S10 · Lesson 2 · The per-unit system

Choosing power and voltage bases, base current and impedance, converting impedances between bases, why per-unit values pass straight through transformers, and solving a generator-transformer-line circuit in per unit

A power system mixes 13.8 kV generators, 345 kV lines and 480 V motors, so the same fault current is thousands of amperes on one side of a transformer and hundreds on the other. Engineers sidestep the bookkeeping by expressing every quantity as a fraction of a chosen base. In per unit, transformers vanish from the circuit, the impedances of machines of very different sizes fall in narrow, familiar ranges, and mistakes stand out: a generator reactance of 15 pu is obviously wrong. Every later lesson works in per unit.

  • The base impedance Zbase=Vbase2/Sbase against the base voltage, for a chosen power base.
  • On a 100 MVA base it's 1.9 Ω at 13.8 kV and 1190 Ω at 345 kV. A per-unit impedance is the ohmic value divided by the base at its own voltage level.
  • That's why a 345 kV line of 200 Ω and a generator of 0.38 Ω can both be about 0.17 to 0.2 pu.

Predict

A generator's nameplate says X'' = 0.2 pu on its own 50 MVA, 13.8 kV rating. What is it on a 100 MVA, 13.8 kV system base?

Name it

Bases

Choose a three-phase power base Sbase (MVA, one value for the whole system) and a line-to-line voltage base Vbase (kV) in one zone. Then

Ibase=Sbase3Vbase,Zbase=Vbase2Sbase

and any quantity in per unit is its actual value divided by its base.

Across transformers

Each transformer's rated voltages set the voltage bases on its two sides, in the ratio of its turns. With bases chosen this way, a transformer's per-unit impedance is the same seen from either side, and the ideal transformer becomes 1:1: it disappears from the per-unit circuit.

Changing base

Equipment data come on the equipment's own rating. To move to the system base:

Znew=Zold(VoldVnew)2SnewSold

Typical values (on own rating)

Generator subtransient reactance 0.1 to 0.3 pu, transformer leakage reactance 0.05 to 0.15 pu, and a line's series impedance a few tenths of a per unit on 100 MVA at its voltage for a long line.

Worked example

A 13.8 kV generator (X'' = 0.4 pu on 100 MVA) feeds a 13.8/345 kV transformer (X = 0.1 pu) and a 345 kV line of 40 + j200 Ω. Find the current for a three-phase short at the line's far end.

Show the solution
  1. Line in per unit. On 100 MVA the 345 kV base impedance is Zbase=3452/100=1190.25Ω so the line is 0.0336 + j0.168 pu.
  2. Total impedance. Adding the generator's j0.4 and the transformer's j0.1: Z=0.0336+j0.668|Z|=0.669pu
  3. Fault current in per unit. With the generator's internal voltage at 1 pu: If=1/0.669=1.495pu
  4. Line side in amperes. On the 345 kV side, Ibase = 167.3 A: I=1.495×167.3=250A
  5. Generator side in amperes. On the generator side, Ibase = 4,184 A: I=1.495×4184=6.25kA One per-unit current, two very different amperes.

Answer 1.495 pu, which is 250 A on the 345 kV line and 6.25 kA in the generator.

Worked example

A 25 MVA transformer has X = 0.08 pu on its rating at 13.2 kV. What is it on 100 MVA and 13.8 kV?

Show the solution
  1. Change both bases. X=0.08(13.213.8)210025=0.293pu
  2. What each correction does. Both corrections matter: the larger power base quadruples it, and the slightly higher voltage base trims it by 8.5%.

Answer 0.293 pu.

Worked example

A 10 MW induction motor at 0.85 power factor runs at its rated 4.16 kV. On a 100 MVA base, what is its current in per unit, and in amperes?

Show the solution
  1. Apparent power. S=10/0.85=11.76MVA=0.1176pu on 100 MVA.
  2. Per-unit current. At 1 pu voltage the per-unit current equals the per-unit apparent power: 0.1176 pu.
  3. Base current at 4.16 kV. Ibase=100×1063×4160=13880A
  4. Current in amperes. I=IpuIbase=1633A
  5. Check. Computing it directly gives the same: I=S3×4160V=1633A

Answer 0.1176 pu, which is 1633 A.

Check

What's the base impedance at 13.8 kV on a 10 MVA base?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

Check

What's the base current at 34.5 kV on 10 MVA?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

Equipment rated 25 MVA at 13.2 kV has X = 0.15 pu on its rating. What is it on 100 MVA at 14.4 kV?

Check

A 115 kV line has a series reactance of 40 Ω. What is it in per unit on 100 MVA?

Check

A 4.16/138 kV transformer has X = 0.05 pu on 100 MVA. How many ohms is that seen from the 138 kV side?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

Check

A source of 1 pu behind a total of 0.6 pu (100 MVA base) is shorted. What's the current in kA at 13.8 kV?

Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.

Check

A load takes 10 MW at power factor 0.8 and its rated 69 kV. Work on a 100 MVA base.

(a)

What is its current in per unit, at 1 pu voltage?

(b)

What is that in amperes?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A system uses base power S MVA and base voltage V kV; a line has X ohms.

Step 1

What is the base impedance in ohms?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does choosing voltage bases in the ratio of a transformer's turns make the transformer disappear from the per-unit circuit?