line models
Short, medium and long line models, ABCD parameters, the propagation constant and wavelength at 60 Hz, the Ferranti rise of an open line, charging vars, and how a line's receiving voltage depends on its loading relative to SIL
At 60 Hz a wavelength is about 5000 km, so most power lines are electrically short and a lumped model works. But even a 200 km line has enough capacitance that, left open at the far end, its voltage there rises above the sending end: the Ferranti effect, which once surprised the engineers of London's first high-voltage cables. This lesson builds the models of increasing accuracy that power-flow programs use for lines, and shows how a line's voltage profile depends on whether it's loaded above or below its natural loading.
- The receiving-end voltage of a lossless line held at 1 pu at the sending end, against line length, for a resistive load given as a multiple k of the surge impedance loading.
- At k = 1 (natural loading) the voltage stays at 1 pu at every length: the line's own vars balance.
- Lighter loads let the voltage rise with length (k = 0 is the open line's Ferranti rise); heavier loads make it sag.
Predict
The 345 kV line of lesson 4 is 200 km long and open at the far end. If the sending end is held at 345 kV, what's the receiving-end voltage?
With no load, and for a lossless line. Here βl = 0.0729°/km × 200 km = 14.6°, so = 1.033 × 345 = 356 kV. The line's capacitive charging current flows through its own inductance and raises the voltage along the way.
Name it
ABCD parameters
Every line model relates sending-end and receiving-end voltage and current as
with total series impedance Z = zl and shunt admittance Y = yl:
- Short line (under about 80 km): A = D = 1, B = Z, C = 0.
- Medium line, nominal π (80 to 250 km): half of Y at each end. , B = Z, .
- Long line: distributed, with propagation constant and : , , .
Lossless lines
γ = jβ with , about 0.073°/km at 60 Hz (wavelength near 4940 km for overhead lines). Then and .
- Open line (Ferranti effect): , 3.3% up at 200 km, 7.7% at 300 km, 38% at 600 km.
- Charging: the line generates vars from its capacitance, about 0.53 Mvar per km for the 345 kV line.
- Loaded with resistance: if the load draws k times SIL at 1 pu, , flat at k = 1.
Regulation
, where the no-load value is .
Worked example
A 69 kV line 30 km long has z = 0.17 + j0.45 Ω/km and delivers 20 MW at 0.9 lagging at 69 kV. What sending voltage does it need?
Show the solution
- Use the short-line model. Per phase, the receiving voltage and the series impedance are
- Line current. at −25.8°.
- Sending voltage. or 72.44 kV line to line.
- Compare the ends. The sending end must be 5.0% higher than the receiving end.
Answer 72.44 kV line to line (41.83 kV per phase at 2.53°), 5.0% above the receiving voltage.
Worked example
Find the nominal-π A constant of the 200 km, 345 kV line (z = 0.03 + j0.363 Ω/km, y = j4.455 µS/km).
Show the solution
- Totals for the line.
- Half the ZY product.
- The A constant. and |A| = 0.9677.
- No-load voltage rise. matching the lossless long-line estimate of 1.0333.
- Line charging. The line generates
Answer A = 0.9677 + j0.0027, so an open line's far end rises to 1.0334 times the sending voltage; the line generates 106 Mvar.
Worked example
A lossless line is 500 km long (wavelength 4940 km). Compare its exact A constant with the nominal π's, and the open-circuit voltage rise each predicts.
Show the solution
- Electrical length. which is 36.4°.
- Exact A constant. so an open line's far end rises to 1/0.805 = 1.243 times the sending voltage.
- Nominal-π A constant. which predicts a rise of 1.253.
- Compare. The two are close at this length, and the nominal π grows increasingly wrong beyond it.
Answer exactly, A = 0.805 and the far end rises to 1.243 times the sending voltage; the nominal π gives A = 0.798 and a rise of 1.253.
Check
An open overhead line 300 km long (wavelength 4940 km). What's its receiving-end voltage relative to the sending end?
Check
A lossless line has L = 1.1 mH/km and C = 9 nF/km. What's its phase constant per km at 60 Hz?
Check
A 345 kV line with B = 3 µS/km is 200 km long. About how many vars does its capacitance generate at rated voltage?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
Check
A lossless line with x = 0.3 Ω/km and b = 3 µS/km is 250 km long. What's its nominal-π A constant?
Check
A lossless 400 km line (wavelength 4940 km) carries a resistive load of 0.5 times its SIL. What's the receiving voltage in per unit of the sending voltage?
Check
A short line with Z = 1 + j8 Ω delivers 20 MW at unity power factor and 34.5 kV. How much higher must the sending voltage be?
Check
A lossless overhead line is 400 km long (wavelength 4940 km).
(a)
What is its exact A constant?
(b)
What does the nominal π give?
(c)
How far does the open far end rise, as a multiple of the sending voltage?
Check
A short line (R + jX ohms) delivers P MW and Q Mvar at V kV.
Step 1
About how many kV does the voltage drop along the line?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
How many MW does it lose?
Explain why
Why does an open-ended line's voltage rise along its length?
Even with nothing connected at the far end, the line's shunt capacitance draws a charging current that leads the voltage by 90°. That current flows through the line's series inductance, and the voltage across an inductance carrying a leading current points opposite to the source voltage's direction of drop: it adds to the voltage instead of subtracting. Each section of the line therefore raises the voltage a little more, so the far end ends up highest. At 60 Hz this is a few percent on a 200 km line and grows quickly with length, which is why long lines carry shunt reactors that absorb the charging vars when lightly loaded.
Practice
Keep practicing
10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.