S10 · Lesson 4 · Transmission line parameters

Series resistance, inductance from geometric mean radius and distance, transposition, bundled conductors, shunt capacitance, and the surge impedance and surge impedance loading that follow from them

An overhead line is three bare conductors hung meters apart in air, and its behavior is set almost entirely by geometry. The magnetic flux between the conductors gives the line its series inductance, the electric field gives it shunt capacitance, and both depend only logarithmically on spacing and conductor size. That's why lines from 69 to 765 kV all have reactances within a factor of two of each other, and why splitting each phase into a bundle of conductors is the main lever designers have.

  • A three-phase line's inductance and capacitance per kilometer against the geometric mean spacing between phases, for a chosen conductor radius.
  • Both depend on the logarithm of spacing over size: doubling the spacing raises L by only 0.14 mH/km.
  • Bundling acts like a much fatter conductor, cutting L and raising C, which lowers the surge impedance and raises how much power the line carries naturally.

Predict

A 345 kV line's single conductors (radius 14 mm) are replaced by two-conductor bundles 45 cm apart. What happens to the series reactance?

Name it

Resistance

R=ρl/A at DC, raised a few percent by skin effect at 60 Hz and by temperature (aluminum: about 0.4% per °C).

Inductance

For a transposed three-phase line (each phase takes each position for a third of the length):

L=2×10−7ln⁡DmDsH/m,Dm=D12D23D313

Dm is the geometric mean distance between phases and Ds the conductor's geometric mean radius: re−1/4 = 0.7788r for a solid round conductor, and listed in tables for stranded ones.

Bundles

n conductors on a circle, spacing d, act like one with GMR Dsd (two), Dsd23 (three) or 1.091Dsd34 (four).

Capacitance

C=2πε0ln⁡(Dm/r)=55.63ln⁡(Dm/r)pF/m (to neutral)

with the outer radius r (or rd for a two-conductor bundle, and so on).

Surge impedance and SIL

A lossless line has Zc=L/C, typically 250 to 400 Ω for overhead lines and 30 to 60 Ω for cables. Loaded with Zc, a line neither absorbs nor produces net vars: its surge impedance loading is SIL=VL2/Zc.

Worked example

A 345 kV line has phases in a flat row 7 m apart, two-conductor bundles 0.45 m apart, and conductors of radius 14.07 mm and GMR 11.37 mm. Find its parameters.

Show the solution
  1. Mean phase spacing. Dm=7×7×143=8.82m
  2. Inductance. The bundle's GMR is 0.01137×0.45 = 71.5 mm, so L=0.2ln⁡(8.82/0.0715)=0.963mH/km and X = 0.363 Ω/km at 60 Hz.
  3. Capacitance. For capacitance the bundle radius is 0.01407×0.45 = 79.6 mm, so C=55.63ln⁡(8.82/0.0796)=11.8nF/km and B = 4.45 µS/km.
  4. Surge impedance and SIL. Zc=L/C=285ΩSIL=3452/285=417MW

Answer L = 0.963 mH/km (X = 0.363 Ω/km), C = 11.8 nF/km (B = 4.45 µS/km), Zc = 285 Ω and SIL = 417 MW.

Worked example

What would the same line be with single conductors?

Show the solution
  1. Inductance. L=0.2ln⁡(8.82/0.01137)=1.33mH/km which is 0.502 Ω/km.
  2. Capacitance. C=55.63ln⁡(8.82/0.01407)=8.64nF/km
  3. Surge impedance and SIL. These come to Zc = 393 Ω and SIL = 303 MW.
  4. Compare with the bundle. The bundle raises the natural loading by 38% on the same towers.

Answer L = 1.33 mH/km (0.502 Ω/km), C = 8.64 nF/km, Zc = 393 Ω and SIL = 303 MW; the bundled line's SIL is 38% higher.

Worked example

A 500 kV line has a geometric mean distance of 12 m, and its bundles have an effective GMR of 0.15 m and an effective radius of 0.17 m. Find L, C, the surge impedance and the SIL.

Show the solution
  1. Inductance. L=2×10−7ln⁡(12/0.15)=0.876mH/km
  2. Capacitance. C=2πϵ0ln⁡(12/0.17)=13.07nF/km
  3. Surge impedance. Zc=L/C=259Ω
  4. Surge impedance loading. SIL=5002/259=965MW
  5. Why bundles help. Bundling lowers L and raises C together, which is how extra-high-voltage lines reach SILs near 1000 MW.

Answer L = 0.876 mH/km, C = 13.07 nF/km, Zc = 259 Ω and SIL = 965 MW.

Check

Phase spacings are 7, 5 and 15 m. What's the geometric mean distance?

Write units the way you normally would: 1.5 m, 1500 mm and 0.0015 km are the same answer.

Check

A transposed line has Dm = 8 m and conductor GMR 8 mm. What's its inductance per kilometer?

Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.

Check

A two-conductor bundle uses conductors of GMR 8 mm spaced 0.3 m. What's its effective GMR?

Write units the way you normally would: 1.5 mm, 1500 µm and 0.0015 m are the same answer.

Check

A line has Dm = 9 m and conductor radius 10 mm. What's its capacitance to neutral per kilometer?

Write units the way you normally would: 1.5 nF, 1500 pF and 0.0015 µF are the same answer.

Check

A 500 kV line has L = 1 mH/km and C = 9 nF/km. What's its surge impedance loading?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

Check

A line of solid round conductors, radius 10 mm, has Dm = 5 m. What's its 60 Hz series reactance per km?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

Check

A line has a geometric mean distance of 12 m, effective bundle GMR 0.1 m and effective radius 0.18 m, at 500 kV.

(a)

What is its inductance per kilometer?

Write units the way you normally would: 1.5 mH/km, 1500 µH/km and 0.0015 H/km are the same answer.

(b)

What is its surge impedance?

(c)

What is its SIL?

Check

A transposed line has GMD D, GMR s and radius r, all in meters.

Step 1

What is L per meter?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why do transmission lines of very different voltages have similar reactances per kilometer?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.